Trane Precedent YHJ072 Installation, Operation And Maintenance Manual page 48

Packaged rooftop air conditioners cooling and gas/electric
Table of Contents

Advertisement

Installation
Figure 70. Examples
Note: Wiring pin numbers are for reference only. There are
multiple smoke detector systems that could have
differently numbered pins. For correct wiring details,
refer to the specific smoke detector, ship-with
literature.
Table 11. Temperature vs. resistance
Temperature
Degrees °F
Degrees °C
-20
-28.9
-15
-26.1
-10
-23.3
-5
-20.6
0
-17.8
48
Nominal Resistance
(kOhms)
170.1
143.5
121.4
103.0
87.56
Table 11. Temperature vs. resistance (continued)
Temperature
Degrees °F
Degrees °C
5
-15.0
10
-12.2
15
-9.4
20
-6.7
25
-3.8
30
-1.1
35
1.7
40°
4.4
45°
7.2
Nominal Resistance
(kOhms)
74.65
63.80
54.66
46.94
40.40
34.85
30.18
26.22
22.85
RT-SVX075C-EN

Advertisement

Table of Contents
loading

This manual is also suitable for:

Precedent yhj300

Table of Contents