Keri Systems B100-KP Setup Manual page 8

Fingerprint reader
Table of Contents

Advertisement

EP Controller Notes
BioSync readers have two LED lines but the EP controllers only have one LED pin-
l
out. This is overcome by wiring the Red LED wire into the buzzer pin-out (pin 4) and
in Doors.NET you have to set the BioSync reader as being a Dual LED reader type.
- In Doors.NET go to Setup >> Hardware Setup >> All.
- Locate and highlight the BioSync reader in the hardware tree.
- Ensure
Advanced View
- Locate LED/Buzzer.
- Set the reader for Separate Red and Green, No Buzzer.
Note:
This will set the controller to use the buzzer for controlling the second LED line and
because of this the reader does not generate any sound when the door is forced or held
open.
When using BioSync readers with EP controllers you have to use custom LED Modes
l
to define the LED behavior for the various reader modes (i.e - access granted,
access denied, locked, unlocked, lockdown, etc). Setting up and using
Modes
is covered in a separate section and available as a standalone document
(p/n: 02315-001).
                                                                       - 8 -                                          P/N: 02384-001 - Rev C
is enabled for the reader properties.
BioSync Fingerprint Readers