The function has to be set before connecting the relay to the supply voltage.
E | ON delay |
R | OFF delay |
Ws* | Single shot leading edge with control input (only TRL07) |
Wa* | ingle shot trailing edge with control input (only TRL07) |
Es* | ON delay with control input (only TRL07) |
Wu | Single shot leading edge voltage controlled |
Bp | Flasher pause first |
* Only available on TRL07
Time range | Adjustment range | |
1s | 50ms | 1s |
10s | 500ms | 10s |
1min | 3s | 1min |
10min | 30s | 10min |
1h | 3min | 1h |
10h | 30min | 10h |
100h | 5h | 100h |
Green LED U/t ON: indication of supply voltage
Green LED U/t flashes: indication of time period
Yellow LED R ON/OFF: indication of relay output
Self-extinguishing plastic housing, IP rating IP40
Mounted on DIN-rail TS 35 according to EN 60715
Mounting position: any
Shockproof terminal connection according to VBG 4 (PZ1 required), IP rating IP20
Tightening torque: max. 1Nm
Terminal capacity:
1 x 0.5 to 2.5mm² with/without multicore cable end
1 x 4mm² without multicore cable end
2 x 0.5 to 1.5mm² with/without multicore cable end
2 x 2.5mm² flexible without multicore cable end
Supply voltage: | 24V to 240V AC/DC |
Terminals: | A1(+)-A2 |
Tolerance: | -15% to +10% |
Rated consumption: | 4VA (1.5W) |
Rated frequency: | AC 48 to 63Hz |
Duty cycle: | 100% |
Reset time: | 100ms |
Residual ripple for DC: | 10% |
Drop-out voltage: | >30% of minimum rated supply voltage |
Overvoltage category: | III (in accordance with IEC 60664-1) |
Rated surge voltage: | 4kV |
1 potential free change over contact | |
Rated voltage: | 250V AC |
Switching capacity: | 2000VA (8A / 250V) |
Fusing: | 8A fast acting |
Mechanical life: | 20 x 10 6 operations |
Electrical life: | 2 x 10 5 operations at 1000VA resistive load |
Switching frequency: | max. 6/min at 1000VA resistive load (in accordance with IEC 60947-5-1) |
Overvoltage category: | III (in accordance with IEC 60664-1) |
Rated surge voltage: | 4kV |
Input not potential free: | Terminals A1-B1 |
Loadable: | yes |
Max. line length: | 10m |
Trigger level (sensitivity): | automatic adaption to supply voltage |
Min. control pulse length: | DC 50 ms / AC 100 ms |
Base accuracy: | ±1% of maximum scale value |
Adjustment accuracy: | <5% of maximum scale value |
Repetition accuracy: | <0.5% or ±5ms |
Voltage influence: | - |
Temperature influence: | ≤0.01% / °C |
Ambient temperature: | -25 to +55°C |
Storage temperature: | -25 to +70°C |
Transport temperature: | -25 to +70°C |
Relative humidity: | 15% to 85% (in accordance with IEC 60721-3-3 class 3K3) |
Pollution degree: | 2, if built in 3 (in accordance with IEC 60664-1) |
Single packing: 72g
When the supply voltage U is applied, the set interval t begins (green LED U/t flashes). After the interval t has expired (green LED U/t illuminated) the output relay R switches into on-position (yellow LED illuminated). This status remains until the supply voltage is interrupted. If the supply voltage is interrupted before the expiry of the interval t, the interval already expired is erased and is restarted when the supply voltage is next applied.
The supply voltage U must be constantly applied to the device (green LED U/t illuminated). When the control contact S is closed, the output relay R switches into on-position (yellow LED illuminated). If the control contact is opened, the set interval t begins (green LED flashes). After the interval t has expired (green LED U/t illuminated) the output relay switches into off-position (yellow LED not illuminated). If the control contact is closed again before the interval t has expired, the interval already expired is erased and is restarted.
The supply voltage U must be constantly applied to the device (green LED U/t illuminated). When the control contact S is closed, the output relay R switches into on-position (green LED U/t illuminated) and the set interval t begins (green LED U/t flashes). After the interval t has expired (green LED U/t illuminated) the output relay switches into off-position (yellow LED not illuminated). During the interval, the control contact can be operated any number of times. A further cycle can only be started when the cycle run has been completed.
The supply voltage U must be constantly applied to the device (green LED U/t illuminated).
Closing the control contact S has no influence on the condition of the output R. When the control contact is opened, the output relay switches into on-position (yellow LED illuminated) and the set interval t begins (green LED U/t flashes). After the interval t has expired (green LED U/t illuminated), the output relay switches into off-position (yellow LED not illuminated). During the interval, the control contact can be operated any number of times. A further cycle can only be started when the cycle run has been completed.
The supply voltage U must be constantly applied to the device (green LED U/t illuminated).
When the control contact S is closed, the set interval t begins (green LED U/t flashes). After the interval t has expired (green LED U/t illuminated) the output relay R switches into on-position (yellow LED illuminated). This status remains until the control contact is opened again. If the control contact is opened before the interval t has expired, the interval already expired is erased and is restarted with the next cycle.
When the supply voltage U is applied, the output relay R switches into on-position (yellow LED illuminated) and the set interval t begins (green LED U/t flashes). After the interval t has expired (green LED U/t illuminated) the output relay switches into off-position (yellow LED not illuminated). This status remains until the supply voltage is interrupted. If the supply voltage is interrupted before the interval t has expired, the output relay switches into off-position. The interval already is erased and is restarted when the supply voltage is next applied.
When the supply voltage U is applied, the set interval t begins (green LED U/t flashes). After the interval t has expired, the output relay R switches into on-position (yellow LED illuminated) and the set interval t begins again. After the interval t has expired, the output relay switches into off-position (yellow LED not illuminated). The output relay is triggered at a ratio of 1:1 until the supply voltage is interrupted.
Never carry out work on live parts! Danger of fatal injury! The product must not be used in case of an obvious damage. To be installed by an authorized person.
Here you can download full pdf version of manual, it may contain additional safety instructions, warranty information, FCC rules, etc.