Eaton TRL04, TRL07 - Timer Technical Data

Technical data

Functions

The function has to be set before connecting the relay to the supply voltage.

E ON delay
R OFF delay
Ws* Single shot leading edge with control input (only TRL07)
Wa* ingle shot trailing edge with control input (only TRL07)
Es* ON delay with control input (only TRL07)
Wu Single shot leading edge voltage controlled
Bp Flasher pause first

* Only available on TRL07

Time ranges

Time range Adjustment range
1s 50ms 1s
10s 500ms 10s
1min 3s 1min
10min 30s 10min
1h 3min 1h
10h 30min 10h
100h 5h 100h

Indicators

Green LED U/t ON: indication of supply voltage
Green LED U/t flashes: indication of time period
Yellow LED R ON/OFF: indication of relay output

Mechanical design

Self-extinguishing plastic housing, IP rating IP40
Mounted on DIN-rail TS 35 according to EN 60715
Mounting position: any
Shockproof terminal connection according to VBG 4 (PZ1 required), IP rating IP20
Tightening torque: max. 1Nm
Terminal capacity:
1 x 0.5 to 2.5mm² with/without multicore cable end
1 x 4mm² without multicore cable end
2 x 0.5 to 1.5mm² with/without multicore cable end
2 x 2.5mm² flexible without multicore cable end

Input circuit

Supply voltage: 24V to 240V AC/DC
Terminals: A1(+)-A2
Tolerance: -15% to +10%
Rated consumption: 4VA (1.5W)
Rated frequency: AC 48 to 63Hz
Duty cycle: 100%
Reset time: 100ms
Residual ripple for DC: 10%
Drop-out voltage: >30% of minimum rated supply voltage
Overvoltage category: III (in accordance with IEC 60664-1)
Rated surge voltage: 4kV

Output circuit

1 potential free change over contact
Rated voltage: 250V AC
Switching capacity: 2000VA (8A / 250V)
Fusing: 8A fast acting
Mechanical life: 20 x 10 6 operations
Electrical life: 2 x 10 5 operations at 1000VA resistive load
Switching frequency: max. 6/min at 1000VA resistive load (in accordance with IEC 60947-5-1)
Overvoltage category: III (in accordance with IEC 60664-1)
Rated surge voltage: 4kV

Control input

Input not potential free: Terminals A1-B1
Loadable: yes
Max. line length: 10m
Trigger level (sensitivity): automatic adaption to supply voltage
Min. control pulse length: DC 50 ms / AC 100 ms

Accuracy

Base accuracy: ±1% of maximum scale value
Adjustment accuracy: <5% of maximum scale value
Repetition accuracy: <0.5% or ±5ms
Voltage influence: -
Temperature influence: ≤0.01% / °C

Ambient conditions

Ambient temperature: -25 to +55°C
Storage temperature: -25 to +70°C
Transport temperature: -25 to +70°C
Relative humidity: 15% to 85% (in accordance with IEC 60721-3-3 class 3K3)
Pollution degree: 2, if built in 3 (in accordance with IEC 60664-1)

Dimensions

Dimensions

Weight

Single packing: 72g

Functions

ON delay (E)

When the supply voltage U is applied, the set interval t begins (green LED U/t flashes). After the interval t has expired (green LED U/t illuminated) the output relay R switches into on-position (yellow LED illuminated). This status remains until the supply voltage is interrupted. If the supply voltage is interrupted before the expiry of the interval t, the interval already expired is erased and is restarted when the supply voltage is next applied.
Functions - ON delay (E)

OFF delay (R)

The supply voltage U must be constantly applied to the device (green LED U/t illuminated). When the control contact S is closed, the output relay R switches into on-position (yellow LED illuminated). If the control contact is opened, the set interval t begins (green LED flashes). After the interval t has expired (green LED U/t illuminated) the output relay switches into off-position (yellow LED not illuminated). If the control contact is closed again before the interval t has expired, the interval already expired is erased and is restarted.
Functions - OFF delay (R)

Single shot leading edge with control input (Ws)

The supply voltage U must be constantly applied to the device (green LED U/t illuminated). When the control contact S is closed, the output relay R switches into on-position (green LED U/t illuminated) and the set interval t begins (green LED U/t flashes). After the interval t has expired (green LED U/t illuminated) the output relay switches into off-position (yellow LED not illuminated). During the interval, the control contact can be operated any number of times. A further cycle can only be started when the cycle run has been completed.
Single shot leading edge with control input (Ws)

Connections

Connections

Single shot trailing edge with control input (Wa)

The supply voltage U must be constantly applied to the device (green LED U/t illuminated).
Closing the control contact S has no influence on the condition of the output R. When the control contact is opened, the output relay switches into on-position (yellow LED illuminated) and the set interval t begins (green LED U/t flashes). After the interval t has expired (green LED U/t illuminated), the output relay switches into off-position (yellow LED not illuminated). During the interval, the control contact can be operated any number of times. A further cycle can only be started when the cycle run has been completed.
Single shot trailling edge with control input (Wa)

ON delay with control input (Es)

The supply voltage U must be constantly applied to the device (green LED U/t illuminated).
When the control contact S is closed, the set interval t begins (green LED U/t flashes). After the interval t has expired (green LED U/t illuminated) the output relay R switches into on-position (yellow LED illuminated). This status remains until the control contact is opened again. If the control contact is opened before the interval t has expired, the interval already expired is erased and is restarted with the next cycle.
ON delay with control input (Es)

Single shot leading edge voltage controlled (Wu)

When the supply voltage U is applied, the output relay R switches into on-position (yellow LED illuminated) and the set interval t begins (green LED U/t flashes). After the interval t has expired (green LED U/t illuminated) the output relay switches into off-position (yellow LED not illuminated). This status remains until the supply voltage is interrupted. If the supply voltage is interrupted before the interval t has expired, the output relay switches into off-position. The interval already is erased and is restarted when the supply voltage is next applied.
Single shot leading edge voltage controlled (Wu)

Flasher pause first (Bp)

When the supply voltage U is applied, the set interval t begins (green LED U/t flashes). After the interval t has expired, the output relay R switches into on-position (yellow LED illuminated) and the set interval t begins again. After the interval t has expired, the output relay switches into off-position (yellow LED not illuminated). The output relay is triggered at a ratio of 1:1 until the supply voltage is interrupted.
Flasher pause first (Bp)


Never carry out work on live parts! Danger of fatal injury! The product must not be used in case of an obvious damage. To be installed by an authorized person.

Documents / Resources

Download manual

Here you can download full pdf version of manual, it may contain additional safety instructions, warranty information, FCC rules, etc.

Download Eaton TRL04, TRL07 - Timer Technical Data

Advertisement

Need help?

Need help?

Do you have a question about the TRL04 and is the answer not in the manual?

Questions and answers

Table of Contents