13.12.5 Operation of the potential-free failure/alarm contact

The DMC 18 is equipped with a potential-free contact to indicate failures or alarm conditions.
Dryer is switched on and no service warning/alarm is active.
4
5
Dryer is off or a service warning/alarm is active.
4
5
13.12.6 How to change operating parameters – SETUP menu
The setup menu can be used to change the dryer's operating parameters.
Only qualified personnel must be allowed to access to the setup menu. The manufacturer is not
responsible for malfunctioning or failure due to modification to the operating parameters.
With dryer ON simultaneously press buttons
Access to the menu is confirmed by message
Set
Keep
pressed to display the value of the selected parameter and use arrows
the value. Release the button
Press
+
ID
HdS - High DewPoint Setting : Alarm threshold for a high
DewPoint (the alarm disappears when the temperature drop
0.5°C / 1°F below alarm point)
Hdd - High DewPoint Delay : high DewPoint alarm enable
delay
LdS - Low DewPoint Setting : Alarm threshold for a low
DewPoint (the alarm disappears when the temperature
becomes 0.5°C / 1°F higher than the alarm point)
Ldd – Low DewPoint Delay : low DewPoint alarm enable
delay
SrV - Service Setting: setting of service warning timer.
00 = service warning timer disabled.
SCL - Scale: display scale of temperatures.

13.12.7 Selection of the BEKOMAT drain model

The DMC18 controls two types of BEKOMAT drains.
The correct settings are carried out in the factory and proper functioning is checked during the final
inspection of the dryer
DRYPOINT® RAX 20-500 NA 1ph UL
Set
Set
to confirm the value and skip to following parameter.
to exit setup menu (if no button is pressed after 30 seconds the menu is exited automatically).
Description
+
for at least 5 seconds to enter the setup menu.
on the display (first parameter of menu).
Limits
0.0...25.0 °C
32 ... 77 °F
01 ... 20
minutes
-10 ... 0.0 °C
14 ... 32 °F
01 ... 20
minutes
0.0 ... 9.0
(x 1000)
hours
°C ... °F
Technical description
and
Resolution
0.5 °C
or
or
1 °F
1 min
0.5 °C
or
or
1 °F
1 min
0.5
(x1000) hours
-
to change
Standard
setup
20
or
68
15
-5
or
23
5
8.0
°F