7.4.2. OR Logic 1 / 2 / 3 / 4 / 5 / 6 / 7 / 8 ..............21 7.4.3. Linkage inputs of OR Logic ................ 21 Elsner Elektronik GmbH • Sohlengrund 16 • 75395 Ostelsheim • Germany Wind Sensor KNX W • from software version 1.00, ETS programme version 1.1...
Page 4
The change status (software version and date) can be found in the contents footer. If you have a device with a later software version, please check www.elsner-elektronik.de in the menu area "Service" to find out whether a more up-to- date version of the manual is available.
The output of each gate may optionally be configured as 1 bit or 2 x 8 bits Configuration is made using the KNX software ETS. The product file can be down- loaded from the Elsner Elektronik website on www.elsner-elektronik.de in the “Ser- vice” menu. 1.1. Deliverables •...
Installation and commissioning Current 230 V AC version max. 20 mA. 20...30 V DC version: max. 30 mA., max. 0,4 W. Residual ripple 10% Data output KNX +/- bus terminal plug Group addresses max. 254 Allocations max. 255 Communication objects Measurement range Wind 0...35 m/s Resolution (wind)
Elsner Elektronik is not liable for any changes in norms and standards which may occur after publication of these operating instructions. 2.1. Location Select an assembly location at the building where wind speed may be collected by the sensor unobstructedly.
Installation and commissioning Fig. 3 Horizontal The wind sensor must be mounted in the horizontal transverse direction (horizontally). 2.2. Mounting the sensor 2.2.1. Attaching the mount The sensor comes with a combination wall/pole mount. The mount comes adhered by adhesive strips to the rear side of the housing. Fasten the mount vertically onto the wall or pole.
Installation and commissioning Fig. 6 Different mounting arms are available from Els- ner Elektronik as additional, optional accessories for flexible installation of the weather station on a wall, pole or beam. Example of the use of a mounting arm: Due to flexible ball joints, the sensor can be brought into ideal position.
Installation and commissioning 2.2.3. Preparing the sensor Unsnap cover and remove upwards Fig. 9 Screw-on cover (230V device) Cover Snaps Bottom part of housing The sensor cover snaps in on the left and right along the bottom edge (see Fig.). The cover of the 230V model is also screwed on top.
Installation and commissioning Lead the cable for the voltage supply and bus connection through the rubber seals on the bottom of the device and connect Voltage L/N and Bus +/- to the terminals provid- Fig. 10 Remove the cable shielding under the circuit board and only feed the connector cables up- wards through the openings in the circuit board.
Installation and commissioning 20...30 V DC version Fig. 12 Tension clamp for voltage supply (20...30 V DC). Massive conductors of up to 1.5 mm² or conductors with fine wires. Terminal configu- ration independent from po- larity (+/- or -/+). Opening for the cable for the voltage supply and for bus ca- Slot for KNX clamp +/- Programming pushbutton for...
Installation and commissioning Fig. 14 With the 230V model, screw the cover on to the underpart, to prevent unauthorised or ac- cidental opening. DANGER! There is a risk to life from the live voltage on a 230 V device! • The cover must be screwed on in operation.
Addressing of the device at the bus The measured wind value and thus all other wind switching outputs may only be sup- plied 60 seconds after the supply voltage has been connected. After the auxiliary voltage has been applied, the device will enter an initialisation phase lasting a few seconds.
Transmission protocol 6. Transmission protocol Units of measurement: Wind in metre per second 6.1. List of all communication objects EIS types: Switching 1/0 Floating point value 8 bit value Abbreviations Flags: Communication Read W Write Transmit Name Function EIStype Flags Wind force measured value Output C R T...
Page 17
Transmission protocol Name Function EIStype Flags Wind threshold value 3 Increment C R W Wind threshold value3 Decrement C R W Wind threshold value 3 Switching output C R T Wind threshold value 3 Switching output C R W block AND Logic 1 Switching output C R T...
Page 18
Transmission protocol Name Function EIStype Flags OR Logic 4 8 bit output B C R T OR Logic 5 Switching output C R T OR Logic 5 8 bit output A C R T OR Logic 5 8 bit output B C R T OR Logic 6 Switching output...
Setting of parameters 7. Setting of parameters 7.1. General settings Maximum telegram quota 1 • 2 • 3 • 5 • 10 • 20 telegrams per second Wind force Measured value • do not send • send periodically • send in case of change •...
Page 20
Setting of parameters If the threshold value is set per Communication object: From the 1st communication onwards, the threshold value corresponds to the value of the communication object and is not multiplied by the factor 0.1. The value communicated last shall be •...
Setting of parameters If block of the switching output is used: Use block of the switching output Evaluation of the blocking object • if value 1: block | if value 0: release • if value 0: block | if value 1: release Value of the blocking object before 0 •...
Setting of parameters Communication object • in case of the change of logic AND Logic 1 sends • in case of the change of logic to 1 • in case of the change of logic to 0 • in case of the change of logic and cyclically •...