EN
Sewi KNX L-Pr
Presence detector with
brightness sensor
Item numbers 70396 (white), 70696 (jet black)
Installation and Adjustment

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the Sewi KNX L-Pr and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for Elsner Sewi KNX L-Pr

  • Page 1 Sewi KNX L-Pr Presence detector with brightness sensor Item numbers 70396 (white), 70696 (jet black) Installation and Adjustment...
  • Page 3: Table Of Contents

    8.9.2. AND logic connection inputs ..............38 8.9.3. Connection inputs of the OR logic ............. 40 Elsner Elektronik GmbH • Sohlengrund 16 • 75395 Ostelsheim • Germany Sensor Sewi KNX L-Pr • from application 1.1 Version 25.01.2021 • Errors excepted. Subject to technical changes.
  • Page 4 The change status (software version and date) can be found in the contents footer. If you have a device with a later software version, please check www.elsner-elektronik.de in the menu area "Service" to find out whether a more up-to- date version of the manual is available.
  • Page 5: Description

    Description Description The Sensor Sewi KNX L-Pr for the KNX building bus system captures brightness and the presence of persons in rooms. The brightness value measured can be used for the control of limit-dependent switching outputs. States can be linked via AND logic gates and OR logic gates.
  • Page 6: Safety And Use Instructions

    • Take the device or system out of service and secure it against unintentional use, if it can be assumed, that risk-free operation is no longer guaranteed. Sensor Sewi KNX L-Pr • Version: 25.01.2021 • Technical Changes and Errors excepted.
  • Page 7: Installation

    Elsner Elektronik is not liable for any changes in norms and standards which may occur after publication of these operating instructions.
  • Page 8: Connection

    The Sensor Sewi KNX L-Pr is surface-mounted but at the same time can also be screwed to a flush-mounted socket. If the Sensor Sewi KNX L-Pr is installed on a flush-mounted socket, it must not con- tain any wiring with 230 V.
  • Page 9: Assembly

    Fig. 5 Lead the bus cable through the cable bushing in the skirting. Fig. 6 Screw the skirting to the ceiling. Hole distance 60 mm. Sensor Sewi KNX L-Pr • Version: 25.01.2021 • Technical Changes and Errors excepted.
  • Page 10: Commissioning

    Disposal After use, the device must be disposed of or recycled in accordance with the legal reg- ulations. Do not dispose of it with the household waste! Sensor Sewi KNX L-Pr • Version: 25.01.2021 • Technical Changes and Errors excepted.
  • Page 11 Disposal Sensor Sewi KNX L-Pr • Version: 25.01.2021 • Technical Changes and Errors excepted.
  • Page 12: Transfer Protocol

    -WC- [7.5] DPT_Time- 2 bytes value 2: Delay from 1 to 0 PeriodSec Brightness sensor 2 threshold Output R-CT [1.1] DPT_Switch 1 bit value 2: Switching output Sensor Sewi KNX L-Pr • Version: 25.01.2021 • Technical Changes and Errors excepted.
  • Page 13 Depending on 4 bytes setting 1145 Computer 1: Output O2 Output R-CT Depending on 4 bytes setting 1146 Computer 1: Condition text Output R-CT [16.0] DPT_String_ASCII bytes Sensor Sewi KNX L-Pr • Version: 25.01.2021 • Technical Changes and Errors excepted.
  • Page 14 R-CT Depending on 4 bytes setting 1170 Computer 4: Condition text Output R-CT [16.0] DPT_String_ASCII bytes 1171 Computer 4: Monitoring status Output R-CT [1.1] DPT_Switch 1 bit Sensor Sewi KNX L-Pr • Version: 25.01.2021 • Technical Changes and Errors excepted.
  • Page 15 R-CT [16.0] DPT_String_ASCII bytes 1195 Computer 7: Monitoring status Output R-CT [1.1] DPT_Switch 1 bit 1196 Computer 7: Block (1: block) Input -WC- [1.1] DPT_Switch 1 bit Sensor Sewi KNX L-Pr • Version: 25.01.2021 • Technical Changes and Errors excepted.
  • Page 16 1416 AND logic 2: 8-bit output A Output R-CT [5.010] DPT_- 1 byte Value_1_Ucount 1417 AND logic 2: 8-bit output B Output R-CT [5.010] DPT_- 1 byte Value_1_Ucount Sensor Sewi KNX L-Pr • Version: 25.01.2021 • Technical Changes and Errors excepted.
  • Page 17 1444 OR logic 1: 8-bit output A Output R-CT [5.010] DPT_- 1 byte Value_1_Ucount 1445 OR logic 1: 8-bit output B Output R-CT [5.010] DPT_- 1 byte Value_1_Ucount Sensor Sewi KNX L-Pr • Version: 25.01.2021 • Technical Changes and Errors excepted.
  • Page 18 1472 OR logic 8: 8-bit output A Output R-CT [5.010] DPT_- 1 byte Value_1_Ucount 1473 OR logic 8: 8-bit output B Output R-CT [5.010] DPT_- 1 byte Value_1_Ucount Sensor Sewi KNX L-Pr • Version: 25.01.2021 • Technical Changes and Errors excepted.
  • Page 19 1547 Motion detector: Master 2: Slave Input -WC- [1.1] DPT_Switch 1 bit message 1548 Motion detector: Master 2: Slave Output --CT [5.1] 1 byte cycle reset DPT_Scaling Sensor Sewi KNX L-Pr • Version: 25.01.2021 • Technical Changes and Errors excepted.
  • Page 20 1570 Motion detector: Master 4: Central off Input -WC- [1.1] DPT_Switch 1 bit 1581 Light controller: Brightness setpoint Input/ RWCT [9.4] DPT_Val- 2 bytes value Output ue_Lux Sensor Sewi KNX L-Pr • Version: 25.01.2021 • Technical Changes and Errors excepted.
  • Page 21: Parameter Setting

    Behaviour on bus restoration of power and following programming or reset: The device sends all outputs according to their send behaviour set in the parameters with the delays established in the "General settings" parameter block. Sensor Sewi KNX L-Pr • Version: 25.01.2021 • Technical Changes and Errors excepted.
  • Page 22: General Settings

    0 • 1 [depending on the type of test object] Test object value without movement e.g. 0 • 1 [depending on the type of test object] Sensor Sewi KNX L-Pr • Version: 25.01.2021 • Technical Changes and Errors excepted.
  • Page 23: Master 1/2/3/4

    If the device is set as a master, the additional master settings 1 to 4 will appear. This enables the Sensor Sewi KNX L-Pr to perform four different control functions for motion detection. Activate the master in order to use it.
  • Page 24 Set the waiting period such that after it all lamps are set to the final brightness. The hysteresis is added to the measured bright- Sensor Sewi KNX L-Pr • Version: 25.01.2021 • Technical Changes and Errors excepted.
  • Page 25 0 s • 5 s • 10 s • ... 2 h (for setting via objects: valid until (for daylight dependent motion detection: 1st communication) fixed value 0s) Sensor Sewi KNX L-Pr • Version: 25.01.2021 • Technical Changes and Errors excepted.
  • Page 26 • at value 1: block | at value 0: release • at value 0: block | at value 1: release Value prior to first communication 0 • 1 Output pattern Sensor Sewi KNX L-Pr • Version: 25.01.2021 • Technical Changes and Errors excepted.
  • Page 27: Align Communication Between Master And Slave

    Set, in which cases the data received via object for setpoint value, setpoint value-ac- tual difference, dimming increment and times are to be retained. Please note that the Sensor Sewi KNX L-Pr • Version: 25.01.2021 • Technical Changes and Errors excepted.
  • Page 28 Define, up to which response value the dim actuator sends a brighter or darker com- mand. On the one hand, this defines the range of use for the lamp, on the other hand, Sensor Sewi KNX L-Pr • Version: 25.01.2021 • Technical Changes and Errors excepted.
  • Page 29 Sensor Sewi KNX L-Pr • Version: 25.01.2021 • Technical Changes and Errors excepted.
  • Page 30: Brightness Measurement

    • send off command • send on command • send value 8.5. Brightness Measurement The Sensor Sewi KNX L-Pr detects the brightness in rooms, for example for control- ling lights. Set the sending pattern for the measured brightness. Sending pattern • never •...
  • Page 31: Brightness Threshold Values

    Absolute value • Increase/decrease Increment in Lux 1 • 2 • 5 • 10 • 20 • 50 • 100 • 200 • 500 • 1000 (upon increase/decrease change) Sensor Sewi KNX L-Pr • Version: 25.01.2021 • Technical Changes and Errors excepted.
  • Page 32 The behaviour of the switching output on release is dependent on the value of the pa- rameter "Switching output sends" (see "Switching output") Switching output sends on change do not send message • Status object/s send/s Sensor Sewi KNX L-Pr • Version: 25.01.2021 • Technical Changes and Errors excepted.
  • Page 33: Night

    No • Yes (in seconds) Switching delay on night none • 1 s … 2 h Switching delay on day none • 1 s … 2 h Sensor Sewi KNX L-Pr • Version: 25.01.2021 • Technical Changes and Errors excepted.
  • Page 34: Computer

    (setting via objects is ignored). Maintain the input values received via communication • never objects • after power supply restoration • after power supply restoration and programming Sensor Sewi KNX L-Pr • Version: 25.01.2021 • Technical Changes and Errors excepted.
  • Page 35 • 4 byte counter without math. symbol • 4 byte counter with math. symbol • 4 byte floating point Output value (if applicable output value A1 / A2) Sensor Sewi KNX L-Pr • Version: 25.01.2021 • Technical Changes and Errors excepted.
  • Page 36 0 [Input range depending on the type of is exceeded output] if blocked 0 [Input range depending on the type of output] Sensor Sewi KNX L-Pr • Version: 25.01.2021 • Technical Changes and Errors excepted.
  • Page 37 No • Yes Analysis of the blocking object • At value 1: block | At value 0: release • At value 0: block | At value 1: release Sensor Sewi KNX L-Pr • Version: 25.01.2021 • Technical Changes and Errors excepted.
  • Page 38: Logic

    Each logic output may transmit one 1 bit or two 8 bit objects. Determine what the out put should send if logic = 1 and = 0. Sensor Sewi KNX L-Pr • Version: 25.01.2021 • Technical Changes and Errors excepted.
  • Page 39 0 … 255 / 100% / 360° / 127; 0 monitoring period is exceeded Output value object B if 0 … 255 / 100% / 360° / 127; 0 monitoring period is exceeded Sensor Sewi KNX L-Pr • Version: 25.01.2021 • Technical Changes and Errors excepted.
  • Page 40: And Logic Connection Inputs

    Output behaviour on exceeding the moni- • Do not send message toring time • Send value exceeding [= value of the parameter "monitoring period"] 8.9.2. AND logic connection inputs Do not use Sensor Sewi KNX L-Pr • Version: 25.01.2021 • Technical Changes and Errors excepted.
  • Page 41 Motion detector test output active Motion detector test output inactive Motion detector test output active Motion detector test output inactive Motion detector slave output active Motion detector slave output inactive Sensor Sewi KNX L-Pr • Version: 25.01.2021 • Technical Changes and Errors excepted.
  • Page 42: Connection Inputs Of The Or Logic

    Switching output AND logic 6 inverted Switching output AND logic 7 Switching output AND logic 7 inverted Switching output AND logic 8 Switching output AND logic 8 inverted Sensor Sewi KNX L-Pr • Version: 25.01.2021 • Technical Changes and Errors excepted.
  • Page 44 Elsner Elektronik GmbH Control and Automation Engineering Sohlengrund 16 75395 Ostelsheim Phone +49 (0) 70 33 / 30 945-0 info@elsner-elektronik.de Germany +49 (0) 70 33 / 30 945-20 www.elsner-elektronik.de Technical support: +49 (0) 70 33 / 30 945-250...