OPERATION OF THE ELECTRONIC UNIT

To access the configuration, calibration and manual mode menus, press the CAL button. The display will show the following
available options:

Standard Configuration

Advanced Configuration

Calibration IN1 (input 1) pH
Calibration IN2 (input 2) redox
Manual Mode 1 (pump 1, acid dosage)
Manual Mode 2 (pump 2, chlorine dosage)
Use the  /  keys to scroll the available options, then press CAL to enter the highlighted mode or ESC to return to
measurement visualization.
Standard Configuration
The standard configuration mode allows the customer to set a series of parameters related to the normal functioning of the
unit. These parameter can be freely accessed and configured from the front keyboard.
1) Once selected the "Standard Configuration" option, press
the CAL button to edit the list of parameters, or press ESC
to return to the normal visualization mode
2) Now use the
and
parameters
3) To modify the displayed parameter, press CAL; to quit the
mode press ESC
Advanced Configuration
The advanced configuration mode also includes the parameters protected by password, that allow a complete configuration
of the system. This mode is normally accessed only by authorized technical personnel.
1) Once selected the "Advanced Configuration" option, press
the CAL button to edit the list of parameters, or press ESC
to return to the normal visualization mode
2) Now use the
and
parameters
3) To modify the displayed parameter, press CAL; to quit the mode press ESC

List of Configuration Parameters

In this section are listed all the configuration parameters.
It is recommended to fill the last column with the values set for your application.
PAR.
Description
P01
Functioning Type Pump 1
P02
Setpoint Pump 1
P03
Hysteresis Pump 1
P04
Dosage Pump 1
Time Base Pump 1
P05
if P01= ON-OFF
if P01= Proportional
P06
Functioning Type Pump 2
P07
Setpoint Pump 2
P08
Hysteresis Pump 2
P09
Dosage Pump 2
Time Base Pump 1
P10
if P01= ON-OFF
if P01= Proportional
P11
Alarm Pump 1
P12
Alarm Pump 2
P13
Start Delay
P14
Language
P15
Restore default values
P16
Password
P17
Alarm Functioning
P18
Flow Functioning
P19
pH Equilibrium
keys to scroll the list of the available
keys to scroll the list of the available
Min Value
ON-OFF / Proportional
0.00pH
0.20pH
Acidification / Alkalinisation
5%
30 sec
ON-OFF / Proportional
0mV
20mV
Chlorination / De-chlorination
5%
30 sec
0min
0min
0min
Français – Español - Polish
0min
S T A N D A R D
C A L > Y E S
P 0 1
A D V A N C E D
C A L > Y E S
Max Value
14.00pH
2.00pH
100%
360 sec
1000mV
200mV
100%
360 sec
240min
240min
60min
Italiano - English
0
255
0
255
Relay NO / Relay NC
Input NO / Input NC
240min
C O N F I G .
E
S C > N O
>
F U N C . T Y P E
O n O f f
C O N F I G .
E S C > N O
Default Value
Set Value
ON-OFF
7.00pH
0.50pH
Acidification
60%
60 sec
ON-OFF
750mV
50mV
Chlorination
60%
60 sec
0min
0min
0min
English
0
0
Relay NO
Input NO
0min
P 1
21