Download Print this page

GE Lumination LRX Series Installation Manual page 3

Led luminaire construction frame

Advertisement

Lumination
(LRX - Series)
®
Bars
A
Option A: Mount fixture by attaching hanger bars to T-Grid
5
ceiling (BH3 SKU 94890).
Option B: Mount fixture with ½" EMT conduit.
Note: Supplied by 3rd party.
LRX-Series Mounting
AC line and dimming wires
Connect conduit end with input leads to existing junction box and make proper connections. Connect the black, white, and green/yellow
7
wires of the input leads to the black, white and green wires using twist-on wire connectors and close junction box.
Optional dimmer: When connecting with dimming controller, wires must be run through another separate knockout hole. Connect the
violet (dimming +) and gray (dimming -) wires to the violet and gray wires of the fixture.
NOTE: Please cover dimming leads with wire nuts if you won't connect with dimming leads.
Lumens Setting Switch
NOTE: For 1000/650lm product, default output lumen is 1000lm.
Push switch up to activate 650lm.
LED.com
© 2023 Current Lighting Solutions, LLC. All rights reserved. Information and specifications subject to change
without notice. All values are design or typical values when measured under laboratory conditions.
Conduit
B
Input and dimming
wires from J-box
Adjust height and
tighten wing nut
Adjust fixture height to be flush with ceiling and tighten
6
both mounting bracket wing nuts.
Wiring Diagram
L
N
Green/Yellow
Ground
0-10 Volt Dimming (Optional)
Gray
LED
Driver
Violet
Maximum Quantity Of Fixtures That Can Be
Connected With One Dimmer
No.
Dimmer Type
1
QSN - 4T16 - S
2
GRX TV1 with Grafik Eye QS Main Unit
3
NTFTV/NFTV/DVTV with PP - 120
4
TVM2 Module
5
TVI - LMF -2S
IND327-Lumination-LRX-Series-Square-LED-Luminaire-Installation-Guide_R01
Installation Guide
Black
White
LRX
Fixture
To 0-10V
0-10V –
Dimmer
0-10V +
Maximum
Fixture
Quantity
80
520
40
80
35
Page 3 of 4
(Rev 05/19/23)