Download Print this page

Chalmit NeoX Installation, Operation And Maintenance Instructions

Led emergency linear luminaire

Advertisement

Quick Links

NeoX (LED Emergency Linear Luminaire)
ATEX ,IECEx and UKEX
INSTALLATION, OPERATION AND MAINTENANCE INSTRUCTIONS
Important: Please read these instructions carefully before installing or maintaining this equipment.
Good electrical practices should always be followed, and this data should be used as a guide only.
Fig. 1
Note: EMI version will not have a battery entry
I-NOXB-02 IOM NeoX Zone 1 EM LED
1
Issue 1
28/11/2022
I-NOXB-02 IOM NeoX Zone 1 EM LED

Advertisement

loading

Summary of Contents for Chalmit NeoX

  • Page 1 I-NOXB-02 IOM NeoX Zone 1 EM LED NeoX (LED Emergency Linear Luminaire) ATEX ,IECEx and UKEX INSTALLATION, OPERATION AND MAINTENANCE INSTRUCTIONS Important: Please read these instructions carefully before installing or maintaining this equipment. Good electrical practices should always be followed, and this data should be used as a guide only.
  • Page 2 Wall mount option supplied not fitted with 4 x M6 ST/ST countersunk screws Specification Type of Protection Ex d Driver, LED Engine (flameproof and increased safety), Ex eb Housing (Increased safety), Ex tb Housing (Dust) Protection Standards EN/IEC 60079-0, EN/IEC 60079-1, EN/IEC 60079-7, EN/IEC 60079-18, EN/IEC 60079-31. Area Classification Zone 1 and Zone 2 areas to (IEC) EN60079-10-1 Zone 21 and Zone 22 areas to (IEC) EN60079-10-2...
  • Page 3: Special Conditions For Safe Use

    Customer Terminations as Follows: LCLC LSLS NN EE SPECIAL CONDITIONS FOR SAFE USE The hot swappable battery stick emergency versions, Before and after removal of battery stick assembly or battery stick entry stopping plug, ensure no dust or debris can enter the entry. The following relate to the installation and/or safe use of the equipment/component: i.
  • Page 4 The NeoX Luminaire operates from mains voltage. This installation leaflet covers the range of ATEX and IECEx NeoX Luminaire models. These luminaires are mainly used in harsh environments and are constructed using Non-corrosive materials. Refer to the current catalogue for information on product references.
  • Page 5 After a complete battery discharge, the unit will switch over to a low discharge current mode, until power restored. 4.1.5 Emergency Commissioning The NeoX is programmed to commence a self-test programmed test upon battery connection & energisation of mains power supply. This product will test the performance of the emergency Luminaire in accordance with IEC 62034. Unless the /NST (Non Self-Test option has been purchased) Please see section 3.0 for battery storage instructions.
  • Page 6 4.1.9 Replacement of Battery Replacement/ connection of Battery can only take place when there is NO Explosive gas or dust atmosphere present. The battery is supplied complete with throw away terminal connections. When removing battery pack, unscrew the two battery clamps disconnect wires coming from the battery terminal connections (wires from battery pack must be isolated individually) and remove battery assembly.
  • Page 7 M25 x 1.5 pitch 4.6.2 RCG Cable Entries The NeoX Luminaire has the option to come factory fitted with Hawke 501/RCG entries. The installer and user must take responsibility for the selection of cables and termination of the cables with Hawke 501/RCG bodies, which are required to hook up the cable to the 501/RCG entries.
  • Page 8 A damaged or non-resilient gasket must be replaced (supplied by Chalmit). The cover should be re-fitted with all screws fully tightened. Any replacement screws must be identical to the original.
  • Page 9 EU/UK-Declaration of conformity UE-Déclaration de conformité EU-Konformitätserklärung Manufacturer Chalmit Address 388 Hillington Road, Glasgow. G52 4BL Scotland UK Product NeoX (LED Emergency Bulkhead Luminaire) Notified Body CML B.V. 2776 CML 22ATEX1473X EU Type Examination Certificate Approved Body Eurofins CML 2503 CML 22UKEX1474X...
  • Page 10 Dieser Strahler widersteht Überspannungen bis 400V AC 1 Minute lang sowie Stoßspannungen von 4kV On behalf of the Chalmit, I declare that, on the date the equipment accompanied by this declaration is placed on the market, the equipment conforms to all technical and regulatory requirements of the above listed directives.