INSTALLATION, OPERATION AND MAINTENANCE INSTRUCTIONS
Protecta III – Zone 2(Ex ec) LED Luminaires for use
with Inotec Central Battery System (CBS)
ATEX, IECEx and UKEX
Important:
Please read these instructions carefully before installing or maintaining this equipment.
Good electrical practices should always be followed, and this data should be used
as a guide only.
MODEL SIZE
I-PR3C-03.doc
DIMENSION 'A'
02L
742
04L
742
07L
1352
Issue 03
17/01/2022
IOM – PROTECTA - LED Ex ec
DIMENSION 'B'
400
400
700
1

Advertisement

loading

Summary of Contents for Chalmit Protecta III 02L

  • Page 1 IOM – PROTECTA - LED Ex ec INSTALLATION, OPERATION AND MAINTENANCE INSTRUCTIONS Protecta III – Zone 2(Ex ec) LED Luminaires for use with Inotec Central Battery System (CBS) ATEX, IECEx and UKEX Important: Please read these instructions carefully before installing or maintaining this equipment. Good electrical practices should always be followed, and this data should be used as a guide only.
  • Page 2 IOM – PROTECTA LED Ex ec Type of Protection Ex ec, (non-sparking). Ex tc, Protection Standards EN/IEC 60079-0, EN/IEC 60079-7, EN/IEC 60079-31 Area Classification Zone 2 areas to EN/IEC 60079-10-1, Zone 22 areas to EN/IEC 60079-10-2. Installation EN/IEC 60079-14 Certificate Type EC CML 21ATEX3109X Type Examination Certificate CML 21UKEX31271X IECEx Certificate of Conformity IECEx CML 21.0008X...
  • Page 3 IOM – PROTECTA LED Ex ec 3.0 Installation and Safety 3.1 General There are no health hazards associated with this product whilst in normal use. However, care should be exercised during the following operations. In the UK the requirements of the 'Health and Safety at Work Act' must be met. Handling and electrical work associated with this product to be in accordance with the 'Manual Handling Operations Regulations' and 'Electricity at Work Regulations, 1989'.
  • Page 4 IOM – PROTECTA LED Ex ec Users must take care not to introduce wiring into parts of the apparatus materially different to that which could be reasonably inferred from the disposition of fixed supply terminals and specified wiring. 3.4 Light Emitting Diodes (LED) LED’s are supplied in either 2000, 4000 or 7000 Lumen options with the colour temperature of 3000K,4000K or 5000K.
  • Page 5 IOM – PROTECTA LED Ex ec The procedure for opening the cover is as follows: Insert the tool into one of the slots in the clamping bar with the end of the tool located into the outer flange of the body as a fulcrum point, a wide blade screwdriver is recommended.
  • Page 6 IOM – PROTECTA LED Ex ec Check any external and internal earths. Check all terminations are firmly screwed down, tighten if necessary. Check clips visually for any damage and replace, if necessary. If it has been suspected that the Luminaire has suffered mechanical damage, a stringent workshop check on all components should be made.
  • Page 7 IOM – PROTECTA LED Ex ec Table B - SCHEDULE – LED CONTROL GEAR – INOTEC MODULE – 230Vac 50/60Hz – 176 to 264Vdc Note: for Dust Ratings Refer to Max Surface Temperatures. Driver Power Line Inrush Current/ No. of strips Lumens Current Consumption...
  • Page 8 IOM – PROTECTA LED Ex ec I-PR3C-03.doc Issue 03 17/01/2022...
  • Page 9 IOM – PROTECTA LED Ex ec EU/UK-Declaration of conformity UE-Déclaration de conformité EU-Konformitätserklärung Manufacturer Chalmit Address 388 Hillington Road, Glasgow. G52 4BL Scotland UK Product Protecta Ill LED Inotec Central Battery System Notified Body CML B.V. 2776 Type Examination Certificate...