9-5. HOW TO CHECK THE PARTS
PEAD-RP60GA
PEAD-RP71GA
PEAD-RP100GA
Parts name
Room temperature
Disconnect the connector then measure the resistance using a tester.
thermistor
(TH1)
(Surrounding temperature 10:~30:)
Pipe temperature
thermistor
(TH2)
Condenser/Evaporator
temperature thermistor
(TH5)
Fan motor (MF)
Measure the resistance between the terminals using a tester (winding temp. 20°C).
Protector
RP60,71
RP100
OPEN
145±5°C
135±5°C
CLOSE
94±15°C
86±15°C
<Thermistor Characteristic graph>
Thermistor for
lower temperature
Thermistor R
=15k" ± 3%
0
Fixed number of B=3480k" ± 2%
Rt=15exp { 3480(
273+t
0:
15k"
10:
9.6k"
20:
6.3k"
25:
5.2k"
30:
4.3k"
40:
3.0k"
Normal
4.3k"~9.6k"
Open or short
Motor terminal
RP60, 71
Orange-Gray
35.0"
Orange-Black
10.3"
Black-Blue
5.87"
Blue-Yellow
6.97"
Yellow-Red
21.4"
Orange-Red
-
Room temperature thermistor(TH1)
Pipe temperature thermistor(TH2)
Condenser/evaporator temperature
thermistor(TH5)
1
1
) }
273
Check points
Abnormal
(Refer to the thermistor)
Normal
RP100
35.2"
2.63"
3.00"
7.01"
-
50.7"
Abnormal
Open or short
< Thermistor for lower temperature >
5
4
3
2
1
-2 -1
1
2
3
4
5
Temperature (
)
:
23