ABB RELION 670 Series Product Manual page 107

Transformer protection
Hide thumbs Also See for RELION 670 Series:
Table of Contents

Advertisement

Transformer protection RET670 2.1 IEC
Table 119. Phase-neutral voltage measurement VNMMXU
Function
Voltage
Phase angle
Table 120. Current sequence component measurement CMSQI
Function
Current positive sequence, I1
Three phase settings
Current zero sequence, 3I0
Three phase settings
Current negative sequence, I2
Three phase settings
Phase angle
Table 121. Voltage sequence measurement VMSQI
Function
Voltage positive sequence, U1
Voltage zero sequence, 3U0
Voltage negative sequence, U2
Phase angle
Table 122. Supervision of mA input signals
Function
mA measuring function
Max current of transducer
to input
Min current of transducer to
input
Alarm level for input
Warning level for input
Alarm hysteresis for input
ABB
GUID-ED634B6D-9918-464F-B6A4-51B78129B819 v5
Range or value
(5 to 175) V
(5 to 175) V
GUID-9B8A7FA5-9C98-4CBD-A162-7112869CF030 v4
Range or value
(0.1–4.0) × I
r
(0.1–1.0) × I
r
(0.1–1.0) × I
r
(0.1–4.0) × I
r
GUID-47094054-A828-459B-BE6A-D7FA1B317DA7 v6
Range or value
(10 to 300) V
(10 to 300) V
(10 to 300) V
(10 to 300) V
Range or value
±5, ±10, ±20 mA
0-5, 0-10, 0-20, 4-20 mA
(-20.00 to +20.00) mA
(-20.00 to +20.00) mA
(-20.00 to +20.00) mA
(-20.00 to +20.00) mA
(0.0-20.0) mA
Accuracy
±0.5% of U at U ≤ 50 V
±0.2% of U at U > 50 V
±0.5 degrees at U ≤ 50 V
±0.2 degrees at U > 50 V
Accuracy
±0.3% of I
at I ≤ 0.5 × I
r
±0.3% of I at I > 0.5 × I
±0.3% of I
at I ≤ 0.5 × I
r
±0.3% of I at I > 0.5 × I
±0.3% of I
at I ≤ 0.5 × I
r
±0.3% of I at I > 0.5 × I
±1.0 degrees at 0.1 × I
±0.5 degrees at 0.5 × I
Accuracy
±0.5% of U at U ≤ 50 V
±0.2% of U at U > 50 V
±0.5% of U at U ≤ 50 V
±0.2% of U at U > 50 V
±0.5% of U at U ≤ 50 V
±0.2% of U at U > 50 V
±0.5 degrees at U ≤ 50 V
±0.2 degrees at U > 50 V
M16080-1 v5
Accuracy
±0.1 % of set value ±0.005 mA
1MRK 504 155-BEN F
r
r
r
r
r
r
< I ≤ 0.5 × I
r
r
< I ≤ 4.0 × I
r
r
107

Advertisement

Table of Contents
loading

This manual is also suitable for:

Relion ret670

Table of Contents