Table 6 — 50VQP072-360, Inverter Duty Motor (with VFD) Electrical Data
50VQP UNIT
VOLTAGE
SIZE
(V-Ph-Hz)
a
208-230/3/60
460/3/60
072
208-230/3/60
460/3/60
208-230/3/60
460/3/60
096
208-230/3/60
460/3/60
208-230/3/60
460/3/60
208-230/3/60
120
460/3/60
208-230/3/60
460/3/60
208-230/3/60
460/3/60
151
208-230/3/60
460/3/60
208-230/3/60
181
460/3/60
208-230/3/60
460/3/60
208-230/3/60
210
460/3/60
208-230/3/60
460/3/60
208-230/3/60
460/3/60
208-230/3/60
460/3/60
240
208-230/3/60
460/3/60
208-230/3/60
460/3/60
208-230/3/60
460/3/60
208-230/3/60
460/3/60
300
208-230/3/60
460/3/60
208-230/3/60
460/3/60
208-230/3/60
360
460/3/60
NOTE(S):
a. A voltage variation of ± 10% of nameplate rating is acceptable. Phase imbalance shall not exceed 2%.
b. HACR circuit breaker in U.S.A. only.
LEGEND
FLA
— Full Load Amps
HACR — Heating, Air Conditioning, and Refrigeration
LRA
— Locked Rotor Amps
RLA
— Rated Load Amps
COMPRESSOR (X2)
VOLTAGE
MIN/MAX
RLA
197/253
10.4
414/506
5.8
197/253
10.4
414/506
5.8
197/253
13.7
414/506
6.2
197/253
13.7
414/506
6.2
197/253
15.6
414/506
7.8
197/253
15.6
414/506
7.8
197/253
15.6
414/506
7.8
197/253
19.2
414/506
8.7
197/253
19.2
414/506
8.7
197/253
22.4
414/506
10.6
197/253
29.5
414/506
14.7
197/253
29.5
414/506
14.7
197/253
29.5
414/506
14.7
197/253
30.1
414/506
16.7
197/253
30.1
414/506
16.7
197/253
30.1
414/506
16.7
197/253
48.1
414/506
18.6
197/253
48.1
414/506
18.6
197/253
55.8
414/506
26.9
197/253
30.1
414/506
16.7
197/253
48.1
414/506
18.6
197/253
55.8
414/506
26.9
BLOWER MOTOR
LRA
QTY
73.0
1
38.0
1
73.0
1
38.0
1
83.1
1
41.0
1
83.1
1
41.0
1
110.0
1
52.0
1
110.0
1
52.0
1
110.0
1
52.0
1
136.0
1
66.1
1
136.0
1
66.1
1
149.0
1
75.0
1
195.0
2
95.0
2
195.0
2
95.0
2
195.0
2
95.0
2
225.0
2
114.0
2
225.0
2
114.0
2
225.0
2
114.0
2
245.0
2
125.0
2
245.0
2
125.0
2
340.0
2
173.0
2
225.0
2
114.0
2
245.0
2
125.0
2
340.0
2
173.0
2
38
MIN CIRCUIT
AMPS
HP
FLA
2.0
6.2
29.6
2.0
3.1
16.2
3.0
8.8
32.2
3.0
4.3
17.4
2.0
6.2
37.0
2.0
3.1
17.1
3.0
8.8
39.6
3.0
4.3
18.3
2.0
6.2
41.3
2.0
3.1
20.7
3.0
8.8
43.9
3.0
4.3
21.9
5.0
13.5
48.6
5.0
6.2
23.8
3.0
8.8
52.0
3.0
4.3
23.9
5.0
13.5
56.7
5.0
6.2
25.8
5.0
13.5
63.9
5.0
6.2
30.1
2.0
6.2
78.8
2.0
3.1
39.3
3.0
8.8
84.0
3.0
4.3
41.7
5.0
13.5
93.4
5.0
6.2
45.5
2.0
6.2
80.1
2.0
3.1
43.8
3.0
8.8
85.3
3.0
4.3
46.2
5.0
13.5
94.7
5.0
6.2
50.0
3.0
8.8
125.8
3.0
4.3
50.5
5.0
13.5
94.7
5.0
6.2
50.0
5.0
13.5
152.6
5.0
6.2
72.9
2.0
6.2
80.1
2.0
3.1
43.8
5.0
13.5
94.7
5.0
6.2
50.0
5.0
13.5
152.6
5.0
6.2
72.9
MAX FUSE/
HACR
b
40
20
40
25
50
20
50
20
50
25
50
25
60
30
70
30
70
30
80
40
100
50
110
50
110
60
110
60
110
60
110
60
150
60
110
60
200
90
110
60
110
60
200