Table 4 — 50VQP072-360 Standard Duty Motor (No VFD) Electrical Data(cont)
50VQP UNIT
VOLTAGE
SIZE
(V-Ph-Hz)
a
208/230-3-60
460-3-60
575-3-60
300
208/230-3-60
460-3-60
575-3-60
208/230-3-60
360
460-3-60
575-3-60
NOTE(S):
a.
HACR circuit breaker in U.S.A. only.
b.
A voltage variation of ± 10% of nameplate rating is acceptable. Phase imbalance shall not exceed 2%.
LEGEND
FLA
— Full Load Amps
HACR — Heating, Air Conditioning, and Refrigeration
LRA
— Locked Rotor Amps
RLA
— Rated Load Amps
COMPRESSOR
VOLTAGE
MIN/MAX
RLA
197/253
48.1
414/506
18.6
518/632
14.7
197/253
48.1
414/506
18.6
518/632
14.7
197/253
55.8
414/506
26.9
518/632
23.7
BLOWER MOTOR
LRA
QTY
FLA
245.0
2
125.0
2
100.0
2
245.0
2
13.4
125.0
2
100.0
2
340.0
2
13.4
173.0
2
132.0
2
36
MIN CIRCUIT
AMPS
HP
8.0
3.0
124.2
3.9
3.0
49.7
3.7
3.0
40.5
5.0
135.0
6.6
5.0
55.1
5.4
5.0
43.9
5.0
152.4
6.6
5.0
73.7
5.4
5.0
64.1
MAX FUSE/
HACR
b
150
60
50
175
70
50
200
100
80