Detecting Leaks; Repairing Leaks; Warranty Policy - Panasonic PAW-280PAH3M-1 Installation Instructions Manual

Air handling unit kit
Hide thumbs Also See for PAW-280PAH3M-1:
Table of Contents

Advertisement

1.3.3 Detecting leaks

● If a leak is suspected, remove or extinguish all naked flames and ventilate the space
immediately.
● To search for and detect any refrigerant leaks, never use potential sources of ignition
like e.g. a halide torch or any other detector using a naked flame.
● Leak detection fluids are suitable for use with most refrigerants, but the use of
detergents containing chlorine shall be avoided, as the chlorine may react with the
refrigerant and corrode the copper pipework.
● Preferably, use an electronic leak dectector, which is suitable for R32, to check for
leaks.
● Make sure that the electronic detector has an adequate sensitivity and that it has been
calibrated in a refirgerant-free area.
● Set the leak detector to a percentage of the lower flammable limit (LFL) of the
relevant refrigerant, and calibrate the detector to the refrigerant used (R32) so that the
appropriate percentage of refrigerant gas (max. 25 %) is confirmed.

1.3.4 Repairing leaks

If a leakage of refrigerant is found, which requires brazing, do the following:
● Recover all refrigerant from the system, or isolate all refrigerant by means of shut-off
valves in a part of the system remote from the leak.
● Purge the system with oxygen-free nitrogen (OFN) both, before and during the brazing
process.
● Re-fill the system with refrigerant and check for any remaining leaks
(see → 1.3.3 Detecting leaks, p. 19).
● Repeat this procedure until no more leaks are detected.
1.4

Warranty policy

We can be held responsible for the quality and performance of the AHU Kit we supply.
However, we cannot be held responsible for the performances, operations and machine controls
of your complete AHU system which incorporates our AHU Kit, nor for the components used in
the refrigerant cycle of your AHU system (including, but not limited to, compressors, high-pressure
switches, check valves, strainers, expansion valves, solenoid valves, 4-way valves, capillary
tubes, accumulator tanks, and heat exchanger tubes), nor for any damages and defects caused
in the process of installing our AHU Kit, by the system design and/or during assembly of your AHU
system.
We do not publish the certificate to show conformity to the EMC and the product safety
requirements applicable to your complete AHU system.
AHU Kit – Installation Instructions – 11/2021
General information and safety notes
1
19

Advertisement

Table of Contents
loading

Table of Contents