Specifications - Empire DVC55IPXLP-2 Installation Instructions And Owner's Manual

Fan typedirect-vent wall furnace
Table of Contents

Advertisement

Available languages

Available languages

When an existing Category 1 heater is removed or replaced,
the original venting system may no longer be sized to
properly vent the attached appliances. Instructions shall
CARBON MONOXIDE POISONING HAZARD
Failure to follow the steps outlined below for each appliance
connected to the venting system being placed into operation
could result in carbon monoxide poisoning or death.
The following steps shall be followed for each appliance
connected to the venting system being placed into operation,
while all other appliances connected to the venting system
are not in operation:
1.
Seal any unused openings in the venting system.
2.
Inspect the venting system for proper size and
horizontal pitch, as required in the National Fuel Gas
Code, ANSI Z223.1/NFPA 54 or the Natural Gas and
Propane Installation Code, CSA B149.1 and these
instructions. Determine that there is no blockage or
restriction, leakage, corrosion and other deficiencies
which could cause an unsafe condition.
3.
As far as practical, close all building doors and
windows and all doors between the space in which
the appliance(s) connected to the venting system are
located and other spaces of the building.
4.
Close fireplace dampers.
Input BTU/HR
Part Numbers
Part Numbers
682160
682269
45051-0-0523
INTRODUCTION (CONT'D)

SPECIFICATIONS

MODEL
Height
Width
Depth
Gas Inlet
CFM
SOR-1
SOK-1
VINYL SIDING VENT KITS
DV-822
VSK2
also indicate effects of an improperly sized venting system
(formation of condensate, leakage, spillage, etc.) and shall
specify the following test procedure:
WARNING
5.
Turn on clothes dryers and any appliance not connected
to the venting system. Turn on any exhaust fans, such
as range hoods and bathroom exhausts, so they are
operating at maximum speed. Do operate a summer
exhaust fan.
6.
Follow the lighting instructions. Place the appliance
being inspected into operation. Adjust the thermostat so
appliance is operating continuously.
7.
Test for spillage from draft hood equipped appliances
at the draft hood relief opening after 5 minutes of main
burner operation. Use the flame of a match or candle.
8.
If improper venting is observed during any of the
above tests, the venting system must be corrected in
accordance with National Fuel Gas Code, ANSI Z223.1/
NFPA 54 and/or Natural Gas and Propane Installation
Code, CSA B149.1.
9.
After is has been determined that each appliance
connected to the venting system properly vents when
tested as outlined above, return doors, windows,
exhaust fans, fireplace dampers and any other gas-fired
burning appliance to their previous conditions of use.
ACCESSORIES
Side Outlet Kit, 10" Boot Assembly w/Register
CONVERSION KITS
Description
Propane to Natural
Natural to Propane
DVC55IPX
55,000
82 3/8"
16"
11 1/2"
1/2" Pipe
400
Register, Side Outlet
Description
Vinyl Siding Vent Kit
Vinyl Siding Vent Kit
Used On
DVC55IPXLP-2
DVC55IPXNAT-2