Midea KHA-06RY1 Installation Manual

Midea KHA-06RY1 Installation Manual

Split type heat pump

Advertisement

Quick Links

INSTRUKCJA INSTALACYJNA
PL
POMPA CIEPŁA SPLIT
INSTALATION MANUAL
EN
SPLIT TYPE HEAT PUMP

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the KHA-06RY1 and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for Midea KHA-06RY1

  • Page 1 INSTRUKCJA INSTALACYJNA POMPA CIEPŁA SPLIT INSTALATION MANUAL SPLIT TYPE HEAT PUMP...
  • Page 3 POMPA CIEPŁA POMPA CIEPŁA KLIMATYZATOR JEDNOSTKA ZEWEWNĘTRZNA JEDNOSTKA ZEWEWNĘTRZNA ŚCIENNY TYPU SPLIT SPLIT SPLIT KHA-06RY1 KHA-12RY3 KHA-08RY1 KHA-14RY3 KHA-10RY1 KHA-16RY3 Instrukcja obsługi Instrukcja instalacyjna Dziękujemy za wybór naszego produktu. Dla zapewnienia prawidłowej obsługi, zapoznaj się z instrukcją i przechowuj ją do wykorzystania w przyszłości.
  • Page 5 10 BIEG TESTOWY PRZEKAZANIE KLIENTOWI 13.1 13.2 13.3 13.4 13.5 13.6 13.7 13.8 DANE TECHNICZNE 15 INFORMACJE O SERWISIE...
  • Page 8 • • : : :...
  • Page 9 • • •...
  • Page 10 instalacyjna...
  • Page 12 • zawiera mniej z odpowiednimi oznaczeniami mniej gazami mniej co 12 co 24 • Koniecznie wchodzenie do r Powiedz • - Nie w miejscach przez prac odpowiednie zaradcze zgodne z • w miejscu •...
  • Page 13 >600 >600 ① ② ① ②...
  • Page 14 1008 1118 Podstawa ≥...
  • Page 16 a A (mm) B1 (mm) B2 (mm) C (mm) A (mm) B1 (mm) B2 (mm) C (mm)
  • Page 19 >15 15 ×20 8/10/12/1 /16 W 15 × 8...
  • Page 21 8-2, 8-1 to MCA w 63 A, Drut > > > > > > > Mi . TOCA 13,50 0,10 0,50 1,50 15,50 1,50 9,15 1,50 10,15 1,50 11,15 1,50 INFORMACJA MCA : TOCA : MFA : MSC: FLA : FLA: 10 W 12 W 3-P...
  • Page 26 26 25...
  • Page 27 9.4 Jednostki trójfazowe 12~16 kW...
  • Page 28 V i n...
  • Page 29 e zas...
  • Page 33 13.1...
  • Page 38 Zabezpieczenie zbior. Zabezpieczenie...
  • Page 39 220 2 0 50Hz 1180*890*560...
  • Page 40 1180*890*560...
  • Page 44 Opis Opis Pozycja Pozycja Zawór czterodrogowy Separator gazu i cieczy Filtr Kapilara...
  • Page 45 S6-1 S6-2 S6-3 10KW 12/9V DEBUGUJ H-PRO H-PRO L-PRO L-PRO EKRANOWANEGO...
  • Page 47 1 2 3 1 2 3 S6-1 S6-2 S6-3 =4100K , R T3/T4/T6(Th) 25/50 =3950K , R T5(Tp) 25/50 12KW 14KW 16KW...
  • Page 51 HEAT PUMP HEAT PUMP KLIMATYZATOR OUTDOOR UNIT OUTDOOR UNIT ŚCIENNY TYPU SPLIT SPLIT SPLIT KHA-06RY1 KHA-12RY3 KHA-08RY1 KHA-14RY3 KHA-10RY1 KHA-16RY3 Instrukcja obsługi Instalation Manual Dziękujemy za wybór naszego produktu. Dla zapewnienia prawidłowej obsługi, zapoznaj się z instrukcją i przechowuj ją do wykorzystania w przyszłości.
  • Page 52: Table Of Contents

    CONTENTS SAFETY PRECAUTIONS ACCESSORIES Accessories supplied with the unit BEFORE INSTALLATION IMPORTANT INFORMATION FOR THE REFRIGERANT INSTALLATION SITE Selecting a location in cold climates Prevent sunshine INSTALLATION PRECAUTIONS Dimensions Installation requirements Drain hole position Installation space requirements 7 INSTALLATION OF THE CONNECTING PIPE Rrfrigerant piping Leakage detection Heat insulation...
  • Page 53 OVERVIEW OF THE UNIT Disassembling the unit Electronic control box 6~16kW 1-phase units 12~16kW 3-phase units TEST RUNNING 11 PRECAUTIONS ON REFRIGERANT LEAKAGE TURN OVER TO CUSTOMER OPERATION AND PERFORMANCE Protection equipment 13.1 13.2 About power cut 13.3 Heating capacity Compressor protection feature 13.4 13.5...
  • Page 54 6 kW 8/10/12/14/16 kW Wiring diagram:8/10kW for example Electric Control System 6 kW Refrigerant System Please remove the hollow plate after installation. 12/14/16 kW 8/10 kW Remove the transportation support 12/14/16 kW NOTE Please remove the noise insulation cover of the compressor first. Please make sure the transportation support had be removed.
  • Page 55: Safety Precautions

    1 SAFETY PRECAUTIONS The precautions listed here are divided into the following types.They are quite important, so be sure to follow them carefully. Meanings of DANGER, WARNING, CAUTION and NOTE symbols. INFORMATION Read these instructions carefully before installation. Keep this manual in a handy for future peference. Improper installation of equipment or accessories may result in electric shock, short-circuit, leakage, fire or other damage to the equipment.
  • Page 56 DANGER Before touching electric terminal parts, turn off power switch. When service panels are removed, live parts can be easily touched by accident. Never leave the unit unattended during installation or servicing when the service panel is removed. Do not touch water pipes during and immediately after operation as the pipes may be hot and could burn your hands.
  • Page 57 Do not install the unit in the following places: - Where there is mist of mineral oil, oil spray or vapors. Plastic parts may deteriorate, and cause them to come loose or water to leak. - Where corrosive gases (such as sulphurous acid gas) are produced. Where corrosion of copper pipes or soldered parts may cause refrigerant to leak.
  • Page 58: Accessories

    2 ACCESSORIES 2.1 Accessories supplied with the unit Installation Fittings Name Shape Quantity Outdoor unit installation & owners manual (this book) Technical data manual Water outlet connection pipe assembly Energy label 3 BEFORE INSTALLATION Before installation Be sure to confirm the model name and the serial number of the unit. Handling 1.
  • Page 59: Important Information For The Refrigerant

    2. While handling the unit keep both sides of the sling level. keep your back straight 3. After mounting the unit,remove the sling from the unit by pulling 1 side of the sling. CAUTION To avoid injury, do not touch the air inlet and aluminum fins of the unit. Do not use the grips in the fan grills to avoid damage.
  • Page 60: Installation Site

    Factory charged refrigerant volume in the unit Model Refrigerant/kg Tonnes CO equivalent 3-phase 12kW 1.84 1.24 3-phase 14kW 1.84 1.24 3-phase 16kW 1.84 1.24 CAUTION Frequency of Refrigerant Leakage Checks - Equipment that contains less than 3 kg of fluorinated greenhouse gases or hermetically sealed equipment, which is labelled accordingly and contains less than 6 kg of fluorinated greenhouse gases shall not be subject to leak checks.
  • Page 61: Selecting A Location In Cold Climates

    5.1 Selecting a location in cold In normal condition,refer to the figures below for installation of the unit: climates Refer to "Handling" in section “4 Before installation” ( ) wall or obstacle NOTE When operating the unit in cold climates, be sure Air inlet >300 to follow the instructions described below.
  • Page 62: Installation Precautions

    6 INSTALLATION PRECAUTIONS 6.1 Dimensions 8/10/12/14/16 kW (unit: mm) 6 kW (unit: mm) Fig: 6-1 Fig: 6-2 Model 1008 8/10/12/14/16kW 1118 6.2 Installation requirements Check the strength and level of the installation ground so that the unit may not cause any vibrations or noise during the operation.
  • Page 63: Drain Hole Position

    6.3 Drain hole position Drain hole Drain hole This drain hole is covered by rubber plug. If the small drain hole can not meet the drainage requirements, the big one can be used at the same time. 8/10/12/14/16 kW 6 kW Fig: 6-5 CAUTION It's necessary to install an electrical heating belt if water can't drain out in cold weather even the big drain hole has...
  • Page 64: Installation Of The Connecting Pipe

    Fig: 6-7 Unit A(mm) B1(mm) B2(mm) C(mm) 6~16kW ≥3000 ≥2000 ≥150 ≥600 2) In case of installing multiple units in lateral connection per row. ≥500mm ≥500mm Fig: 6-8 A(mm) B1(mm) B2(mm) C(mm) Unit 6~16kW ≥3000 ≥2000 ≥300 ≥600 7 INSTALLATION OF THE CONNECTING PIPE 7.1 Refrigerant piping liqulid 6~16kW...
  • Page 65: Leakage Detection

    CAUTION ● Please pay attention to avoid the components where it is connecting to the connecting pipes. To prevent the refrigerant piping from oxidizing inside when welding, it is necessary to charge nitrogen, or oxide ● will chock the circulation system. 7.2 Leakage detection Use soap water or leakage detector to check every joint whether leak or not (Refer to Fig.7-2 ).Note: A is high pressure side stop valve...
  • Page 66: Connecting Method

    7.4 Connecting method Outdoor Unit Indoor Unit Figure 7-3 Models 6~16 kW Max.piping length (H+L1) Max difference in height (H) 1) Size of pipes of Gas side and Liquid side MODEL Refrigerant Gas side/Liquid side Φ15.9/Φ6.35 8/10kW Φ15.9/Φ9.52 3-phase 12/14/16kW Φ15.9/Φ9.52 2) Connection method Gas side...
  • Page 67: Remove Dirt Or Water In The Pipes

    7.5 Remove dirt or water in the pipes 1) Make sure there is no any dirt or water before connectiong the piping to the outdoor and indoor units. 2) Wash the pipes with high pressure nitrogen, never use refrigerant of outdoor unit. 7.6 Airtight testing Charge pressured nitrogen after connecting indoor/outdoor unit pipes to do airtight testing.
  • Page 68: Outdoor Unit Wiring

    8 OUTDOOR UNIT WIRING WARNING A main switch or other means of disconnection, having a contact separation in all poles, must be incorporated in the fixed wiring in accordance with relevant local laws and regulations. Switch off the power supply before making any connections.
  • Page 69: Safety Device Requirment

    8.3 Safety device requirment 1. Select the wire diameters( minimum value) individually for each unit based on the table 8-1 and table 8-2, where the rated current in table 8-1 means MCA in table 8-2. In case the MCA exceeds 63A, the wire diameters should be selected according to the national wiring regulation.
  • Page 70: To Finish The Outdoor Unit Installation

    L2 L3 OUTDOOR UNIT OUTDOOR UNIT POWER SUPPLY POWER SUPPLY 1-phase 3-phase NOTE The ground fault circuit interrupter must be a high-speed type breaker of 30 mA (<0.1 s). Please use 3-core shielded wire. 8.5 To finish the outdoor unit installation insulate and fix the refrigerant piping and interconnection cable as follows: Gas pipe Gas pipe insulation...
  • Page 71: Electronic Control Box

    8/10/12/14/16kW Door 1 To access to the compressor and Door 1 To access to the compressor and electrical parts. electrical parts WARNING Cut off all power supply— i.e. unit power supply and backup heater and domestic hot water tank power supply (if applicable) —...
  • Page 72 (Back) CN30 PCB A PCB B PCB C 12/14/16kW 3-phase NOTE The picture is for reference only, please refer to the actual product.
  • Page 73: 16Kw 1-Phase Units

    9.3 6~16kW 1-phase units 1) PCB A, 6-10kw,Inverter module Remarks: for 6kw, two capacitors CN20 Code Assembly unit Assembly unit Code Compressor connection port U Reserved(CN302) Compressor connection port V Port for communication with PCB B(CN32) Compressor connection port W Input port N for rectifier bridge(CN502) Output port for +12V/9V(CN20) Input port L for rectifier bridge(CN501)
  • Page 74 3) PCB B, 6-16kw,Main control board CN10 CN27 CN11 CN22 CN24 CN17 CN26 CN28 CN13 CN55 CN18 CN14 CN7 CN5 CN6 CN16 CN19 CN21 CN29 CN33 CN2 CN30 CN36 CN37 CN38 CN20 26 25 24 Code Assembly unit Code Assembly unit Output port L to PCB A(CN28) Port for low pressure switch (CN14) Port for communication with hydro-box control board...
  • Page 75: 16Kw 3-Phase Units

    9.4 12~16kW 3-phase units 1) PCB A, Inverter module CN16 CN22 CN15 CN23 CN17 CN18 CN20 CN19 Code Assembly unit Assembly unit Code Power Input port L1 (CN16) Output port for +15V(CN20) Input port P_in for IPM module (CN1) Compressor connection port W (CN19) Port for communication with PCB B (CN8) Compressor connection port V (CN18) Compressor connection port U (CN17)
  • Page 76 2) PCB B, Main control board CN41 CN26 CN24 CN36 CN21 CN18 CN31 CN29 CN10 CN35 CN11 CN28 CN20 CN37 CN27 V i n CN22 CN30 CN38 CN53 CN109 Code Assembly unit Assembly unit Code Port for temp.sensor Tp(CN8) Port for ground wire(CN38) Port for outdoor ambient temp.
  • Page 77 3) PCB C, filter board CN204 CN205 CN206 CN30 CN213 CN214 CN202 CN211 CN203 CN200 CN201 CN212 PCB C 3-phase 12/14/16kW Code Assembly unit Code Assembly unit Port for communication with PCB B (CN8) Power supply L2(CN201) Power supply L3(CN200) Power filtering L3(L3’) Power supply N(CN203) Power filtering L2(L2’)
  • Page 78: Test Running

    10 TEST RUNNING Operate according to "key points for test running" on the electric control box cover. CAUTION ● Test running can not start until the outdoor unit has been connected to the power for 12 hours. ● Test running can not start until all the valves are affirmed open. ●...
  • Page 79: Turn Over To Customer

    Outdoor Unit Indoor Unit Room is filled of leaked refrigerant. (All refrigerant has leaked out.) 8/10/12/14/16 kW Fig.11-2 Indoor unit A. Ventilation peristome B. Leakage alarm related to mechanical ventilator (Leakage hunting siren should be installed in places where the refrigerant can be easily gathered) Fig.11-3 Max.
  • Page 80 WARNING Turn off any combustible heating devices, ventilate the Ask your dealer for installation of the heat pump. room, and contact the dealer where you purchased the Incomplete installation performed by yourself may result in a unit. water leakage, electric shock, and fire. Do not use the heat pump until a service person confirms that the portion where the refrigerant leaks is repaired.
  • Page 81: Operation And Performance

    NOTE Never expose little children, plants or animals directly to the air flow. When the protection equipment starts, please shut down the Adverse influence to little children, animals and plants may manual power switch, and restart operation after problem is result.
  • Page 82: Error Codes

    13.8 Error codes When a safety device is activated, an error code will be displayed on the user interface. A list of all errors and corrective actions can be found in the table below. Reset the safety by turning the unit OFF and back ON. In case this procedure for resetting the safety is not successful, contact your local dealer.
  • Page 83 ERROR MALFUNCTION FAILURE CAUSE CODE OR PROTECTION AND CORRECTIVE ACTION 1. Strong wind or typhoon below toward to the fan, to make the fan running in the opposite direction. Change the unit direction or make shelter to avoid typhoon below to the fan. The DC fan failure 2.fan motor is broken, change a new fan motor.
  • Page 84 ERROR MALFUNCTION FAILURE CAUSE CODE OR PROTECTION AND CORRECTIVE ACTION Heating mode, DHW mode: 1. The water flow is low; water temp is high, whether there is air in the water system. Release the air. 2. Water pressure is lower than 0.1Mpa, charge the water to let the pressure in the range of 0.15~0.2Mpa.
  • Page 85 ERROR MALFUNCTION FAILURE CAUSE CODE OR PROTECTION AND CORRECTIVE ACTION 1. Check the power supply. 2. If the power supply is OK,and check if LED light is OK, check the voltage PN, if it is 380V, the problem usually comes from the main board.
  • Page 86 ERROR MALFUNCTION FAILURE CAUSE CODE OR PROTECTION AND CORRECTIVE ACTION Module protection DC generatrix low voltage protection DC generatrix high voltage protection 1. Check the Heat pump system pressure; 2. Check the phase resistance of compressor; 3. Check the U、V、W power line connection sequence between the inventer board and the compressor;...
  • Page 87: Technical Specifications

    14 TECHNICAL SPECIFICATIONS Model 10kW 220-240V~ 50Hz Power supply Rated power input 2600W 3300W 3600W Rated current 12.0A 14.5A 16.0A Refer to the technical data Norminal capacity Dimensions (W×H×D)[mm] 1008*712*426 1118*865*523 Packing (W×H×D)[mm] 1065*810*485 1190*970*560 DC motor / Horizontal Fan motor DC inverter dual rotary Compressor Fin-coil...
  • Page 88 Model 12kW 14kW 16kW 3-phase 3-phase 3-phase 380-415V 3N~ 50Hz Power supply Rated power input 6100W 5400W 5700W 11.0A Rated current 10.0A 9.0A Refer to the technical data Norminal capacity Dimensions (W×H×D)[mm] 1118*865*523 1118*865*523 Packing (W×H×D)[mm] 1190*970*560 1190*970*560 DC motor / Horizontal Fan motor DC inverter dual rotary Compressor...
  • Page 89: Information Servicing

    15 INFORMATION SERVICING 1) Checks to the area Prior to beginning work on systems containing flammable refrigerants, safety checks are necessary to ensure that the risk of ignition is minmised. For repair to the refrigerating system, the following precautions shall be complied with prior to conducting work on the system.
  • Page 90 b) Particular attention shall be paid to the following to ensure that by working on electrical components, the casing is not altered in such a way that the level of protection is affected. This shall include damage to cables, excessive number of connections, terminals not made to original specification, damage to seals, incorrect fitting of glands, etc.
  • Page 91 Cylinders shall be kept upright. Ensure that the refrigeration system is earthed prior to charging the system with refrigerant. Label the system when charging is complete(if not already). Extreme care shall be taken not to overfill the refrigeration system. Prior to recharging the system it shall be pressure tested with OFN. The system shall be leak tested on completion of charging but prior to commissioning.
  • Page 92 ANNEX A: Refrigerant cycle Cooling Heating Item Description Item Description Evaporation sensor in heating Compressor (Condenser sensor in cooling) 4-Way Valve Stop valve (gas) Gas-liquid separator Stop valve (liquid) Air side heat exchanger High Pressure Switch Electronic expansion Valve Low Pressure Switch Single-way electromagnetic valve Pressure sensor Strainer...
  • Page 93 ANNEX B: To install the E-heating tape at the drainage outlet (by client) Connect the wireCeating tape at the drainage outlet to the wire joint XT3. To the heating tape of drainage outlet NOTE The picture is for reference only, please refer to the actual product.