TECHNICAL SPECIFICATIONS
Model
PR750RT2U
General
UPS Topology
Energy Saving
Input
Nominal Input
Voltage
Input Voltage Range
Input Frequency
Plug Type
Power Cord Length
Output
Power Capacity
750VA/750W
On Battery Output
Voltage
On Battery Output
Frequency
On Battery Output
Waveform
Battery
Battery Type
Replacement Battery
Pack (RBP)
RBP Quantity
Typical Recharge Time
Physical
Dimensions
Weight
43.2lbs / 19.6kg
Conformance
Approvals
Environmental
*Refer below de-rating information for 100/110V systems:
PR1500RT2U: 1200VA/1200W@100V, 1350VA/1350W@110V; PR2000RT2U: 1600VA/1600W@100V, 1800VA/1800W@110V; PR3000RT2U: 2400VA/2400W@100V,
2700VA/2700W@110V.
PR1000RT2U
100/110/120/125V
For 110/120/125V systems: 75V – 155V; For 100V systems: 70V – 129V
NEMA 5-15P
1000VA/1000W
100/110/120/125V +/- 5%
RB1250X4
RB1270X4H
2U Rack, 17.1" x 3.4" x 16.2" / 433 x 86.5 x 412 (mm)
50.1lbs / 22.7kg
UL1778, CSA C22.2 No 107.3, FCC Class B, VCCI Class B, ENERGY STAR
PR1500RT2U
PR2000RT2U
Line-interactive
TM
GreenPower UPS
Bypass Technology
50/60Hz +/- 3Hz (Auto-sensing)
NEMA 5-20P
10ft / 3m
1500VA/1500W*
2000VA/2000W*
50/60Hz +/- 1%
Sine Wave
Sealed Maintenance Free Lead Acid Battery
1
3 hours to 90% from total discharge under 100% load
55.8lbs / 25.3kg
59.8lbs / 27.1kg
RoHS Compliant
PR2200RT2U
100/110/120V
For 110/120V systems: 75V – 155V; For 100V
systems: 70V – 129V
NEMA5-30P
2200VA/2200W
100/110/120V +/- 5%
RB1290X4J
2U Rack, 17.1" x 3.4"
x 16.7" / 433 x 86.5 x
59.8lbs / 27.1kg
UL1778, CSA C22.2 No 107.3, FCC Class A, VCCI
Class A, ENERGY STAR
PR3000RT2U
3000VA/3000W*
500 (mm)
76.5lbs / 34.7kg