Pure Humidifier SX Series Installation Instructions And Operation And Maintenance Manual

Steam heat exchanger humidifier
Hide thumbs Also See for SX Series:

Advertisement

TM
READ AND SAVE THESE INSTRUCTIONS
Standard Water
SX Series
Steam Heat Exchanger Humidifi er
Installation Instructions
Operation and Maintenance Manual
Our results are comforting
PURE HUMIDIFIER® and INTAC® are registered trademarks of PURE Humidifi er Co.
Form No: SXOM-6-2023

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the SX Series and is the answer not in the manual?

Questions and answers

Summary of Contents for Pure Humidifier SX Series

  • Page 1 READ AND SAVE THESE INSTRUCTIONS Standard Water SX Series Steam Heat Exchanger Humidifi er Installation Instructions Operation and Maintenance Manual Our results are comforting PURE HUMIDIFIER® and INTAC® are registered trademarks of PURE Humidifi er Co. Form No: SXOM-6-2023...
  • Page 2 SX Humidifi ers We at PURE Humidifi er Co. thank you for choosing one of our quality products. PURE Humidifi er Co.’s SX Series humidifi ers are models of simplicity to install, operate and maintain. However, they must be maintained to provide maximum operating effi...
  • Page 3: Table Of Contents

    Table of Contents Introduction Warnings ………………………………………………………………………………………..Overview Features ………………………………………………………………………………………..Capacities, Weights & Water Volumes ………………………………………………………… Clearances & Mounting Considerations ……………………………………………….... Dimensions SX-1R through SX-4R ………………………………………………………………… SX-8R ………………………………………………………………………....SX-12R ………………………………………………………………………....Installation Installation & Location ……………………………………………………………………….….. Mounting Applications Support Legs …………………………………………………………………….….. Wall Brackets ………………………………………………………………………... Drain Pan Mounting ……………………………………………………………………….…...
  • Page 4: Warnings

    WARNINGS PLEASE READ AND FOLLOW ALL INSTRUCTIONS CAREFULLY. PROPER OPERATION AND HUMIDITY CONTROL IS POSSIBLE ONLY WITH PROPER INSTALLATION AND MAINTENANCE. To ensure proper installation of this product, it must be installed by qualifi ed HVAC and electrical contractors, and must be in compliance with local, state, federal, and governing codes.
  • Page 5: Features

    Features Features 1. Tri-Probe Sensor 5. Heat Exchanger/Plant Steam Condensate Outlet 2. 1/4” NPT Fill Inlet Connection 6. Pressurized Boiler Steam Inlet 3. Overfl ow Piping 7. Heat Exchanger 4. Automatic Drain Valve 8. Humidifi er Steam Outlet Connection...
  • Page 6: Capacities, Weights & Water Volumes

    Capacities, Weights & Water Volumes Humidifi er Capacity † Steam Pressure at the Humidifi er Control Valve Model 5 psig 34.5 kPa 10 psig 69 kPa 13 psig 90 kPa 15 psig 103 kPa lbs/hr kg/hr lbs/hr kg/hr lbs/hr kg/hr lbs/hr kg/hr SX-1R...
  • Page 7: Clearances & Mounting Considerations

    Clearances & Mounting Considerations 12” 6” (30.5 cm) (15.2 cm) 6” (15.2 cm) SX-1R: 20” (50.8 cm) SX-2R: 20” (50.8 cm) SX-3R: 24” (61.0 cm) 36” (91.4 cm) with factory mounted SX-4R: 34” (86.4 cm) control panel SX-8R: 34” (86.4 cm) SX-12R: 34”...
  • Page 8: Dimensions

    Dimensions SX-1R through SX-4R NEMA-12 Humidifi er Control Cabinet Steam Outlet Connection (reference control cabinet notes) (size and qty will vary w/application “B” “E” SX-1R: 3.53” (8.9) Heat Exchanger Removal SX-2R: 3.53” (8.9) (see Clearances & “D” SX-3R: 3.56” (9.0) Mounting Considerations SX-4R: 5.44”...
  • Page 9: Sx-8R

    Dimensions SX-8R NEMA-12 Humidifi er Control Cabinet Steam Outlet Connection (reference control cabinet notes) (size and qty will vary w/application “B” “E” Heat Exchanger Removal 3.87” (see Clearances & (9.8) Mounting Considerations page for clearance dimension) “D” Cabinet Depth: 6.00” (15.2) Top View Door has been removed from the drawing for clarity.
  • Page 10: Sx-12R

    Dimensions SX-12R NEMA-12 Humidifi er Control Cabinet Steam Outlet Connection (reference control cabinet notes) (size and qty will vary w/application “B” “E” Heat Exchanger Removal (see Clearances & 3.87” (9.8) Mounting Considerations page for clearance dimension) “D” Cabinet Depth: 6.00” (15.2) Top View Door has been removed from the drawing for clarity.
  • Page 11: Installation & Location

    Installation & Location Important: Remove all shipping brackets and materials Location of Controls before operating the humidi er. Humidi er ue gases must be vented to the outside atmosphere. Power It is important to avoid mounting any controls within the supply disconnect switch must be in the o position while visible steam.
  • Page 12: Mounting Applications

    Mounting Applications Support Legs Typical PURE Humidifi er SX Series Humidifi er Support Legs attach to humidifi er front and back plate mounting channels. Mounting hardware is by PURE Humidifi er Co. 24” (61) Above Floor Floor Secure to fl oor (mounting...
  • Page 13: Wall Brackets

    Mounting Applications Wall Brackets Optional Flexible Hose Kit (for remote mounting of humidifi er injection tube) Typical PURE Humidifi er SX Series Humidifi er Front View Wall Stud “A” Dim. “A” Dim. “B” Model inches inches Wall Bracket SX-1R 30.50 77.5...
  • Page 14: Drain Pan Mounting

    Drain Pan Mounting Drain Pan Mounting A drain pan is an additional safety feature which may be required to be supplied in the fi eld. In a proper humidifi er installation, a drain pan is not required. However, if the humidifi er and injection tube are located in an area that contains valuable equipment or is a water sensitive area, PURE Humidifi...
  • Page 15: Water Supply & Drain Piping

    Water Supply & Drain Piping ALL DRAIN AND CONDENSATE PIPING MUST BE INSTALLED IN ACCORDANCE TO LOCAL PLUMBING CODES. HIGH CHLORIDE CONTENT IN FEED WATER CAN CAUSE CHLORIDE STRESS CRACKING AND CHLORIDE PITTING IN STAINLESS COMPONENTS. CHLORIDE STRESS CORROSION CRACKING (CSCC) AND CHLORIDE PITTING OF STAINLESS STEEL COMPONENTS IS NOT COVERED BY WARRANTY.
  • Page 16: Drain Piping

    Piping Drain Piping 1/4”-NPT Water Inlet † Connection Steam Outlet Connection SIDE VIEW Heat Exchanger “H” 3/4” SW Copper Water Seal Drain Connection Open Sanitary Drain Water Seal Height Δ Capacity “H” lbs/hr kg/hr inches Up to 60 Up to 27.2 8”...
  • Page 17: Steam & Condensate Piping

    Steam & Condensate Piping SX-1R through SX-4R Control Valve Vacuum Breaker Pneumatic Actuator Shown (by others) (by PURE) Wye Strainer Water Supply Line (by PURE) Shut-Off Valve (by others) Steam Supply Line 3/4” SW Reservoir Heat Exchanger Drain Connection Condensate Steam Trap (by PURE) Non-Pressurized Condensate Return Line...
  • Page 18: Sx-8R

    Steam & Condensate Piping SX-8R Vacuum Breaker Control Valve (by others, Typ. 2) Pneumatic Actuator Shown (by PURE, Typ. 2) Water Supply Line Wye Strainer (by PURE, Typ. 2) Shut-Off Valve (by others, Typ. 2) Steam Supply Line (Typ. 2) Condensate Steam Trap (by PURE, Typ.
  • Page 19: Sx-12R

    Steam & Condensate Piping SX-12R Vacuum Breaker Control Valve (by others, Typ. 3) Pneumatic Actuator Shown Water Supply Line (by PURE, Typ. 3) Wye Strainer (by PURE, Typ. 3) Shut-Off Valve (by others, Typ. 3) Steam Supply Line (Typ. 3) Condensate Steam Trap (by PURE, Typ.
  • Page 20: Supply Piping Examples

    Steam Supply Piping Examples Pitch Use two 45° elbows for (see Note 1) hard piping or wide 90° for exible steam hose ¹ ”/1’ 2”/1’ see Note 2 Supply piping see Note 2 connectors (see Note 4) Pitched Towards Steam Generator Pitched Towards Tube Assembly Drain Tee (see Note 7)
  • Page 21: Injection Tube Installation

    Single or Multiple Injection Tube Installation Single or Multiple Injection Tube Installation Single injection tubes should be installed in the center of the duct. Multiple injection tubes should have the tubes staggered within the duct as shown in the illustration. The supply piping and injection tube should be pitched according to the examples on page 13.
  • Page 22 Single or Multiple Injection Tube Installation Single or Multiple Injection Tubes with Drain Tee Flexible Hose or Hard Piping Stainless Steel Drain Duct (below humidifi er) Tee (optional) “H” Water 3/4” SW Seal Height Condensate drain line (by others) Open Sanitary Drain Water Seal Height Δ...
  • Page 23: Steam Supply Piping

    Steam Supply Piping PURE recommends stainless tubing or pipe to match the steam outlet diameter connection on the humidi er cover. Stainless has superior corrosion resistance over copper and is less expensive but slightly harder to install. Stainless tubing is preferable over stainless pipe due to the fact that the tubing is less expensive and reduces heat loss/condensate formation during operation.
  • Page 24: Blower Pack

    Blower Pack In applications where a ducted air system is not available, PURE off ers the optional Blower Pack. The Blower Pack contains a two-speed adjustable blower that moves the air over the steam discharge outlet and disperses the steam directly into the space (see Fig.
  • Page 25 Blower Pack Locating Blower Pack The distance that visible steam will travel after leaving the Blower Pack is dependent upon the relative humidity in the room and the capacity of the humidifi er. If this visible steam comes in contact with any solid object (walls, beams, machinery, etc.) it may form condensate and drip.
  • Page 26: Controls Location

    Controls Locations Outside Air Tube Assembly Air ow Proving Switch On/O or Modulating Outside Air Temperature Sensor High Limit Humidistat Return Air Exhaust Air Air Handling Unit 8’-10’ Minimum Window Window Door Recommended Humidistat and Sensor Locations A. Optimal location for even air ow and a stable temperature B.
  • Page 27: Pre-Startup Checklist

    SX Pre-Startup Procedure Pre-Startup Checklist _____ 8. PIPING: High Pressure Condensate Line - The condensate line should not be elevated but should run to Before starting the SX PURE Humidifi er Co. Electric a non-pressurized condensate pump receiver or through a Humidifi...
  • Page 28: Sx Startup Procedure

    SX Startup Procedure Startup Procedure _____ 1. Turn the electric power “on” to the humidifi er. _____ 11. Check the main steam supply pressure. The pressure should match the factory nameplate. NOTE: Do not _____ 2. RH Setpoint on the touchscreen should be set to exceed the factory nameplate pressure rating! See warning 0.0% RH (no call for humidity).
  • Page 29: Troubleshooting

    Troubleshooting • Verify humidifi er and accessories are installed according to Operation and Maintenance manuals. • Please read all Operation and Maintenance manuals to familiarize yourself with the equipment. • A job specifi c wiring diagram can be located inside the control panel door. Problem Possible Cause Recommended Action...
  • Page 30: Maintenance Instructions

    PURE Humidifi er Co. SX Maintenance Instructions The SX Series Electric Humidifi er is designed to provide the best possible operation with minimum maintenance. However, the humidifi er should be inspected and place on a dedicated maintenance schedule to ensure continued operation of the humidifi...
  • Page 31: Exchanger Gasket Replacement Instructions

    Exchanger Gasket Replacement Instructions WARNING Disconnect the humidifi er power, gas, exhaust system and allow the humidifi er to cool prior to servicing. Drain water level below the level of the exchanger being serviced. Heat exchangers have a top and bottom. There is a break (crease) on the bottom side of the heat exchanger.
  • Page 32: Cover Gasket Replacement Instructions

    Cover Gasket Replacement Instructions Remove the reservoir cover. While looking at the top of the unit, reference Figure A and B to determine which humidi er tank style you have. Figure A Installation Fit the gasket around the entire lip of the tank opening. Cut the gasket ¹ ” longer than required, this will ensure proper t when the cover is clamped back on.
  • Page 33: Tool Requirements And Torque List

    Tool Requirements & Torque List Recommended Maintenance Tool List 7/16” Wrench 3/4” Wrench Crescent Wrench 11/32” Nut Driver or Socket 3/8” Nut Driver or Socket 5/32” Allen Head Flat Head Screw Driver Wire Stripper Wire Crimper Torque List Cover Bolts 18 inch/pounds MAX Side Entry Exchanger Bolts 80 inch/pounds MAX...
  • Page 34: Maintenance Notes

    Maintenance Notes Maintenance Performed Date...
  • Page 35: Sx-1R Through Sx-4R Exploded Parts Drawing

    Exploded Parts Drawing SX-1 through SX-4...
  • Page 36: Sx-1R Through Sx-4R Parts List

    PURE Humidifi er Co. SX-1 through SX-4 Parts List & Two Year Recommended Spare Parts Qty Per Unit Cover Clamp Screw (10-24 x 1" Hex Socket) 15522 #12 SAE Zinc " 8 " 4 l l i " 4 l l i "...
  • Page 37: Sx-8R Exploded Parts Drawing

    Exploded Parts Drawing SX-8...
  • Page 38: Sx-8R Parts List

    PURE Humidifi er Co. SX-8 Parts List & Two Year Recommended Spare Parts Qty Per Unit Cover Clamp Screw (10-24 x 1" Hex Socket) 15522 #12 SAE Zinc " 8 " 4 l l i " 4 " 2 " 4 l l i l l i "...
  • Page 39: Sx-12R Exploded Parts Drawing

    Exploded Parts Drawing SX-12...
  • Page 40: Sx-12R Parts List

    PURE Humidifi er Co. SX-12 Parts List & Two Year Recommended Spare Parts Qty Per Unit Cover Clamp Screw (10-24 x 1" Hex Socket) 15522 #12 SAE Zinc " 8 " 4 l l i " 4 " 2 " 4 l l i l l i "...
  • Page 41: Warranty

    The PURE Humidi er Co. Warranty PURE Humidi er Co. guarantees its products to be free from defects in material and workmanship for a period of one year from the date of shipment; provided the product is properly installed, serviced, and put into the service for which it was intended.
  • Page 44 DISCLAIMER Product Changes: Changes in products may be required from time to time due to the need for continuing improvement of products and due to factors beyond PURE Humidi er Co.’s control. PURE Humidi er Co. reserves the right to make reasonable changes in products, speci cations and performance of any kind without notice or liability.