SUMMARY OF REVIEWS The information below describes the reviews made in this manual. Version Review Description First edition. General review. General review.
1.3.1 Panel Handling ...........................6 1.3.1.1 Representative Image of the AFW11 Packaged for Land Transport ......6 1.3.1.2 Representative Image of the AFW11 Packaged for Land or Sea Transport in a Closed Container ........................7 1.3.1.3 Representative Image of the AFW11 Handled by the Lifting Eyes ......7 2 GENERAL INFORMATION .................
NOTE! For the purposes of this manual, qualified personnel are those trained and able to: 1. Install, ground, power up and operate the AFW11 in accordance with this manual and the safety legal procedures in force. 2. Wear/use protective equipment according to the standards in force.
1.3 HANDLING 1.3.1 Panel Handling 1.3.1.1 Representative Image of the AFW11 Packaged for Land Transport Handling the AFW11 with a forklift should be done as follow: Figure 1.1: Fork lift truck Figure 1.3: Lifted forklift back view Figure 1.2: Forklift lowered back view Figure 1.4: Forklift lowered side view...
SAFETY INSTRUCTIONS 1.3.1.2 Representative Image of the AFW11 Packaged for Land or Sea Transport in a Closed Container Handling the AFW11 with a forklift should be done as follow: Figure 1.7: Forklift lowered back view Figure 1.8: Lifted forklift back view Figure 1.6: Fork lift truck...
Page 8
Metallic reinforcement Lock washer Hex nut Figure 1.12: Exploded detail lifting eyes The distribution of the lifting eyes in the assembled set must follow the arrangement shown in the image below: Figure 1.13: Distribution of the lifting eyes 8 | AFW11...
2.4.2 IOB-01 Board CFW11 I/O Expansion Module (IOB-01/SLOT 1). Contents of the IOB-01 board: one isolated analog input, two analog outputs, two isolated digital inputs and two isolated digital outputs. Figure 2.3: IOB-01 Board Figure 2.4: Electrical connection IOB-01 12 | AFW11...
A DeviceNet network can contain up to 64 devices, with addresses from 0 to 63. Any of these can be used. There is no restriction, although 63 should be avoided as it is often used for commissioning purposes. 11 2131 aJ 15 ����� Figure 2.6: Devicenet AFW11 | 13...
Profinet is a protocol that allows up to 14 input words and 14 output words for cyclic data communication. Figure 2.8: Profinet 2.4.7 Ethernet IP Communication CFW11 Ethernet IP Module (ETHERNETIP-2P-05/SLOT 4). Ethernet is a technology for interconnecting local area networks (LAN) based on frame forwarding. Figure 2.9: Ethernet 14 | AFW11...
The option item must be used with WEG motors installed between 100 and 300 m; when using motors from other manufacturers it must be installed between 0 and 300 m. Figure 2.11: Electrical representation of the reactor AFW11 | 15...
B – Heatsink G – FLASH memory module C – Top cover H – Front cover D – Fan with mounting bracket I – HMI E – COMM 2 module (anybus) Figure 2.12: Parts of the CFW11 frame A 16 | AFW11...
15 - Value of the drive short-circuit current 7 - Drive protection rating 16 - Rated input frequency 8 - Certifications (if any) 17 - Value of the drive rated control voltage 9 - QRCode containing internal manufacturing information Figure 2.13: Label detail AFW11 | 17...
The recommended basic drive for the CFW-11 is schematically shown in Figure 3.1 on page Figure 3.2 on page Figure 3.3 on page 20 Figure 3.4 on page 21, currents from 3 A to 1141 A. Figure 3.1: Single line AFW11 3-31 A AFW11 | 18...
Page 19
TYPICAL SCHEMES Figure 3.2: Single line AFW11 38-760 A 19 | AFW11...
Page 20
TYPICAL SCHEMES Figure 3.3: Single line AFW11 Frame H 795-1141 A AFW11 | 20...
Page 21
TYPICAL SCHEMES Figure 3.4: Single line AFW11 Frame H 478-625 A 21 | AFW11...
The panels must be installed in the electric room according to the layout below. The panels must be fastened to a concrete or metallic floor properly leveled. After positioned on the concrete floor, The AFW11 must be anchored with 4 anchor bolts 3/8" x 3"; at the couplings between the columns, only two diagonally.
Page 23
INSTALLING Figure 4.3: Fixing details of AFW Frame E Figure 4.4: Fixing details of AFW Frame F Figure 4.5: Fixing details of AFW Frame G 23 | AFW11...
Slotted/Phillips truss head screw 6x60 mm. The details for fastening to concrete and hollow bricks can be seen in as follow. Figure 4.7: Details of the fastening of the panels to concrete and hollow brick walls AFW11 | 24...
TRANSFORMADOR CONFORME CUADRO ABAJO PRIMÁRIO DO TRANSFORMADOR TRANSFORMER PRIMARY PRIMARIO DEL TRANSFORMADOR TENSÃO CONECTAR LIGAR VOLTAGE JUMPE CONNECT TENSIÓN JUMPER CONECTAR 380 V 440 V 460 V 480 V Figure 4.8: Mechanical details: Frames A and B 25 | AFW11...
Page 26
REALIZAR CONEXIÓN DEL PRIMARIO DEL TRANSFORMADOR CONFORME CUADRO ABAJO PRIMÁRIO DO TRANSFORMADOR TRANSFORMER PRIMARY PRIMARIO DEL TRANSFORMADOR TENSÃO CONECTAR LIGAR VOLTAGE JUMPE CONNECT TENSIÓN JUMPER CONECTAR 380 V 440 V 460 V 480 V Figure 4.9: Mechanical details: Frame C AFW11 | 26...
Page 27
REALIZAR CONEXIÓN DEL PRIMARIO DEL TRANSFORMADOR CONFORME CUADRO ABAJO PRIMÁRIO DO TRANSFORMADOR TRANSFORMER PRIMARY PRIMARIO DEL TRANSFORMADOR TENSÃO CONECTAR LIGAR VOLTAGE JUMPE CONNECT TENSIÓN JUMPER CONECTAR 380 V 440 V 460 V 480 V Figure 4.10: Mechanical details: Frame D 27 | AFW11...
Page 28
TRANSFORMADOR CONFORME CUADRO ABAJO PRIMÁRIO DO TRANSFORMADOR TRANSFORMER PRIMARY PRIMARIO DEL TRANSFORMADOR TENSÃO CONECTAR LIGAR VOLTAGE JUMPE CONNECT TENSIÓN JUMPER CONECTAR 380 V 440 V 460 V 480 V Figure 4.11: Mechanical details: Frame E - IP54 AFW11 | 28...
Page 29
TRANSFORMADOR CONFORME CUADRO ABAJO PRIMÁRIO DO TRANSFORMADOR TRANSFORMER PRIMARY PRIMARIO DEL TRANSFORMADOR TENSÃO CONECTAR LIGAR VOLTAGE JUMPE CONNECT TENSIÓN JUMPER CONECTAR 380 V 440 V 460 V 480 V Figure 4.12: Mechanical details: Frame F – IP54 29 | AFW11...
Page 30
TRANSFORMADOR CONFORME CUADRO ABAJO PRIMÁRIO DO TRANSFORMADOR TRANSFORMER PRIMARY PRIMARIO DEL TRANSFORMADOR TENSÃO CONECTAR LIGAR VOLTAGE JUMPE CONNECT TENSIÓN JUMPER CONECTAR 380 V 440 V 460 V 480 V Figure 4.13: Mechanical details: Frame G – IP54 AFW11 | 30...
Page 31
TRANSFORMADOR CONFORME CUADRO ABAJO PRIMÁRIO DO TRANSFORMADOR TRANSFORMER PRIMARY PRIMARIO DEL TRANSFORMADOR TENSÃO CONECTAR LIGAR VOLTAGE JUMPE CONNECT TENSIÓN JUMPER CONECTAR 380 V 440 V 460 V 480 V Figure 4.14: Mechanical details: Frame H – IP54 31 | AFW11...
Do not use the neutral for grounding, but a specific conductor. DANGER! The supply line voltage must be compatible with the AFW11 voltage range. Assemble and connect all the devices sent separately for shipment reasons, carefully checking their position and connection in the respective drawings.
185 SIL 4x95 SIL 2x95 SIL 3x150 SIL 2x120 SIL NOTE! For the correct cable sizing, take into account the installation conditions, the maximum permissible line voltage drop, and follow the electrical instructions defined by local regulations. 35 | AFW11...
INSTALLING 4.4.3 Connecting the Power Supply The connection of the AFW11 to the mains must be made directly on terminals L1, L2, L3 of the Q1 circuit breaker/disconnector (Phase R/S/T) and on the Ground Bar (frame grounding - PE), as shown in Figure 4.16...
Check the "Defect" indication; if activated, solve it before proceeding with the procedure. Use the On and Off buttons to control the system. NOTE! In case of remote operation, the remote emergency button must be checked, and the system can be controlled using the remote buttons. AFW11 | 37...
That must be done especially when the protection devices actuate without any known reason. When the control protection circuit breaker trips, identify and solve the cause before turning the equipment back on. In case the panel presents any defect not mentioned above, contact WEG Technical Support at 0800-7010701. AFW11 | 38...
ONE-LINE DIAGRAM 7 ONE-LINE DIAGRAM Figure 7.1: Frame A, B, C and D - 3 A to 88 A AFW11 | 39...
Page 40
ONE-LINE DIAGRAM Figure 7.2: Frames E, F and G - 105 A to 760 A 40 | AFW11...
Page 41
ONE-LINE DIAGRAM Figure 7.3: Frame H – 478 A to 625 A AFW11 | 41...
Page 42
ONE-LINE DIAGRAM Figure 7.4: Frame H – 628 A to 1141 A 42 | AFW11...
Page 43
Manual de Instalación AFW11 Documento: 10009619203 Material: 16606370 Revisión: 02 Idioma: Español Fecha de la Publicación: 06/2023...
Page 44
SUMARIO DE REVISIONES La información abajo describe las revisiones ocurridas en este manual. Versión Revisión Descripción Primera edición. Revisión general. Revisión general.
Page 45
1.2 RECOMENDACIONES PRELIMINARES ..................46 1.3 MANIPULACIÓN ..........................47 1.3.1 Manipulación de los Accionamientos ................... 47 1.3.1.1 Imagen Representativa del AFW11 Embalado para tipo Transporte Terrestre ..47 1.3.1.2 Imagen Representativa del AFW11 Embalado para tipo Transporte Terrestre o Marítimo en Contenedor Cerrado ..............48 1.3.1.3 Imagen Representativa del AFW11 Manejado por los Cáncamos de Elevación ..48...
Para los propósitos de este manual, personas cualificadas son aquellas capacitadas de forma de estar aptas para: 1. Instalar, poner a tierra, energizar y operar el AFW11, de acuerdo con este manual y con los procedimientos legales de seguridad vigentes.
1.3.1 Manipulación de los Accionamientos 1.3.1.1 Imagen Representativa del AFW11 Embalado para tipo Transporte Terrestre La manipulación del AFW11 con una carretilla elevadora debe realizarse de la siguiente manera: Figura 1.1: Carretilla elevadora de horquilla Figura 1.3: Vista trasera de la carretilla Figura 1.2: Vista trasera de carretilla...
1.3.1.2 Imagen Representativa del AFW11 Embalado para tipo Transporte Terrestre o Marítimo en Contenedor Cerrado La manipulación del AFW11 con una carretilla elevadora debe realizarse de la siguiente manera: Figura 1.7: Vista trasera de carretilla Figura 1.8: Vista trasera de la carretilla Figura 1.6: Carretilla elevadora de...
Page 49
Figura 1.12: Ojal de izamiento con detalle de explosión La distribución de los ojales de izamiento en el conjunto montado debe seguir la disposición conforme la imagen de abajo: Figura 1.13: Distribución de los ojales de izamiento 49 | AFW11...
Page 51
Blanco = Sin módulo de expansión de I/Os Con módulo de expansión de I/Os IOB-01 Con módulo de expansión de I/Os IOE-02 13 – Grado de Protección del Tablero IP42 Grado de protección IP42 IP54 Grado de protección IP54 51 | AFW11...
La protección del CFW-11 está de acuerdo con el CFW-11 - Guía de Fusibles Recomendados, disponible en el sitio WEG. 2.4 ACCESORIOS 2.4.1 Tarjeta IOE-02 Módulo CFW11 PT100 / 5 canales de sensores de temperatura (IOE-02 / SLOT 1). Figura 2.1: Tarjeta IOE-02 Figura 2.2: Conexión eléctrica IOE-02 AFW11 | 52...
Módulo de expansión de I / O CFW11 (IOB-01 / SLOT 1). Contenido de la tarjeta IOB-01: una entrada analógica aislada, dos salidas analógicas, dos entradas digitales aisladas y dos salidas digitales aisladas. Figura 2.3: Tarjeta IOB-01 Figura 2.4: Conexión eléctrica IOB-01 53 | AFW11...
Una red DeviceNet puede contener hasta 64 dispositivos, direccionados de 0 a 63. Puede ser utilizado cualquiera de ellos. No hay ninguna restricción, aunque se deba evitar el 63, ya que éste suele ser utilizado para fines de comisionamiento. � 112131415 ����� Figura 2.6: Devicenet AFW11 | 54...
Figura 2.8: Profinet 2.4.7 Comunicación Ethernet IP Módulo CFW11 Ethernet IP (ETHERNETIP-2P-05 / SLOT 4). Ethernet es una tecnología para interconexión de redes locales (LAN) con base en el envío de cuadros. Figura 2.9: Ethernet 55 | AFW11...
Esto disminuye el dv/dt (tasa de variación de la tensión) de los pulsos generados en la salida del convertidor. El opcional debe ser utilizado con motores WEG instalados entre 100 a 300 m, y cuando sean utilizados motores de demás fabricantes instalados entre 0 a 300 m. Figura 2.11: Representación eléctrica del reactor AFW11 | 56...
F - Módulo de tarjeta accesorio C - Tapa superior G - Módulo de memoria FLASH D - Ventilador con soporte de fijación H - Tapa frontal I – HMI Figura 2.12: Partes del CFW11 tamaño A 57 | AFW11...
7 - Grado de protección del accionamiento 16 - Frecuencia nominal de entrada 8 - Certificaciones (cuando haya) 17 - Valor de la tensión nominal de comando del accionamiento 9 - QRCode conteniendo informaciones internas de fabricación Figura 2.13: Detalle de la Etiqueta AFW11 | 58...
El accionamiento básico recomendado para el CFW-11 es esquemáticamente presentado en las Figura 3.1 de la página Figura 3.2 de la página Figura 3.3 de la página 61 Figura 3.4 de la página corrientes de 3 A a 1141 A. Figura 3.1: Unifilar AFW11 3-31 A AFW11 | 59...
Page 60
ESQUEMAS TÍPICOS Figura 3.2: Unifilar AFW11 38-760 A 60 | AFW11...
Page 61
ESQUEMAS TÍPICOS Figura 3.3: Unifilar AFW11 MEC H 795-1141 A AFW11 | 61...
Page 62
ESQUEMAS TÍPICOS Figura 3.4: Unifilar AFW11 MEC H 478-625 A 62 | AFW11...
El AFW11 debe ser fijado (anclado), tras la colocación en el piso de concreto, con 4 ancladores 3/8" x 3", en los acoplamientos entre columnas pueden ser solamente dos en diagonal.
Page 64
INSTALACIÓN Figura 4.3: Detalles de fijación AFW Tamaño E Figura 4.4: Detalles de fijación AFW Tamaño F Figura 4.5: Detalles de fijación AFW Tamaño G 64 | AFW11...
Tornillo hendidura/phillips cabeza bridada 6x60 mm. Los detalles de fijación en concreto y del ladrillo hueco pueden ser encontrados en la a continuación. Figura 4.7: Detalles de fijación de los tableros en pared de concreto y ladrillo hueco AFW11 | 65...
TRANSFORMADOR CONFORME CUADRO ABAJO PRIMÁRIO DO TRANSFORMADOR TRANSFORMER PRIMARY PRIMARIO DEL TRANSFORMADOR TENSÃO CONECTAR LIGAR VOLTAGE JUMPE CONNECT TENSIÓN JUMPER CONECTAR 380 V 440 V 460 V 480 V Figura 4.8: Detalles mecánicos: Tamaños A y B 66 | AFW11...
Page 67
REALIZAR CONEXIÓN DEL PRIMARIO DEL TRANSFORMADOR CONFORME CUADRO ABAJO PRIMÁRIO DO TRANSFORMADOR TRANSFORMER PRIMARY PRIMARIO DEL TRANSFORMADOR TENSÃO CONECTAR LIGAR VOLTAGE JUMPE CONNECT TENSIÓN JUMPER CONECTAR 380 V 440 V 460 V 480 V Figura 4.9: Detalles mecánicos: Tamaño C AFW11 | 67...
Page 68
REALIZAR CONEXIÓN DEL PRIMARIO DEL TRANSFORMADOR CONFORME CUADRO ABAJO PRIMÁRIO DO TRANSFORMADOR TRANSFORMER PRIMARY PRIMARIO DEL TRANSFORMADOR TENSÃO CONECTAR LIGAR VOLTAGE JUMPE CONNECT TENSIÓN JUMPER CONECTAR 380 V 440 V 460 V 480 V Figura 4.10: Detalles mecánicos: Tamaño D 68 | AFW11...
Page 69
TRANSFORMADOR CONFORME CUADRO ABAJO PRIMÁRIO DO TRANSFORMADOR TRANSFORMER PRIMARY PRIMARIO DEL TRANSFORMADOR TENSÃO CONECTAR LIGAR VOLTAGE JUMPE CONNECT TENSIÓN JUMPER CONECTAR 380 V 440 V 460 V 480 V Figura 4.11: Detalles mecánicos: Tamaño E - IP54 AFW11 | 69...
Page 70
TRANSFORMADOR CONFORME CUADRO ABAJO PRIMÁRIO DO TRANSFORMADOR TRANSFORMER PRIMARY PRIMARIO DEL TRANSFORMADOR TENSÃO CONECTAR LIGAR VOLTAGE JUMPE CONNECT TENSIÓN JUMPER CONECTAR 380 V 440 V 460 V 480 V Figura 4.12: Detalles mecánicos: Tamaño F – IP54 70 | AFW11...
Page 71
TRANSFORMADOR CONFORME CUADRO ABAJO PRIMÁRIO DO TRANSFORMADOR TRANSFORMER PRIMARY PRIMARIO DEL TRANSFORMADOR TENSÃO CONECTAR LIGAR VOLTAGE JUMPE CONNECT TENSIÓN JUMPER CONECTAR 380 V 440 V 460 V 480 V Figura 4.13: Detalles mecánicos: Tamaño G – IP54 AFW11 | 71...
Page 72
TRANSFORMADOR CONFORME CUADRO ABAJO PRIMÁRIO DO TRANSFORMADOR TRANSFORMER PRIMARY PRIMARIO DEL TRANSFORMADOR TENSÃO CONECTAR LIGAR VOLTAGE JUMPE CONNECT TENSIÓN JUMPER CONECTAR 380 V 440 V 460 V 480 V Figura 4.14: Detalles mecánicos: Tamaño H – IP54 72 | AFW11...
Para la puesta a tierra no utilice el neutro, sino un conductor específico. ¡PELIGRO! La tensión de la red de alimentación debe ser compatible con el rango de tensión del AFW11. Efectuar el montaje y la conexión de todos los aparatos que fueron enviados en separado, por motivos de transporte, verificando cuidadosamente la posición y la conexión de éstos, en los respectivos dibujos.
Page 74
INSTALACIÓN Figura 4.15: Detalle eléctrico del circuito auxiliar 1000 VOGEL LEIDE 74 | AFW11...
185 SIL 4x95 SIL 2x95 SIL 3x150 SIL 2x120 SIL ¡NOTA! Para el correcto dimensionamiento de los cables, tomar en cuenta las condiciones de instalación, máxima caída de tensión permitida y utilizar normas de instalaciones eléctricas locales. 76 | AFW11...
INSTALACIÓN 4.4.3 Conexión de la Red de Alimentación La conexión del AFW11 a la red eléctrica debe ser hecha directamente en los terminales L1, L2, L3 del disyuntor/seccionadora Q1 (Fase R/S/T) y en la Barra Tierra (puesta a tierra de la estructura - PE) conforme Figura 4.16 de la página 77...
Utilizar los botones de enciende y apaga para comandar el sistema. ¡NOTA! En caso de utilización remota se debe verificar el botón de emergencia remoto y se puede comandar el sistema por los botones remotos. AFW11 | 78...
Cuando ocurre desarme del disyuntor de protección del comando, identificar y corregir su causa antes de reencender el equipo. En caso de que el tablero presente algún defecto no mencionado arriba, contactar a la Asistencia Técnica WEG, a través del teléfono 0800-7010701. AFW11 | 79...
DIAGRAMA UNIFILAR 7 DIAGRAMA UNIFILAR Figura 7.1: Tamaños A, B, C y D - 3 A a 88 A AFW11 | 80...
Page 81
DIAGRAMA UNIFILAR Figura 7.2: Tamaños E, F y G - 105 A a 760 A 81 | AFW11...
Page 82
DIAGRAMA UNIFILAR Figura 7.3: Tamaño H – 478 A a 625 A AFW11 | 82...
Page 83
DIAGRAMA UNIFILAR Figura 7.4: Tamaño H – 628 A a 1141 A 83 | AFW11...
Page 84
Manual de Instalação AFW11 Documento: 10009619203 Material: 16606370 Revisão: 02 Idioma: Português Data da Publicação: 06/2023...
Page 85
SUMÁRIO DAS REVISÕES A informação abaixo descreve as revisões ocorridas neste manual. Versão Revisão Descrição Primeira edição. Revisão geral. Revisão geral.
Page 86
1.2 RECOMENDAÇÕES PRELIMINARES ....................87 1.3 MANUSEIO ............................88 1.3.1 Manuseio dos Acionamentos ....................88 1.3.1.1 Imagem Representativa do AFW11 Embalado para Tipo de Transporte Terrestre . 88 1.3.1.2 Imagem Representativa do AFW11 Embalado para tipo de Transporte Terrestre ou Marítimo em Container Fechado ..............89 1.3.1.3 Imagem Representativa do AFW11 Manuseado pelos Olhais de Içamento ..89...
INSTRUÇÕES DE SEGURANÇA 1 INSTRUÇÕES DE SEGURANÇA Este manual contém as informações necessárias para o uso correto do AFW11. As instruções a seguir são de extrema importância para um bom desempenho, e devem ser integralmente observadas durante a instalação, manutenção e operação do sistema. A não observância das instruções de segurança, podem ocasionar ferimentos, morte ou danos no equipamento.
1.3 MANUSEIO 1.3.1 Manuseio dos Acionamentos 1.3.1.1 Imagem Representativa do AFW11 Embalado para Tipo de Transporte Terrestre O manuseio do AFW11 com empilhadeira deverá ser realizado da seguinte forma: Figura 1.1: Empilhadeira Figura 1.2: Vista posterior empilha- Figura 1.3: Vista posterior empilha-...
INSTRUÇÕES DE SEGURANÇA 1.3.1.2 Imagem Representativa do AFW11 Embalado para tipo de Transporte Terrestre ou Marítimo em Container Fechado O manuseio do AFW11 com empilhadeira deverá ser realizado da seguinte forma: Figura 1.7: Vista posterior empilha- Figura 1.8: Vista posterior empilha- Figura 1.6: Empilhadeira...
Page 90
Estrutura Reforço metálico Arruela de pressão Porca sextavada Figura 1.12: Detalhe explodido olhal de içamento A distribuição dos olhais de içamento no conjunto montado deve seguir a disposição conforme imagem abaixo: Figura 1.13: Distribuição olhais de içamento 90 | AFW11...
Page 92
Branco = Sem módulo de expansão de I/Os Com módulo de expansão de I/Os IOB-01 Com módulo de expansão de I/Os IOE-02 13 - Grau de Proteção do Painel IP42 Grau de proteção IP42 IP54 Grau de proteção IP54 92 | AFW11...
A proteção do CFW-11 está de acordo com o CFW-11 - Guia de Fusíveis Recomendados, disponível no site WEG. 2.4 ACESSÓRIOS 2.4.1 Cartão IOE-02 Módulo CFW11 PT100 / 5 canais de sensores de temperatura (IOE-02 / SLOT 1). Figura 2.1: Cartão IOE-02 Figura 2.2: Ligação elétrica IOE-02 AFW11 | 93...
Módulo de expansão de I / O CFW11 (IOB-01 / SLOT 1). Conteúdo do cartão IOB-01: uma entrada analógica isolada, duas saídas analógicas, duas entradas digitais isoladas e duas saídas digitais isoladas. Figura 2.3: Cartão IOB-01 Figura 2.4: Ligação elétrica IOB-01 94 | AFW11...
Uma rede DeviceNet pode conter até 64 dispositivos, endereçados de 0 a 63. Qualquer um destes pode ser utilizado. Não há qualquer restrição, embora se deva evitar o 63, pois este costuma ser utilizado para fins de comissionamento. 11 2131 aJ 15 ����� Figura 2.6: Devicenet AFW11 | 95...
Figura 2.8: Profinet 2.4.7 Comunicação Ethernet IP Módulo CFW11 Ethernet IP (ETHERNETIP-2P-05 / SLOT 4). Ethernet é uma tecnologia para interconexão de redes locais (LAN) com base no encaminhamento de quadros. Figura 2.9: Ethernet 96 | AFW11...
(taxa de variação da tensão) dos pulsos gerados na saída do inversor. O opcional deve ser utilizado com motores WEG instalados entre 100 a 300 m, e quando utilizado motores de demais fabricantes instalados entre 0 a 300 m. Figura 2.11: Representação elétrica do reator AFW11 | 97...
F - Módulo de cartão acessório C - Tampa superior G - Módulo de memória FLASH D - Ventilador com suporte de fixação H - Tampa frontal I – HMI Figura 2.12: Partes do CFW11 mecânica A 98 | AFW11...
7 - Grau de proteção do acionamento 16 - Frequência nominal de entrada 8 - Cerificações (quando houver) 17 - Valor da tensão nominal de comando do acionamento 9 - QRCode contendo informações internas de fabricação Figura 2.13: Detalhe da Etiqueta AFW11 | 99...
O acionamento básico recomendado para o CFW-11 é esquematicamente apresentado nas Figura 3.1 na página 100, Figura 3.2 na página 101, Figura 3.3 na página 102 e Figura 3.4 na página 103, correntes de 3 A até 1141 A. Figura 3.1: Unifilar AFW11 3-31 A AFW11 | 100...
Page 101
ESQUEMAS TÍPICOS Figura 3.2: Unifilar AFW11 38-760 A 101 | AFW11...
Page 102
ESQUEMAS TÍPICOS Figura 3.3: Unifilar AFW11 MEC H 795-1141 A AFW11 | 102...
Page 103
ESQUEMAS TÍPICOS Figura 3.4: Unifilar AFW11 MEC H 478-625 A 103 | AFW11...
Os painéis devem ser instalados na sala elétrica de acordo com o layout abaixo. A fixação dos painéis deve ser executada em piso de concreto ou metálico devidamente nivelado. O AFW11 deve, após a colocação no piso de concreto, ser fixada (chumbada) com 4 chumbadores 3/8" x 3", nos acoplamentos entre colunas podem ser somente dois em diagonal.
Page 105
INSTALAÇÃO Figura 4.3: Detalhes de fixação AFW Mecânica E Figura 4.4: Detalhes de fixação AFW Mecânica F Figura 4.5: Detalhes de fixação AFW Mecânica G 105 | AFW11...
Parafuso fenda/phillips cabeça flangeada 6x60 mm. Os detalhes de fixação em concreto e tijolo oco podem ser observados nas figuras a seguir. Figura 4.7: Detalhes de fixação dos painéis em parede de concreto e tijolo oco AFW11 | 106...
TRANSFORMADOR CONFORME CUADRO ABAJO PRIMÁRIO DO TRANSFORMADOR TRANSFORMER PRIMARY PRIMARIO DEL TRANSFORMADOR TENSÃO CONECTAR LIGAR VOLTAGE JUMPE CONNECT TENSIÓN JUMPER CONECTAR 380 V 440 V 460 V 480 V Figura 4.8: Detalhes mecânicos: Mecânica A e B 107 | AFW11...
Page 108
REALIZAR CONEXIÓN DEL PRIMARIO DEL TRANSFORMADOR CONFORME CUADRO ABAJO PRIMÁRIO DO TRANSFORMADOR TRANSFORMER PRIMARY PRIMARIO DEL TRANSFORMADOR TENSÃO CONECTAR LIGAR VOLTAGE JUMPE CONNECT TENSIÓN JUMPER CONECTAR 380 V 440 V 460 V 480 V Figura 4.9: Detalhes mecânicos: Mecânica C AFW11 | 108...
Page 109
REALIZAR CONEXIÓN DEL PRIMARIO DEL TRANSFORMADOR CONFORME CUADRO ABAJO PRIMÁRIO DO TRANSFORMADOR TRANSFORMER PRIMARY PRIMARIO DEL TRANSFORMADOR TENSÃO CONECTAR LIGAR VOLTAGE JUMPE CONNECT TENSIÓN JUMPER CONECTAR 380 V 440 V 460 V 480 V Figura 4.10: Detalhes mecânicos: Mecânica D 109 | AFW11...
Page 110
TRANSFORMADOR CONFORME CUADRO ABAJO PRIMÁRIO DO TRANSFORMADOR TRANSFORMER PRIMARY PRIMARIO DEL TRANSFORMADOR TENSÃO CONECTAR LIGAR VOLTAGE JUMPE CONNECT TENSIÓN JUMPER CONECTAR 380 V 440 V 460 V 480 V Figura 4.11: Detalhes mecânicos: Mecânica E - IP54 AFW11 | 110...
Page 111
TRANSFORMADOR CONFORME CUADRO ABAJO PRIMÁRIO DO TRANSFORMADOR TRANSFORMER PRIMARY PRIMARIO DEL TRANSFORMADOR TENSÃO CONECTAR LIGAR VOLTAGE JUMPE CONNECT TENSIÓN JUMPER CONECTAR 380 V 440 V 460 V 480 V Figura 4.12: Detalhes mecânicos: Mecânica F – IP54 111 | AFW11...
Page 112
TRANSFORMADOR CONFORME CUADRO ABAJO PRIMÁRIO DO TRANSFORMADOR TRANSFORMER PRIMARY PRIMARIO DEL TRANSFORMADOR TENSÃO CONECTAR LIGAR VOLTAGE JUMPE CONNECT TENSIÓN JUMPER CONECTAR 380 V 440 V 460 V 480 V Figura 4.13: Detalhes mecânicos: Mecânica G – IP54 AFW11 | 112...
Page 113
TRANSFORMADOR CONFORME CUADRO ABAJO PRIMÁRIO DO TRANSFORMADOR TRANSFORMER PRIMARY PRIMARIO DEL TRANSFORMADOR TENSÃO CONECTAR LIGAR VOLTAGE JUMPE CONNECT TENSIÓN JUMPER CONECTAR 380 V 440 V 460 V 480 V Figura 4.14: Detalhes mecânicos: Mecânica H – IP54 113 | AFW11...
Para aterramento não utilize o neutro e sim um condutor específico. PERIGO! A tensão da rede de alimentação deve ser compatível com a faixa de tensão do AFW11. Efetuar a montagem e ligação de todos os aparelhos que foram enviados em separado, por motivos de transporte, verificando cuidadosamente a posição e a conexão destes, nos respectivos desenhos.
Page 115
INSTALAÇÃO Figura 4.15: Detalhe elétrico do circuito auxiliar 1000 VOGEL LEIDE 115 | AFW11...
2x185 SIL 185 SIL 4x95 SIL 2x95 SIL 3x150 SIL 2x120 SIL NOTA! Para o correto dimensionamento dos cabos, levar em conta as condições de instalação, máxima queda de tensão permitida e utilizar normas de instalações elétricas locais. 117 | AFW11...
INSTALAÇÃO 4.4.3 Conexão da Rede de Alimentação A conexão do AFW11 à rede elétrica deve ser feita diretamente nos terminais L1, L2, L3 do disjuntor/ seccionadora Q1 (Fase R/S/T) e na Barra Terra (aterramento da estrutura - PE) conforme Figura 4.16 na...
Verificar sinalização de "Defeito", se acionado, resolve-lo antes de seguir com o procedimento. Utilizar os botões de liga e desliga para comandar o sistema. NOTA! Em caso de utilização remota deve-se verificar o botão de emergência remoto e pode-se comandar o sistema pelos botões remotos. AFW11 | 119...
Quando ocorre desarme do disjuntor de proteção do comando, identificar e sanar sua causa antes de religar o equipamento. Caso o painel apresente algum defeito não mencionado acima, contatar a Assistência Técnica WEG através do telefone 0800-7010701. AFW11 | 120...