Setting Up Communication Between Pcm600 And The Ied; When Ied Has Blank Front Panel; When Ied Has Front Port With Rj-45 - Hitachi Relion REB670 Commissioning Manual

Table of Contents

Advertisement

1MRK 505 372-UEN Rev. K
If the upper row in the window indicates 'Fail' instead of 'Ready' and the green LED flashes, an
internal failure in the IED has been detected.
4.5
Setting up communication between PCM600 and the
IED
The communication between the IED and PCM600 is independent of the communication protocol
used within the substation or to the NCC.
4.5.1

When IED has blank front panel

IED with blank front panel will not have front port. Instead in the IED's AP1 will be turned on which
will have the default IP address 192.168.1.10 and subnet mask 255.255.255.0. If the user wants to
change the default IP address, use RIA600 or PCM600.
4.5.2

When IED has front port with RJ-45

The communication media is always Ethernet and the used transport layer is TCP/IP.
Each IED has an RJ-45 Ethernet interface connector on the front. The front Ethernet connector is
recommended to be used for communication with PCM600.
When an Ethernet-based station protocol is used, PCM600 communication can use the same
Ethernet port and IP address.
To connect PCM600 to the IED, two basic variants must be considered.
Direct point-to-point link between PCM600 and the IED front port. The front port can be seen as
a service port.
A link via a station LAN or from remote via a network.
The physical connection and the IP address must be configured in both cases to enable
communication.
The communication procedures are the same in both cases.
1.
If needed, set the IP address for the IEDs.
2.
Set up the PC or workstation for a direct link (point-to-point), or
3.
Connect the PC or workstation to the LAN/WAN network.
4.
Configure the IED IP addresses in the PCM600 project for each IED to match the IP addresses
of the physical IEDs.
Setting up IP addresses
Communication between the IED and PCM600 is enabled from the LHMI. The IP address and the
corresponding communication subnetwork mask must be set via the Ethernet configuration tool
(ECT) for each available Ethernet interface in the IED. Each Ethernet interface has a default factory
IP address when the IED is delivered. The IP adress and the subnetwork mask might have to be
reset when an additional Ethernet interface is installed or an interface is replaced.
DHCP is available for the front port, and a device connected to it can thereby obtain an automatically
assigned IP address via the local HMI path Main menu/ Configuration/ Communication/ Ethernet
configuration/ Front port/ DHCP.
Busbar protection REB670
Commissioning manual
DHCP is not available on this port.
© 2017 - 2022 Hitachi Energy. All rights reserved
Section 4
Starting up
SEMOD58570-5 v16
GUID-8BBF8B90-8E20-428D-82EE-18F36D5C8054 v1
GUID-9EE3E4F1-1BD8-49D3-9221-A43D7F8A99AD v1
39

Advertisement

Table of Contents
loading

This manual is also suitable for:

Relion 670 series

Table of Contents