Danfoss KP 15 Installation Manual page 2

Pressure switch

Advertisement

CAUTION:
Disconnect power supply before wiring connections are made or service to avoid possible electrical shock or damage
to equipment. Do never touch live parts with your fingers or with any tool.
LP side: A-C opens on pressure drop
HP side: A-C opens on pressure rise
LP = Low Pressure
-1 bar (P
)(30 inHg)
e
LP, aut. reset
Manual trip function
TRIP:
use FINGERS ONLY!
(Do NOT use screwdriver)
Adjustment
0.7 bar (10 psi)/rev.
2 | AN211686434433en-000701
Electrical rating - General
AC 1: 16 A
LR 112A
AC 3: 16 A
AC 15: 10 A
Short circuit protection:
Fuse 16 Amp
LP = Low Pressure
-1 bar (P
LP, man. reset
0.15 bar (2 psi)/rev.
2.3 bar
(33.5 psi)/rev.
6 mm
(15/64 in)
When used acc. to UL regulations
DC 13
400 V
12 W
AC
220 V
Use copper wire only
Tightening torque 20 lb. in
)(30 inHg)
e
Convertible reset
KP 15: LP/HP convertible, KP 17WB: HP convertible
Insert a screwdriver into the slot on the lock disc and
turn it to desired reset configuration.
Do not turn the screw on the lock disc as it may damage
the convertible reset mechanism.
Reset options
LP man.
LP auto.
HP man
HP man
Note: Do not select automatic reset if safety of the system
requires manual reset.
Note: Selected reset configuration may be protected against
unauthorized actions applying a seal.
Listed refrigeration controller
61B5
Voltage
FL
LR
Contacts
AC
DC
A
A
240
8
48
A - B
120
16
96
A - C
240
A - D
240
HP = High Pressure
HP
LP auto.
HP auto.
© Danfoss | Climate Solutions | 2021.05
Resist.
Pilot
load
duty
8 A
3 A
16 A
12 W
50 VA
LP man.
HP auto.