Alarmtech PSV 2435-40 Instruction Manual

Advertisement

Instruction manual
DESCRIPTION
PSV 2435-40 is an up-to date power supply unit with battery
backup compliant with EN standards. Unit provides all features
required by EN 50131-6:2008, security
Distinctive and unique feature of PSV 2435-40 is invented by
Alarmtech ViP mode – Voltage-in-Parallel. Power supply units
with ViP feature can be connected in parallel both (+) and (-) on
one common power bus without a need of additional synchroni-
zation. Connected units will share load on a bus. ViP feature can
be used to build distributed and redundant power systems. It can
be also used to compensate voltage drops on a bus by placing
power supply units in distant bus sections.
Power conversion is based on high frequency SMPS regulator
providing high conversion efficiency. Low losses inside unit pre-
serve batteries from overheating shortening battery life time.
Computerized battery recharging circuit works in constant poten-
tial – limited current mode – the best mode to provide the longest
possible battery life time.
Power unit is equipped with built-in diagnostic system detecting
and signalling mains failure, different battery failures including
end-of-life warning, output faults like low voltage or broken fuse.
APPLICATIONS
 Power supply system for 24 V installations
 Distributed power supply systems with built-in redundancy
 Power supply systems for access control, fire and intruder
alarm installations
BLOCK DIAGRAM
230 VAC
L
PE
N
© 2015 Alarmtech
Power Supplies
.
grade 3
Remote battery
Signalling outputs
EPS, APS, OUT, SAB, SDT
Power supply unit
PSV-2435
SMPS w. LLC controller
ViP mode, security grade 3
12V battery
12V battery
40 Ah
40 Ah
MAIN FEATURES
 Security grade 3 (EN 50131-6:2008)
 Type A – mains supply with rechargeable battery
 Basic parameters in grade 3 (default):
 Total rated output: 1 A
(30 h in battery mode with 40 Ah batteries)
 Battery recharging current: 1.5 A
(providing recharging time below 24 h)
 Total rated maximal output to installation: 2 A
 Basic parameters in grade 2:
(PSV-2435-40 can be downgraded from default grade 3 to
grade 2 with the help of PSVlink software)
 Total rated output: 2.6 A
(12 h in battery mode with 40 Ah batteries)
 Battery recharging current: 0.5 A
(providing recharging time below 72 h)
 Total rated maximal output to installation: 3 A
 Total current capacity of power unit – 27.6V, 3.5 A
 ViP (Voltage-in-Parallel) feature increasing reliability and ca-
pacity of power supply systems – power supplies with ViP fea-
ture can be connected in parallel to same bus without need
for additional synchronization
 Capable to work with pack of two 12 V/40 Ah sealed lead acid
batteries
 Short circuit and overload protection
 Detection of no mains supply (EPS fault)
 Detection of different battery faults (APS fault) – not con-
nected, low voltage, high internal resistance
 Detection of low output voltage (OUT fault)
 Detection and LED identification of broken fuses
 Detection of power unit failure
 Deep discharge protection of battery (DDP)
 Remote and local battery testing
 Tamper security provided – case opening and pry-off
 Optional Fuse Card with 6 fused outputs and Ground Fault
Detector (model PSV FC24-6)
test
Front panel
24 VDC output
EPS – External Power Supply (mains)
APS – Alternative Power Source (battery)
OUT - Output voltage
SAB – Sabotage
SDT – Storage Device (battery) Test
1 / 4
Battery 40 Ah/Security grade 3
Optional Fuse Card
Signalling outputs
PSV FC24-6
6 fused
Fuse Card
output
PSV FC24-6
channels
PE
PSV 2435-40 manual 1511en
24 VDC/3.5 A
PSV 2435-40

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the PSV 2435-40 and is the answer not in the manual?

Questions and answers

Summary of Contents for Alarmtech PSV 2435-40

  • Page 1 DESCRIPTION MAIN FEATURES  Security grade 3 (EN 50131-6:2008) PSV 2435-40 is an up-to date power supply unit with battery  Type A – mains supply with rechargeable battery backup compliant with EN standards. Unit provides all features  Basic parameters in grade 3 (default):...
  • Page 2  Make internal connection in battery pack connecting left bat-  Make sure that cable delivering 230VAC to PSV 2435-40 is dis- tery (+) with right battery (-) with the help of grey cable connected from mains ...
  • Page 3 Front panel / USB link Open: battery circuit enabled OUT fault output (isolated) Storage Device Test ground (-) Closed: battery circuit disabled Storage Device Test input (*) Closed-to-open: battery test triggered © 2015 Alarmtech 3 / 4 PSV 2435-40 manual 1511en...
  • Page 4 Environmental Class acc. to EN 50130-5:1998: Class II Weight without batteries: approx. 11 kg Weight with batteries: approx. 37 kg Dimensions: 440 x 425 x 200 mm (W x H x D) Compliance: © 2015 Alarmtech 4 / 4 PSV 2435-40 manual 1511en...

Table of Contents