Alarmtech PSV 2435-12 Instruction Manual

Battery 12 ah/security

Advertisement

Quick Links

Instruction manual

DESCRIPTION

PSV 2435-12 is an up-to date power supply unit with battery
backup compliant with EN standards. Unit provides all features
required by EN 50131-6:2008, security grade 3.
Distinctive and unique feature of PSV 2435-12 is invented by
Alarmtech ViP mode – Voltage-in-Parallel. Power supply units
with ViP feature can be connected in parallel both (+) and (-) on
one common power bus without a need of additional synchroni-
zation. Connected units will share load on a bus. ViP feature can
be used to build distributed and redundant power systems. It can
be also used to compensate voltage drops on a bus by placing
power supply units in distant bus sections.
Power conversion is based on high frequency SMPS regulator
providing high conversion efficiency. Low losses inside unit pre-
serve batteries from overheating shortening battery life time.
Computerized battery recharging circuit works in constant poten-
tial – limited current mode – the best mode to provide the longest
possible battery life time.
Power unit is equipped with built-in diagnostic system detecting
and signalling mains failure, different battery failures including
end-of-life warning, output faults like low voltage or broken fuse.

APPLICATIONS

 Power supply system for 24 V installations
 Distributed power supply systems with built-in redundancy
 Power supply systems for access control, fire and intruder
alarm installations

BLOCK DIAGRAM

EPS – External Power Supply (mains)
APS – Alternative Power Source (battery)
OUT - Output voltage
SAB – Sabotage
SDT – Storage Device (battery) Test
© 2016 Alarmtech –
www.alarmtech.se
Power Supplies
L
230 VAC
PE
input
N

MAIN FEATURES

 Security grade 3 (EN 50131-6:2008)
 Type A – mains supply with rechargeable battery
 Total rated output in grade 3:
 0.25 A (30 h in battery mode with 12 Ah batteries)
 Total rated output in grade 2:
 0.74 A (12 h in battery mode with 12 Ah batteries)
 Total rated maximal output to installation: 3.0 A
 Battery recharging current – 0.5 A, providing recharging time
below 24 h
 Total current capacity of power unit – 27.6V, 3.5 A
 ViP (Voltage-in-Parallel) feature increasing reliability and ca-
pacity of power supply systems – power supplies with ViP fea-
ture can be connected in parallel to same bus without need
for additional synchronization
 Capable to work with pack of two 12 V/12 Ah sealed lead acid
batteries
 Short circuit and overload protection
 Detection of no mains supply (EPS fault)
 Detection of different battery faults (APS fault) – not con-
nected, low voltage, high internal resistance
 Detection of low output voltage (OUT fault)
 Detection and LED identification of broken fuses
 Detection of power unit failure
 Deep discharge protection of battery (DDP)
 Remote and local battery testing
 Tamper security provided – case opening and pry-off
230 VAC
_
+
Power Supply 24 VDC
Power unit
ViP
PSV 2435
output
Signalling outputs
SDT
EPS, APS, OUT, SAB
input
Fault signalling
Remote battery
outputs
test
1 / 4
Battery 12 Ah/Security grade 3
OUT +
24 VDC Output
OUT -
BAT +
BAT -
12 V battery
12 V battery
12 Ah
12 Ah
Battery pack
2x 12 V/12
Ah
PSV 2435-12 manual 1629en
24 VDC/3.5 A
PSV 2435-12

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the PSV 2435-12 and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for Alarmtech PSV 2435-12

  • Page 1 DESCRIPTION MAIN FEATURES  Security grade 3 (EN 50131-6:2008) PSV 2435-12 is an up-to date power supply unit with battery  Type A – mains supply with rechargeable battery backup compliant with EN standards. Unit provides all features  Total rated output in grade 3: required by EN 50131-6:2008, security grade 3.
  • Page 2 12 V/12 Ah Case fixing hole Case fixing hole PSV 2435-12 power supply installation and start-up procedure:  Fix unit in destination place using 4 fixing holes 2435-12 unit and cooperating units (outputs EPS, APS, OUT,  Place two sealed lead acid batteries 12 V/ 12 Ah in battery SAB, input –SDT*)
  • Page 3: Front Panel

    OUT fault output (isolated) Storage Device Test ground (-) Front panel / USB link Storage Device Test input (*) Open: battery circuit enabled Closed: battery circuit disabled Closed-to-open: battery test triggered © 2016 Alarmtech – www.alarmtech.se 3 / 4 PSV 2435-12 manual 1629en...
  • Page 4 Environmental Class acc. to EN 50130-5:1998: Class II Weight without batteries: approx. 3.3 kg Weight with batteries: approx. 11.4 kg Dimensions: 345 x 325 x 130 mm (W x H x D) Compliance: © 2016 Alarmtech – www.alarmtech.se 4 / 4 PSV 2435-12 manual 1629en...