Connection between WWS 100 and WSC 3x0 Plus

X5 or X6
(Break glass unit 1 & 2)
1
24V
2
Comm
3
0V
The WWS 100 Sensor is connected to the 5X or
6X on the smoke panel (the input for break glass
unit or Master-Slave connection).
The max number of sensors, which can be
connected to the smoke panel depends of type
of smoke panel and number of break glass units
(WSK 50x) also connected to the smoke panel.
Max number of sensor and break glass units
connected to the smoke panel (plus version):
1
2
3
4
5
6
7
8
9 10 11 12 13 14 15 16
WSC 310 P:
• 2 x WWS 100 + 10 x WSK 50x
WSC 320 P:
• 10 x WWS 100 + 10 x WSK 50x
Only 2 of the WSK 50x (1 per line) can be type
WSK 501 / 502, to which keypads and smoke
detectors can be connected. The remaining break
glass units must be type WSK 503/504.