Agricultural Or Horticultural Facilities According To Din Vde 0100-705; Damp And Wet Areas, Rooms And Outdoor Areas According To Din Vde 0100-737 - OBO Bettermann A Series Mounting And Installation

Junction boxes
Table of Contents

Advertisement

Mounting and installation information for junction boxes
Electrical resources used in areas of pools of swimming
baths and other pools must correspond at least to the
following protection ratings:
Area
Outdoors,
for cleaning work with
spray water
0
1
2
3.4. Agricultural or horticultural facilities according
to DIN VDE 0100-705
In these areas, there are different requirements for the
switch-off devices of the circuits, but also requirements
for the materials used.
In final circuits with sockets, there must be an offset cur-
rent protection device with a rated differential current =
30 mA.
In all other circuits, except those supplying distributors,
there must be an offset current unit with a rated differen-
tial current = 300 mA.
With regard to the material used for the junction/con-
nection sockets, before the installation it is necessary to
check which chemical concentrations are present in the
environment. This has a serious influence on the resist-
ance of the products used.
Examples:
Stables, chicken coops, pigsties, breeding spaces, stor-
age locations for straw, fertilisers and cereals, etc.
3.5. Damp and wet areas, rooms and outdoor areas
according to DIN VDE 0100-737
Important protection requirements:
In damp and wet areas and rooms, electrical resources
must at least be protected against water droplets (protec-
tion rating IPX1).
12
Outdoors,
without spray water
IPX5/IPX8
IPX8
IPX5
IPX4
IPX5
IPX4
Indoors,
for cleaning work with
spray water
IPX5/IPX8
IPX5
IPX5
In areas and rooms, in which spray water is used and the
resources are normally not sprayed directly for cleaning
purposes, the resources must have at least spray water
protection (protection rating IPX4). In areas and rooms
in which spray water is used, resources that are direct-
ly subjected to the water jet must, with regard to water
protection, have a protection rating suitable to being sub-
jected to a water jet or have sufficient additional protec-
tion that does not impair perfect operation of a resource
protected in such a manner.
Examples:
Canteens, unheated and unventilated cellars, laundries,
refrigerators, greenhouses, laundrettes, etc.
Junction box in greenhouse
Indoors,
without spray water
IPX8
IPX4
IPX4