Electrode Setting; Burner Start-Up Cycle; Adjustments, To Avoid Flame - Detachment, At Burner - Ignition (Only For Gas Oil) - Riello COH 180 Installation, Use And Maintenance Instructions

Kerosene and gas oil burner
Table of Contents

Advertisement

8.7

Electrode setting

The position of the electrodes cannot be regulat-
ed. In case of failure, check that the measure-
ments as shown on the figure are respected.
WARNING
Before removing or assembling the nozzle, loosen the screw
A)(Fig. 15) and move the electrodes ahead.
8.8

Burner start-up cycle

Normal
Thermostat
Motor
Ignition transformer
Valve
Flame
Lock-out lamp
8.9

Adjustments, to avoid flame - detachment, at burner - ignition (only for gas oil)

This inconvenience can occur, when the temperature of the light
oil decreases below +8 °C.
CORRECT POSITIONING OF THE ELECTRODES
Refer to Fig. 15.
PUMP - SETTING
When the temperature of the light oil decreases below +8 °C, in-
crease the pressure to 14 bar.
COMBUSTION HEAD ADJUSTMENT
Regulate the combustion head one set-point further ahead than
indicated in the instructions.
Example: the instructions require to set the combustion-head on
set-point 3.
Instead, the setting is made on set-point 4.
FAN - AIR DAMPER ADJUSTMENT
Adjust the damper, reducing the excess air until the Bacharach
number is not near 1.
(i.e. a combustion with the lowest possible excess-air).
Start-up, calibration and operation of the burner
~ 12s
4 ± 0.3 mm
D5230
Lock-out due to failure to light
~ 12s
19
GB
A
2 - 2.3 mm
~ 5s
Fig. 15
D5229
Fig. 16
2903210

Advertisement

Table of Contents
loading

This manual is also suitable for:

3745964

Table of Contents