Samsung AM140RNPDKH Series Installation Manual page 31

Table of Contents

Advertisement

(*3)
Heater operation when the SEG9 of 02 series installation option is set to using hot water heater or when SEG15 is set to
using external heater
heating thermostat is on, and turned off when the heating thermostat is off.
Room temp. ≤ set temp. + f(heating compensation temp.)
- External heater is turned on when the temperature is maintained as 4.5 °C for 10 minutes.
Room temp. > set temp. + f(heating compensation temp.)
- External heater is turned off when the temperature is maintained as 4.5 °C + 1 °C (1 °C is the Hysteresis for On/
Off selection.]
Additional information on SEG 3, 4, 5, 6, 8, 9
When the SEG 3 is set as "1" and follow AutoChangeOver for HR only operation, it will operate as below.
Temp.
Ts
Set temp. for Auto mode
❋ Cooling/Heating mode can be changed when Thermo Off status is maintained during the time with SEG9.
Standard temp. for
Heating
Cooling
b
Standard temp. for Cooling
d
Standard temp. for
Cooling
Heating
ENGLISH-31
c
B
A
a
Standard temp. for Heating
A : Set with SEG4(˚C)
B : Set with SEG5(˚C)
C : Set with SEG6(˚C)
D : Set with SEG8(˚C)
C
D