Download Print this page

Siemens SICAM A8000 Series Quick Start Manual page 4

Hide thumbs Also See for SICAM A8000 Series:

Advertisement

Available languages

Available languages

Commissioning
• Check the adherence of the specified limit values.
• Connect the desired devices. Cabinet-internal wiring is preferably carried out with plastic-
insulated cables according to IEC 60364-5-52. Types: H05V-K, H05V2-K (0.5 to 1 mm²)
or H07V-K, H07V2-K (1.5 to 2.5 mm²). Use only copper wires.
• Connect the desired type of Ethernet interfaces to the RJ45 plugs.
• Connect the desired type of antenna cable to the antenna plug.
• For the operation of the master module CP-8021/CP-8022 an external power supply
module (PS-8620, PS-8622, PS-8640 or PS-8642) is required (for details on the power
supply modules see corresponding product information).
Note:
For the operation of the master module CP-8021/CP-8022, firmware CPC80 as of
version 16.40 or higher is required.
Technical Data
Power supply
Operating voltage
Supply for external modem via X2
(CP-8021, or CP-8022 with
deactivated internal LTE/GPRS
modem)
Supply for external modem via X2
(CP-8022 with activated internal
LTE/GPRS modem)
Mechanics and connectors
Protection type acc. IEC 60529
Protection class acc. IEC 61140
Rated impulse voltage
Ethernet/LAN
X1, X4
serial RS-232
X2
serial RS-485
X3
serial RS-232/RS-485
X6
(only CP-8022)
LTE/GPRS
X7
(only CP-8022)
Climatic ambient conditions
Operation temperature
Temperature gradient
Relative air humidity
Air pressure
Temperature for storage/transport
Pollution degree
CP-8021 / CP-8022 Product Information
C53207-A5063-C481-7B-7483 / DC8-021-2.09; Edition 03.2023
Input DC 5 V:
DC 4.75 to 5.5 V
1.6 W (CP-8021)
1.7 W (CP-8022)
Input DC 28 V:
DC 25.2 to 30.8 V
3.5 W (CP-8021)
with external modem
6 W (CP-8022)
with external modem
De-energized (for reset of modem)
DC 5.2 V
± 5 %
2.5 W
DC 12 V
± 5 %
2.5 W
De-energized (for reset of modem)
DC 5.2 V
± 5 %
0.75 W
IP 20
III
2 kV (the electrical insulation rating of 2 kVp is
provided solely for connection to SELV circuits)
RJ45 connector 8-pole (IEC 60603-7)
Auto-MDI(X)
Line length max. 100 m
RJ45 connector 8-pole (IEC 60603-7)
Galvanically not insulated
Data rate max. 115.2 kbit/s
Line length < 2.5 m (cabinet-internal)
Push-in terminal 8-pole (without shield clamping)
2
Max. cable cross section 1.5 mm
Data rate max. 115.2 kbit/s
Push-in terminal 8-pole (without shield clamping)
2
Max. cable cross section 1.5 mm
Data rate max. 115.2 kbit/s
SMA connector
EGSM/GPRS/EDGE 900/1800 MHz
WCDMA B1, B8
LTE FDD B1, B3, B7, B8, B20, B28
Permitted antenna gain:
GSM 900 MHz ≤ 6 dBi
DCS 1800 MHz ≤ 11 dBi
WCDMA B8 ≤ 8.90 dBi
WCDMA B1 ≤ 12.30 dBi
LTE FDD B1 ≤ 12.30 dBi
LTE FDD B3 ≤ 12.30 dBi
LTE FDD B7 ≤ 13 dBi
LTE FDD B8 ≤ 9.40 dBi
LTE FDD B20 ≤ 9.20 dBi
LTE FDD B28 ≤ 9.30 dBi
-40 to +70 °C
≤ 30 °C/h
5 to 95 % (condensation not permissible)
70 to 106 kPa (up to 3000 m)
-30 to +85 °C
2
CP-8021 Master Module / CP-8022 Master Module (LTE/GPRS)
Block Diagram and Pin Assignment
Pins on Connectors X3 and X6
(View from rear)
SICAM A8000 Series
4

Advertisement

loading

This manual is also suitable for:

Sicam cp-8021Sicam cp-8022