• When cooling, heat exchanger of non-operating indoor unit frosts.
• When heating, non-operating indoor unit gets warm.
Check of LEV
Turn ON the power supply to the outdoor unit after
checking LEV coil is mounted to the LEV body securely.
Is "click - click" sound heard?
Or, do you feel vibration of LEV coil with your hand?
No
Disconnect the LEV connectors.
Is there normal resistance to LEV coil?
(Refer to 12-5.)
No
Replace LEV coil.
*1
LEV
LEV
MXZ-2F
Connector
CN724
LEV A
CN725
LEV B
CN791
LEV A
CN792
LEV B
CN793
LEV C
CN794
LEV D
CN795
LEV E
CN796
LEV F
CN797
LEV R
OBH790H
*
1
MXZ-4F72
MXZ-3F
MXZ-4F83VF
MXZ-4F80VF
169
Connector
MXZ-2F
CN724
Inverter P.C. board
CN725
CN791
CN792
CN793
CN794
CN795
CN796
CN797
Yes
Yes
MXZ-5F
MXZ-6F
MXZ-3F, 4F, 5F,6F
2F53/4F83VFHZ
Outdoor control
P.C. board
Normal
Replace the outdoor
control P.C. board.
MXZ-
MXZ-
2F53VFHZ
4F83VFHZ