800-DI14
digital input module
Expansion module for the UMG 801
(as of firmware 1.5.0)
User manual and technical data

Advertisement

Table of Contents
loading

Summary of Contents for janitza 800-DI14

  • Page 1 800-DI14 digital input module Expansion module for the UMG 801 (as of firmware 1.5.0) User manual and technical data Janitza electronics GmbH Vor dem Polstück 6 D-35633 Lahnau Support tel. +49 6441 9642-22 Email: info@janitza.com www.janitza.com...
  • Page 2 800-DI14 module www.janitza.de Digital input module 800-DI14 for the UMG 801 (as of firmware 1.5.0) Doc. no.: 2.053.097.0.a Date: 06/2023 The German version is the original version of the documentation...
  • Page 3 Nonetheless, we wish to point out that updates of this document are not always possible at the same time as technical refinements are implemented in our products. Please see our website under www.janitza.de for the current version. Please see our website under www.janitza.de for the current version.
  • Page 4: Table Of Contents

    Hazards when handling the device, components and modules Electrically qualified personnel Warranty in the event of damage Safety information for handling current transformers 3. Product description 800-DI14 digital input module Incoming goods inspection Intended use Overview of module functions EU/UKCA Declaration of Conformity...
  • Page 5 Web page of the UMG 801 basic device 7. Operation, display and button functions Basic device with 800-DI14 module Module-relevant menu items of the basic device with one 800-DI14 module 8. Digital input module 800-DI14 - Status messages 9. Module-relevant measuring displays (800-DI14 module only) 10.
  • Page 6 800-DI14 module www.janitza.de 13. Module replacement 13.1 Module replacement 13.2 Modules - Error cases 14. Service and maintenance 14.1 Repair 14.2 Service 14.3 Device adjustment 14.4 Calibration interval 14.5 Firmware update 14.6 Procedure in the event of a malfunction 14.7 Resetting the module to the standard factory settings 14.8...
  • Page 7 800-DI14 module...
  • Page 8: Information On The Devices And The User Manual

    We ask for your understanding for these simpli- · This user manual applies to the 800-DI14 module. fications. Separate validities and distinctions are marked. · First make sure you have read and understood the usage information accompanying the product.
  • Page 9: Defective Device/Disposal

    · When doing so, please bear the terms for transpor- tation in mind. INFORMATION Please return defective or damaged devices, modules or components to Janitza electronics GmbH in ac- cordance with the shipping instructions for air or road freight (complete with accessories). Observe special regulations for devices with built-in...
  • Page 10: Safety

    800-DI14 module www.janitza.de Safety The chapter on Safety contains information which 2.3 Product safety must be observed to ensure your personal safety The devices, components and modules reflect and avoid material damage. current engineering practice and accepted safety standards, but hazards can arise nonetheless.
  • Page 11: Hazards When Handling The Device, Components And Modules

    · Hazardous voltages can be present in all cir- material damage! cuitry parts that are connected to the power · Do not use Janitza meters, modules or compo- supply. nents for critical switching, control or protection · Protect wires, cables and devices with a suit-...
  • Page 12: Electrically Qualified Personnel

    800-DI14 module www.janitza.de 2.5 Electrically qualified personnel 2.7 Safety information for handling current transformers To avoid bodily injury and material damage, only electrically qualified personnel are permitted to work Definition of the terms current transformers/cur- on the devices and their components, modules,...
  • Page 13 800-DI14 module CAUTION Risk of injury or damage to the meter due to high measurement currents at the connections of the current transformers! High measuring currents can cause temperatures of up to 80 °C (176 °F) at the connections of the current transformers/current sensors.
  • Page 14: Product Description

    The UMG 801 basic device detects an input signal at the digital input of the 800-DI14 module when: Exercise due caution when unpacking and packing · A voltage of at least 18 V and at most 28 V DC the device, do not use force and only use suitable (typically at 4 mA) is present.
  • Page 15: Intended Use

    28 V DC (typically at 4 mA) or I = min. 0.5 mA and part B - Unintentional Radiators. max. 6 mA. 3.7 Transformers It is not permitted to use the outputs of Janitza measurement devices, components and modules for switching protective devices or protective relays! Use only "Current transformers for measuring purposes"...
  • Page 16: Scope Of Delivery

    DIN (12 languages) rails. For the operation of the devices, components Tab. Scope of delivery for 800-DI14 digital input module and modules integrated in your meter and module topology, please refer to the respective additional INFORMATION usage information.
  • Page 17 800-DI14 module...
  • Page 18: Mounting

    Observe the mounting instructions for your basic device (e.g. check the bus connector installation!) and mount the 800-DI14 module in the de-energized system as follows: 1. Press in the bottom bolts on the rear of the module.
  • Page 19 800-DI14 module With bus connector UMG 801 Bottom bolts Internal bus connector Fig.: Side view of UMG 801 and 800-DI14 module click! 5. Then cable your module and apply voltage to the DIN rail basic device (system). Fig.: Side view of UMG 801 and 800-DI14 module...
  • Page 20 Bus connector Bus connector sockets sockets Fig. Mounting example: Front view of UMG 801 (basic device) with 800-DI14 module Error after starting the basic device with module: INFORMATION INFORMATION After installing your module, check the function of the communication between the basic device and...
  • Page 21 800-DI14 module...
  • Page 22: Connections/Controls

    800-DI14 module www.janitza.de 4.1 Connections/controls INFORMATION The digital input module is supplied with the neces- sary screw terminals and bus connectors (JanBus interface) for connection to the basic device or other modules. Item Designation Description Screw terminals, 8-pole Digital inputs (bottom of module).
  • Page 23: Module Markings - Rating Plate

    800-DI14 module Vor dem Polstück 6 35633 Lahnau / Germany 800-CON RJ45 • 5231223 0800/0001 4.2 Module markings – rating plate Made in Germany • www.janitza.com Janitza electronics GmbH DI14 Vor dem Polstück 6 35633 Lahnau / Germany 800-DI14 • 5231222 0400/0001 Made in Germany •...
  • Page 24: Installation

    UMG 801 basic device by an additional 14 digital inputs. 1 - DI8 When connected to the UMG 801 basic device, the digital inputs of your 800-DI14 module receive infor- 2 - DI9 mation from other devices with digital outputs (pulse generators).
  • Page 25: Connection Example

    2k21 2k21 Digital Digital Digital Digital Input 7 Input 7 Input 14 Input 14 2k21 2k21 2k21 2k21 Fig. Connection example of external switching contacts S1 - S7 and S8 - S14 to the digital inputs of the 800-DI14 module...
  • Page 26: Module Identification / Diagnostics On The Basic Device

    800-DI14 module www.janitza.de 5.4 Module identification / Diagnostics on the 5.4.1 Entry Identify all modules basic device · In the Diagnostics window, use buttons 2 “5” and 5 “6” to select the menu item Identify all modules INFORMATION and confirm with button 3 Enter.
  • Page 27: Entry Identify One Module

    800-DI14 module LED status of the module in operation: 5.4.2 Entry Identify one module · In the Diagnostics window, use buttons 2 “5” and 5 “6” to select the menu item Identify one module and confirm with button 3 Enter.
  • Page 28: Module Communication / Pc Connection

    (UMG 801). The PC and basic device require a fixed IP address. The basic device connected to your module or mod- ule series uses the integrated Ethernet interface for UMG 801 with 800-DI14 module communication with a PC. PC with GridVis ®...
  • Page 29: Module Communication Options

    800-DI14 module 6.4 Module communication options 6.4.2 Web page of the UMG 801 basic device 6.4.1 Module handling in the GridVis software Another option to configure modules or read out ® measured values is available via the device homep- The interface of the GridVis power grid monitoring ®...
  • Page 30: Operation, Display And Button Functions

    1st module INFORMATION nth module (up to 10 modules) · The following illustration shows module-relevant menu items of the basic device with one 800-DI14 Configuration module. A detailed presentation of the menu items can be found in the UMG 801 user manual.
  • Page 31: Digital Input Module 800-Di14 - Status Messages

    800-DI14 module Digital input module 800-DI14 - Status messages Use the 14 digital inputs of the 800-DI14 module to 1. Module 800-DI14 send information from other devices with a digital output to your basic device. Status messages of the digital inputs appear as follows on the UMG 801 basic device:...
  • Page 32: Module-Relevant Measuring Displays (800-Di14 Module Only)

    Module-relevant measuring displays (800-DI14 module only) INFORMATION The following module-relevant measuring and meter displays of the basic device with 800-DI14 module do not show a specific use case and may differ depending on the connection of your basic device with modules and the measuring environment.
  • Page 33 Module position Identify single module Duration Confirm Display "Identify one module" with module position, duration and confirm. Menu (System information) System Information 3. Module 800-DI14 Info 1/2 Menu Multifunctional channels Basic device 1. Module 800-DI14 Type 800-DI14 Digital I/O Status Configuration Serial no.
  • Page 34: Device Views

    Front view 18 mm/0.71 in Bottom view Top view View from left 26 mm/1.02 in 36 mm/1.42 in 14 mm/0.55 in 6 mm/0.24 in Rear view Communication bus connector to the 800-DI14 module Sockets for Sockets for 800-DI14 module further modules Connector for the bus connector Contacts for the UMG 801...
  • Page 35: Technical Data

    800-DI14 module 11. Technical data General Net weight (with plug-in terminals) 73 g (0.16 lb)  W = 18 mm (w = 0.71 in), H = 90 mm (h = 3.54 in), Device dimensions (without plug-in terminals) D = 76 mm (d = 2.99 in) Mounting orientation As desired TS 35/7.5 according to EN 60715 Fastening/mounting - TS 35/10 Suitable DIN rails - (35 mm / 1.38 in) TS 35/15 x 1.5...
  • Page 36 Lights "red" when initializing/starting the device and in the event of a fault. INFORMATION Detailed information on the functions and data of the basic device can be found in the usage information included with the basic device or available for download at www.janitza.de!
  • Page 37: Dismounting

    1. Disconnect the supply of power to the system! INFORMATION Secure it against being switched on! Check to be sure it is de-energized! Ground and short circuit! After dismounting the 800-DI14 module, the Grid- software deactivates the corresponding mod- Cover or block off adjacent live parts! ®...
  • Page 38 Cover or block off adjacent live parts! 3. If these measures are unsuccessful, please con- tact our support team (www.janitza.de). In the event of an error, the red LED (E) of the module blinks during operation at an interval of 0.5 s.
  • Page 39 800-DI14 module...
  • Page 40 800-DI14 module www.janitza.de 14. Service and maintenance Prior to outbound delivery, your device (component/ INFORMATION module) is subjected to various safety tests and is marked with a seal. If the device (component/mod- This user manual describes the modules and pro- ule) is opened, the safety tests must be repeated.
  • Page 41 800-DI14 module 14.8 Information on saving measured values and configuration data INFORMATION The basic device stores the following measured val- ues every 5 minutes at the latest: · S0 meter readings · Min. / max. / average values · Energy values (work values) The basic device saves configuration data...
  • Page 42 800-DI14 module www.janitza.de...
  • Page 43 800-DI14 module...
  • Page 44 Janitza electronics GmbH Vor dem Polstück 6 D-35633 Lahnau Support tel. +49 6441 9642-22 Email: info@janitza.com www.janitza.com...