Warning About Misuse; Exclusion Of Liability; Product Description; Ordering Code - schmersal SRB 207AN Operating Instructions Manual

Table of Contents

Advertisement

Operating instructions
Safety-monitoring module

1.6 Warning about misuse

In case of inadequate or improper use or manipulations of
the safety-monitoring module, personal hazards or damage
to machinery or plant components cannot be excluded.
The relevant requirements of the standards ISO 14119 and
ISO 13850 must be observed.

1.7 Exclusion of liability

We shall accept no liability for damages and malfunctions resulting from
defective mounting or failure to comply with this operating instructions
manual. The manufacturer shall accept no liability for damages
resulting from the use of unauthorised spare parts or accessories.
For safety reasons, invasive work on the device as well as arbitrary
repairs, conversions and modifications to the device are strictly
forbidden; the manufacturer shall accept no liability for damages
resulting from such invasive work, arbitrary repairs, conversions and/or
modifications to the device.
The safety-monitoring module must only be used when the enclosure is
closed, i.e. with the front cover fitted.

2. Product description

2.1 Ordering code

This operating instructions manual applies to the following types:
SRB 207AN
Only if the information described in this operating instructions
manual are realised correctly, the safety function and therefore
the compliance with the Machinery Directive is maintained.

2.2 Special versions

For special versions, which are not listed in the order code below 2.1,
these specifications apply accordingly, provided that they correspond to
the standard version.

2.3 Purpose

The safety-monitoring module for integration in safety circuits is
designed for fitting in control cabinets. It is used for the safe evaluation
of the signals of positive break position switches for safety functions or
magnetic safety sensors on sliding, hinged and removable safety guards
as well as emergency stop control devices. Up to 6 safety guards can be
monitored by means of the AES 207AN safety-monitoring module.
Design
The safety-monitoring module has a multichannel structure. It includes
safety relays with monitored positive action contacts. The NO contacts
of the relays, which are wired in series, build the enabling contacts. 6
signalling outputs signal the position of the corresponding safety guard.
The entire concept of the control system in which the safety
component is integrated, must be validated to the relevant
standards.
2

2.4 Technical data

General data:
Standards:
Climate resistance:
Mounting:
Terminal designations:
Material of the housings:
Material of the contacts:
Weight:
Start conditions:
Feedback circuit (Y/N):
Pull-in delay for automatic start:
Pull-in delay with reset button:
Drop-out delay in case of emergency stop:
Drop-out delay on "supply failure":
Mechanical data:
Connection type:
Cable section:
Connecting cable:
Tightening torque for the terminals:
With removable terminals (Y/N):
Mechanical life:
Electrical life:
Resistance to shock:
Resistance to vibrations to EN 60068-2-6:
Ambient conditions:
Ambient temperature:
Storage and transport temperature:
Protection class:
Air clearances and creepage
distances to IEC 60664-1:
EMC rating:
Electrical data:
Contact resistance in new state:
Power consumption:
Rated operating voltage U
:
e
Fuse rating for the operating voltage:
- 24 V version:
Monitored inputs:
Cross-wire detection (Y/N):
Wire breakage detection (Y/N):
Earth leakage detection (Y/N):
Number of NO contacts:
Number of NC contacts:
Cable length:
Conduction resistance:
Outputs:
Number of safety contacts:
Number of auxiliary contacts:
Number of signalling outputs:
Switching capacity of the safety contacts:
Fuse rating of the safety contacts:
Utilisation category to EN 60947-5-1:
Dimensions H × W × D:
The data specified in this manual are applicable when the
component is operated with rated operating voltage U
EN
SRB 207AN
EN 60204-1, EN 60947-5-1
ISO 13849-1, IEC 61508
EN 60068-2-78
snaps onto standard DIN rail to EN 60715
EN 60947-1
Plastic, glass-fibre reinforced
thermoplastic, ventilated
AgCdO, self-cleaning, positive drive
Automatic or start button
typ. 120 ms
typ. 20 ms / max.
Screw connection
min. 0,25 mm² / max. 2,5 mm²
rigid or flexible
10 million operations
Derating curve available on request
10 g / 11 ms
10 ... 55 Hz,
amplitude 0.35 mm
– 25 °C ... +45 °C
– 40 °C ... +85 °C
Enclosure: IP40
Terminals: IP20
Clearance: IP54
4 kV/2 (basic insulation)
to EMC Directive
max. 100 mΩ
max. 3.6 W / 6.6 VA
24 VDC –15% / +20%,
residual ripple max. 10%
F1: internal electronic trip,
tripping current > 1 A; reset after
disconnection of the supply voltage
1,500 m with 1.5 mm²,
2,500 m with 2.5 mm²
13-14 / 23-24:
max. 250 V, 6 A ohmic (inductive in case of
appropriate protective wiring)
6.3 A slow blow
AC-15: 230 V / 6 A
DC-13: 24 V / 6 A
100 mm × 45 mm × 121 mm
±0%.
e
300 g
yes
typ. 30 ms
35 ms
On request
0.6 Nm
yes
Yes
Yes
Yes
1 ... 6 St.
1 ... 6 St.
max. 40 Ω
2
1
6