ACH550-UH User's Manual
ACH550-UH-
see below
-124A-4
-125A-4
-157A-4
-180A-4
-246A-4
-245A-4
-316A-4
-368A-4
-414A-4
-486A-4
-526A-4
-602A-4
-645A-4
Fuses, 500...600 volt, fuses
ACH550-xx-
see below
-02A7-6
-03A9-6
-06A1-6
-09A0-6
-011A-6
-017A-6
-022A-6
-027A-6
-032A-6
-041A-6
-052A-6
-062A-6
-077A-6
-099A-6
-125A-6
-144A-6
Emergency stop devices
The overall design of the installation must include emergency stop devices and any
other safety equipment that may be needed. Pressing STOP on the drive's control
panel does NOT:
• Generate an emergency stop of the motor.
• Separate the drive from dangerous potential.
Input Current (A)
IEC269 gG (A)
124
160
124
157
200
180
250
245
315
245
Does Not Apply
316
368
414
486
526
602
645
Input Current
A
IEC269 gG (A)
2.7
10
3.9
6.1
9
16
11
17
25
22
27
35
32
41
50
52
60
62
80
77
99
125
125
160
144
200
Input Fuses
UL Class T (A)
Bussmann Type
175
JJS-175
200
JJS-200
250
JJS-250
350
JJS-350
400
JJS-400
400
JJS-400
400
JJS-400
600
JJS-600
600
JJS-600
800
JJS-800
800
JJS-800
800
JJS-800
Mains Fuses
UL Class T (A)
Bussmann Type
10
JJS-10
15
JJS-15
25
JJS-25
40
JJS-40
50
JJS-50
60
JJS-60
80
JJS-80
100
JJS-100
150
JJS-150
175
JJS-175
200
JJS-200
1-305
Technical data