Weil-McLain SlimFit 2 Series Manual page 52

Hide thumbs Also See for SlimFit 2 Series:
Table of Contents

Advertisement

SlimFit
COMMERCIAL CONDENSING GAS
Field wiring
K. 0–10 VDC Remote MODULATION input –
tion using an external controller only works with each boiler set up
as a SINGLE boiler in the SlimFit Control setup.
1. See illustration at right and Figure 50, page 54 for details.
2. This illustration also shows how to connect TT or end switch contacts at
INPUT 2 and INPUT 3 for other uses.
3. This function can only be used with a single boiler, NOT for a boiler in a
network.
4. Note that using 0–10VDC input replaces INPUT 1 to generate a heat demand
as shown at right.
5. Remote modulation requires a 0–10VDC input signal at P15-4/5 as shown
at right.
a. The 0–10VDC input positive connection must be at terminal 6 and com-
mon connection at terminal 5.
6. Control setup:
a. Many options are available for configuring the control. The following is
a suggested setup that uses factory default settings as much as possible.
b. If DHW is required, use PRIORITY 1 to minimize setup steps.
Connect the DHW aquastat to INPUT 2 or INPUT 3 and assign the
input used to PRIORITY 1.
Verify that control settings are suitable for the application, changing
if necessary.
c. Use PRIORITY 2 for the system to be remote modulated.
The factory default settings for this priority are best suited for space
heating.
Assign INPUT 1 to the priority chosen. Accept all defaults for INPUT 1
— no changes should be necessary during the WIZARD.
After the WIZARD has been completed, go to the ASSIGN INPUTS
menu for INPUT 1. Change SOURCE to 0–10V (default setting is TT1).
See page 69 for ASSIGN INPUTS menu information.
7. Operation:
a. A heat demand is activated at 0.9VDC and turns off at 0.8VDC. 2 VDC =
20% input. 10 VDC = 100% input. These voltage settings are not adjustable.
b. OUTPUT 1 (120 VAC) is activated and deactivated as the heat demand is
turned on and off. This output is a good choice to operate the system pump.
8. NOTE: The SlimFit control can be configured to use either 0–10VDC for
target operation (see previous section) or modulation,
L. 120 VAC Power Receptacle
1. Electrical rating is 2.0 amps max at 120 VAC.
2. This receptacle can be used to plug in a condensate pump.
52
-
FIRED WATER BOILER
(SlimFit control module, left side)
— Remote modula-
Boiler Manual Series 2
(continued)
OPTIONAL
See Figure 50, page 54 for details
.
Part number 550-100-162/0815

Advertisement

Table of Contents
loading

This manual is also suitable for:

Slimfit 550Slimfit 750

Table of Contents