DS 300 HB Series � 3/3 � 40-80 kVA � DSP CONTROLLED UPS
USER MANUAL
856 Status code
Status
Description
Restart
Returning to fault
857 Status code
Status
Description
Restart
Returning to fault
858 Status code
Status
Description
Restart
Returning to fault
859 Status code
Status
Description
Restart
Returning to fault
54
Inverter warning
UPS is currently in SLAVE mode ,MASTER function transferred to another UPS
--
--
Inverter warning
In parallel system there is no MASTER communication packages ,output switch
turned on after 2 seconds MASTER mode started
--
--
Inverter warning
In parallel system there is no MASTER communication packages ,output switch
turned on after 2 seconds MASTER mode started during on bypass
--
--
Inverter alarm
In parallel system transfer the load to maintenance bypass command received
--
--