AIR CONDITIONER (SPLIT TYPE)
Installation Manual
Scan QR CODE to access installation and owner's manual on website.
https://www.toshiba-carrier.co.th/manuals/default.aspx
Manual are available in EN/FR/DE/IT/ES/PT/NL/EL/RU/TR/SV/FI/DA/NO/
PL/BG/RO/ET/LV/HR/CS/SK/SL/HU/AR.
R32
Outdoor Unit
Model name:
<Heat Pump Model>
RAV-GV1601AT8P-E1
For commercial use
English

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the RAV-GV1601AT8P-E1 and is the answer not in the manual?

Questions and answers

Summary of Contents for Toshiba RAV-GV1601AT8P-E1

  • Page 1 AIR CONDITIONER (SPLIT TYPE) Outdoor Unit Installation Manual For commercial use Model name: <Heat Pump Model> RAV-GV1601AT8P-E1 Scan QR CODE to access installation and owner’s manual on website. https://www.toshiba-carrier.co.th/manuals/default.aspx Manual are available in EN/FR/DE/IT/ES/PT/NL/EL/RU/TR/SV/FI/DA/NO/ PL/BG/RO/ET/LV/HR/CS/SK/SL/HU/AR. English...
  • Page 2: Table Of Contents

    Earthing ..........................12 Ssc (*1) Finishing ..........................12 Ssc (KVA) Model Test run ..........................12 Single system RAV-GV1601AT8P-E1 10 Annual maintenance ......................12 11 Air conditioner operating conditions .................12 12 Functions to be implemented locally .................12 13 Troubleshooting ........................15 14 Appendix ..........................15 15 Specifications ........................17...
  • Page 3 Cautions for outdoor unit installation space  Center of gravity • In the event that the outdoor unit is installed in a small space and refrigerant leaks, accumulation of highly concentrated (Unit: mm) refrigerant may cause a fire hazard. Therefore, be sure to follow the installation space instructions in the Installation Manual, and Center of gravity provide open space on at least one of the four outdoor unit sides.
  • Page 4: Accessory Parts

    – 3 – Accessory parts Installation of R32 refrigerant air conditioner Part name Qʼty Shape Usage Installation Manual Booklet For hand this directly to the customer. CAUTION R32 refrigerant air conditioner installation y This air conditioner adopts the HFC refrigerant (R32) which does not destroy ozone layer. Drain nipple Therefore, during installation work, make sure that water, dust, former refrigerant, or refrigerant oil does not enter the R32 refrigerant air conditioner cycle.
  • Page 5: Installation Conditions

    Installation conditions Tools / equipment How to use tools / equipment Bender Bending pipes Conventional tools (R410A)  Before installation Electrical wiring Refrigerant recovery y Be sure to fix the power wires and system Refrigerant recovery Conventional tools (R32 or R410A) equipment Be sure to prepare to the following items before interconnection wires with clamps so that they do not...
  • Page 6 – 5 –  Installation location  Necessary space for y When the outdoor unit is installed in an elevated <Example> position, be sure to secure its feet. installation (Unit: mm) y A location in which drain water poses any problems. Wind shield WARNING Obstacle at rear side...
  • Page 7 Obstacle in front Obstacles in both front and rear of unit  Installation of outdoor unit Set the out margin of the anchor bolt to 15 mm or less. Open above and to the right and left of the unit. Above unit is free The height of an obstacle in both the front and rear of y Before installation, check the strength and...
  • Page 8: Refrigerant Piping

    – 7 – Flaring Refrigerant piping Supplied protective bush 1. Cut the pipe with a pipe cutter. Be sure to remove burrs that may cause a gas leak.  Refrigerant Piping  Knockout of pipe cover 2. Insert a flare nut into the pipe, and then flare the pipe.
  • Page 9  Tightening of connecting part  Refrigerant pipe length Single Align the centers of the connecting pipes and fully tighten the flare nut with your Allowable pipe length (m) Height difference (Indoor-outdoor H) (m) fingers. Then fix the nut with a wrench as shown in the figure and tighten it with a Total length L Indoor unit: Upper Outdoor unit: Lower torque wrench. Half union or packed valve Flare nut Pipe diameter (mm)
  • Page 10: This Equipment Complies With Iec 61000-3-12 Provided That The Short-Circuit Power Ssc Is Greater Than Or 5 Air Purging

    – 9 – Air purging  Air purge Vacuum pump With respect to the preservation of the terrestrial As shown in the figure, connect the charge hose after  Airtight test environment, adopt “Vacuum pump” to purge air the manifold valve is closed completely. (Evacuate air in the connecting pipes) when installing ↓...
  • Page 11  Pump down process  How to open the valve Gas leak inspection Indoor unit inspection locations 1. Turn off the Air Conditioner system. Fully open the valves of the outdoor unit. (First fully Use a leak detector manufactured specially for HFC refrigerant (piping connections) 2.
  • Page 12: Electrical Work

    – 11 – Electrical work Stripping length power cord and For the air conditioner, connect a power wire with the following specifications. connecting wire Model RAV- GV1601 WARNING y Remove the panel, and you can see electric parts on 380-415 V 3N ~, 50 Hz Power supply the front side.
  • Page 13: Earthing

    Earthing Air conditioner operating conditions For proper performance, operate the air conditioner under the following temperature conditions: WARNING Cooling operation Dry bulb temp. -15°C to 46°C Be sure to connect the earth wire. (grounding work) Heating operation Wet bulb temp. -15°C to 15°C Incomplete grounding may cause an electric shock.
  • Page 14 – 13 –  Refrigerant recovery Steps taken to recover the refrigerant 1. Operate the Indoor unit in the fan mode. When recovering the refrigerant in situations such as when relocating an indoor unit or outdoor unit, the recovery 2. Check that the LED displays are placed in their initial status. If not, place them in the initial status. operation can be performed by operating the SW01 and SW02 switches on the P.C.
  • Page 15  Existing piping How to check the existing piping settings You can check whether the existing piping settings are enabled. The following settings are required when using a pipe Ø19.1 mm as the existing piping at the gas pipe side. 1.
  • Page 16: Troubleshooting

    – 15 – Troubleshooting Appendix You can perform fault diagnosis of the outdoor unit with the LEDs on the P.C. Board of the outdoor unit in addition [1] Existing piping 4. When refrigerant cannot be recovered using a to using the check codes displayed on the wired remote controller of the indoor unit. refrigerant recovery unit.
  • Page 17 Curing of pipes Existing pipes: Cannot be used. Are there scratches or dents on the existing pipes? When removing and opening the indoor or outdoor unit y Use new pipes. for a long time, cure the pipes as follows: y Otherwise rust may be generated when moisture or foreign matter due to condensation enters the pipes.
  • Page 18: Specifications

    Floor standing unit Wall mounted unit Ceiling mounted unit quantity* Model Weight (kg) Cooling Heating RAV-GV1601AT8P-E1 M (kg) Product information of ecodesign requirements, (Regulation (EU) 2016/2281) 2.200 41.530 4.614 3.089 http://ecodesign.toshiba-airconditioning.eu/en * Total refrigerant quantity: Refrigerant quantity pre-charged at factory...
  • Page 19: Declaration Of Conformity

    PL6 7DB, United Kingdom Hereby declares that the machinery described below: Hereby declares that the machinery described below: Generic Denomination: Air Conditioner Generic Denomination: Air Conditioner Model / type: RAV-GV1601AT8P-E1 Model / type: RAV-GV1601AT8P-E1 Commercial name: Digital Inverter Series Air Conditioner Commercial name:...
  • Page 20: Warnings On Refrigerant Leakage

    – 19 – Warnings on refrigerant leakage  To Fix the Fluorinated Fill in the label as follows: Greenhouse Gases Label Refrigerant Label Check of concentration limit This product contains fluorinated greenhouse gases. The room in which the air conditioner is to be installed requires a design that in the event of refrigerant Contains fluorinated greenhouse Do not vent gases into the atmosphere.