7.2 INSTALLATION PLACE PROVISION

● Secure the outdoor unit with the anchor bolts.
● Fix the outdoor unit to the anchor bolts by field-supplied
special washer.
● When installing the outdoor unit, fix the unit by anchor
bolts. Regarding the location of fixing holes
12.5
223
75
● Example of fixing outdoor unit by anchor bolts.
A
is diff
● When installing the unit on a roof or a veranda, drain
water may turn to ice in a cold morning. Therefore,
avoid draining in an area where people often use
because it is slippery.
In case of installing in such a place, provide the
additional drainage around the foundation.
Drain Hole
Drain Hole 4× 24
Special Washer
Rubber Mat
Anchor Bolt
Concrete
653
225
12.5
Anchor bolt
1100
27 32.4
205
205
● The whole of the base of the outdoor unit should be
installed on a foundation. When using vibration-proof
mat, it should also be positioned in the same way. When
installing the outdoor unit on a field-supplied frame,
use metal plates to adjust the frame width for stable
installation as shown in figure.
Outdoor unit is
unstable
Unit:mm
Outdoor unit
is stable
Recommended metal plate size (field-supplied
- Material: Hot-rolled mild steel plate (SPHC)
- Plate thickness: 4.5T
Unit:mm
108
11
GENERAL DIMENSIONS
INCORRECT
75mm
Base width of
outdoor unit
Frame
75mm
Frame width
(field supplied)
CORRECT
75mm
Base width of
outdoor unit
Frame
100mm or more

Hide quick links: