A0220 Point Sensor ....................14 5. ORDERING INFORMATION ..................15 6. WARRANTY ........................15 7. PERFORMANCE TEST ....................15 APPENDIX A D0920 REVISION HISTORY ............... 17 LIST OF FIGURES D0920 Arc Detection Unit ....................5 A0220 Point Sensor ....................... 5 D0920 Outline and Mounting Details ................
The D0920 requires a 230 Vac supply and supports up to three point sensors (A0220) mounted in a switchboard. On the occurrence of an arc fault, the D0920 detects the fault and pulses the trip output in less than 1 ms. The fast trip time reduces the risk of personal injury and equipment damage.
2.1.1 Sensor Adjust The D0920 sensitivity default is 6 mA of sensor output current to cause a trip. This is equivalent to a light intensity of 12,000 lux on a single sensor or 6,000 lux on each of two sensors. This means that the total light intensity on all sensors installed has to exceed 12,000 lux to cause a trip.
INSTALLATION 3.1 D0920 Arc-Detection Unit Outline and connection details are shown in Fig. 3. The D0920 can be DIN-rail mounted only. A typical wiring diagram is shown in Fig. 4. Connect supply voltage to terminals 5 (L1) and 6 (L2/N). The nominal supply voltage is 230 Vac.
Trip the D0920 by moving a light source close to a point sensor. When a trip occurs, the red TRIPPED LED will be on. Relay K1 (terminals 9 and 10) will be closed when the D0920 has tripped.