Address Setting - Toshiba MMY-MAP0806HT8P-ME Installation Manual

Hide thumbs Also See for MMY-MAP0806HT8P-ME:
Table of Contents

Advertisement

Screw size and tightening torque
Power supply terminal
Earth screw
◆ Communication wire connection
Get the communication wire through the cutout on the side of the electrical control box and connect it to the
communication wire terminals, then fix it with the communication cable clamp.
U1
U2
S
U3 U4
TO
TO
INDOOR
SHIELD
CENTRAL
UNIT
CONTROLLER
Screw size and tightening torque
Communication wire terminal
43-EN
1117101401-3_EN.indd 22
1117101401-3_EN.indd 22
Tightening torque
Screw size
(N•m)
M6
2.5 to 3.0
M8
5.5 to 6.6
U5 U6
S
TO
OUTDOOR
SHIELD
UNIT
U
, U
: Communication wiring between outdoor units
5
6
U
, U
: Central control device
3
4
S: Shield wire earth
U
, U
: Communication wiring between Indoor/Outdoor unit
1
2
Tightening torque
Screw size
(N•m)
M4
1.2 to 1.4
9

Address setting

On this unit, it is required to set the addresses of the indoor units before starting air conditioning.
Set the addresses following the steps below.
CAUTION
• Be sure to complete the electric wiring before setting the addresses.
• If you turn on the outdoor unit before turning on the indoor units, the CODE No. [E19] is indicated on the 7-
segment display on the interface P.C. board of the outdoor unit until the indoor units are turned on. This is not a
malfunction.
• It may take up to ten minutes (normally about fi ve minutes) to address one refrigerant line automatically.
• Settings on the outdoor unit are required for automatic addressing. (Address setting is not started simply by
turning on the power.)
• Running the unit is not required for address setting.
• The addresses can be set manually.
Automatic addressing:
setting addresses using SW15 on the interface P.C. board on the header outdoor unit
Manual addressing:
setting addresses on the wired remote controller.
* When setting an address manually, the wired remote controller must temporarily be
paired with an indoor unit one-to-one. (when the system is organized for group
operation and no Remote controller)
REQUIREMENT
• High voltage parts exist in the electrical control box.
If you set addresses on an outdoor unit, operate the
unit through the access door shown on the illustration
on the right to avoid electric shock. Do not remove the
cover of electrical control box.
* After fi nishing operations, close the access door cover
and fi x it with the screw.
■ Automatic address setting
No central control:
Central control of 2 or more refrigerant lines:
When controlling a single refrigerant line
(Example)
centrally
Address setting
To procedure 1
procedure
Central
Outdoor
Outdoor
remote
controller
System wiring
Indoor
Indoor
diagram
Remote
Remote
controller
controller
controller
– 22 –
Cover of the electrical
Access
control box
door cover
Fixing screw for the
access door cover
go to Address setting procedure 1
go to Address setting procedure 2
When controlling 2 or more refrigerant lines
centrally
To procedure 2
Central
Outdoor
Outdoor
remote
controller
Indoor
Indoor
Indoor
Indoor
Indoor
Remote
Remote
Remote
Remote
controller
controller
controller
Central
remote
controller
Indoor
44-EN
1/12/16 3:18 PM
1/12/16 3:18 PM