System
HP
8HP
8HP
10HP
10HP
12HP
12HP
14HP
14HP
16HP
16HP
18HP
10HP
20HP
10HP
22HP
12HP
24HP
12HP
High-efficiency model
26HP
14HP
28HP
14HP
30HP
16HP
32HP
16HP
34HP
12HP
36HP
12HP
38HP
14HP
40HP
14HP
42HP
16HP
44HP
16HP
Table 2
Additional refrigerant charge amount Indoor unit
Additional refrigerant charge amount
Table 3
Pipe dia. at liquid side
mm
Additional refrigerant amount/1m
kg/m
Charging of refrigerant
• Keeping the valve of the outdoor unit closed, be sure to charge the liquid refrigerant into the service port at the
liquid side.
• If the specifi ed amount of refrigerant cannot be charged, fully open the valves of the outdoor unit at liquid and
gas sides, operate the air conditioner in COOL mode, and then charge refrigerant into service port at the gas
side. In this time, choke the refrigerant slightly by operating the valve of the canister to charge liquid refrigerant.
• The liquid refrigerant may be charged suddenly, therefore be sure to charge refrigerant gradually.
33-EN
1117101401-3_EN.indd 17
1117101401-3_EN.indd 17
Compensation by
Combination
Charged refrigerant
System HP
HP
kg
11.5
11.5
11.5
11.5
11.5
8HP
23
10HP
23
10HP
23
12HP
23
12HP
23
14HP
23
14HP
23
16HP
23
12HP
10HP
34.5
12HP
12HP
34.5
12HP
12HP
34.5
14HP
12HP
34.5
14HP
12HP
34.5
16HP
12HP
34.5
Air to Air Heat
Standard Indoor
Fresh Air Intake
exchanger with
unit
Indoor Unit
kg/HP
0.4
0.2
6.4
9.5
12.7
15.9
19.0
Ø
Ø
Ø
Ø
Ø
0.025
0.055
0.105
0.160
0.250
– 17 –
■ Full opening of the valve
Open the valves of the outdoor unit fully.
kg
-1.5
-1.5
MAP080
1.5
MAP100
1.5
MAP120
-5
Packed valve
-3
Using a 4mm-hexagonal wrench,
-3
fully open the valve rods.
-3
-3
0
3
3
Liquid side
3
-4.5
-4.5
-1.5
1.5
1.5
1.5
Balance packed valve
Balance pipe
Using a 4mm-hexagonal wrench, fully open the valve rods.
Balance valve
Using a wrench, turn it counterclockwise by 90° until it hits the stopper.
(Full open)
DX-coil
0.2
22.2
Ø
Gas side
0.350
MAP140
MAP10A
MAP160
MAP12A
MAP180
MAP14A
MAP200
MAP16A
Ball valve
Using a flathead screwdriver, turn it counterclockwise by 90° until it hits
the stopper. (Full open)
Position of screwdriver slot
Service
Valve unit
Fully closed
Fully opened
port
Using fl athead
screwdriver, turn it
counterclockwise by
(1)
90° until it hits the
Slot
stopper. (Full open)
(2)
* When opened fully, do not apply excessive
Flare nut
torque after the screwdriver hits the
stopper; otherwise a problem may be
caused on the valve. (5 N•m or less)
Fully closed
Fully opened