AUXILIARY POWER RECEPTACLES
Start the engine and set the "IDLER" control switch to
the "High Idle" mode. Voltage is now correct at the
receptacles for auxiliary power. This must be done
before a tripped GFCI receptacle can be reset prop-
erly. See the MAINTENANCE section for detailed
information on testing and resetting the GFCI recep-
tacle.
The auxiliary power of the RANGER® 305D consists
of two 20 Amp-120 VAC (5-20R) duplex receptacles
with GFCI protection and one 50 Amp 120/240 VAC
(14-50R) receptacle. The 240 VAC receptacle can be
split for single phase 120 VAC operation.
The auxiliary power capacity is 10,000 watts Peak,
9,500 Watts Continuous of 60 Hz, single phase
power. The auxiliary power capacity rating in watts is
equivalent to volt-amperes at unity power factor. The
max permissible current of the 240 VAC output is 40
amps. The 240 VAC output can be split to provide
two separate 120 VAC outputs with a max permissi-
ble current of 40 Amps per output to two separate
120 VAC branch circuits (these circuits cannot be
paralleled). Output voltage is within ± 10% at all loads
up to rated capacity. All auxiliary power is protected
by circuit breakers.
The 120 V auxiliary power receptacles should only be
used with three wire grounded type plugs or
approved double insulated tools with two wire plugs.
The current rating of any plug used with the system
must be at least equal to the current capacity of the
associated receptacle.
NOTE: The 240 V receptacle has two 120 V circuits,
but are of opposite polarities and cannot be paral-
leled.

STANDBY POWER CONNECTIONS

The RANGER® 305D is suitable for temporary,
standby or emergency power using the engine manu-
facturer's recommended maintenance schedule.
The RANGER® 305D can be permanently installed
as a standby power unit for 240 VAC, 3 wire, single
phase, 40 amp service. Connections must be made
by a licensed electrician who can determine how the
120/240 VAC power can be adapted to the particular
installation and comply with all applicable electrical
codes.
INSTALLATION
• Install the double-pole, double-throw switch
between the power company meter and the premis-
es disconnect. Switch rating must be the same or
greater than the customer's premises disconnect
and service over current protection.
• Take necessary steps to assure load is limited to
the capacity of the RANGER® 305D by installing a
50 amp, 240 VAC double pole circuit breaker.
Maximum rated load for each leg of the 240 VAC
auxiliary is 40 amperes. Loading above the rated
output will reduce output voltage below the allow-
able - 10% of rated voltage which may damage
appliances or other motor-driven equipment and
may result in overheating of the RANGER® 305D
engine and/or alternator windings.
• Install a 50 amp, 120/240 VAC plug (NEMA Type
14-50) to the double-pole circuit breaker using No.
6, 4 conductor cable of the desired length. (The 50
amp, 120/240 VAC plug is available in the optional
K802R plug kit or as part number T12153-9.)
• Plug this cable into the 50 Amp, 120/240 Volt recep-
tacle on the RANGER® 305D case front.