High Altitude Information - Lennox Allied Air Enterprises A95DF2V Installation Instructions Manual

Warm air gas furnace/downflow air discharge direct vent & non-direct vent
Table of Contents

Advertisement

A95DF2E
Gas
95G2DFE
Natural
All Models
Lp/Propane
Proper Combustion
Furnace should operate minimum 15 minutes with correct
manifold pressure and gas flow rate before checking
combustion. Take combustion sample beyond the flue outlet
and compare to the tables below. The maximum carbon
monoxide reading should not exceed 100 ppm.
CO
% for Nat
A96DF2V
2
95G2DFV
Low Fire
045
5.6 - 6.6
070
5.5 - 6.5
090
5.9 - 6.9
110
6.3 - 7.3
The maximum carbon monoxide reading should not exceed 100 ppm.
Conversion Kit Fan Pressure Switch Requirements at Varying Altitudes
A95DF2E
95G2DFE
045
070
090
110
*Conversion requires installation of a gas valve manifold spring which is provided with the gas conversion kit.
Pressure switch is factory set. No adjustment necessary. All models use the factory-installed pressure switch from 0-4500 feet (0-1371 m).
Page 48 of 58
Manifold and Supply Line Pressures Altitudes
0 - 4500 ft.
4501 - 5500 ft.
Low
High
Low
Fire
Fire
Fire
1.7
3.5
1.6
4.9
10.0
4.6
CO
% for L.P.
2
High Fire
Low Fire
High Fire
7.8 - 8.8
6.6 - 7.6
9.1 - 10.1
7.3 - 8.3
6.5 - 7.5
8.6 - 9.6
7.8 - 8.8
6.9 - 7.9
9.1 - 10.1
8.2 - 9.2
7.3 - 8.3
9.5 - 10.5
Table 16
High Altitude
Natural to LP/
Natural Burner
Propane
0 - 7500 ft
7501 - 10000 ft
(0 - 2286m)
(2286 - 3048m)
11K48
Manifold Pressure in w.g.
5501 - 6500ft.
High
Low
High
Fire
Fire
Fire
3.3
1.5
3.2
9.4
4.4
9.1
Table 15

High Altitude Information

NOTE: In Canada, certification for installations at elevations
over 4500 feet (1371 m) is the jurisdiction of local authorities.
Units may be installed at altitudes up to 10,000 ft. above
sea level without manifold adjustment. Units installed
at altitude of 4501 - 10,000 feet (1371 to 3048 m) may
require a pressure switch change which can be ordered
separately. Table 17 lists conversion kit and pressure switch
requirements at varying altitudes.
The combustion air pressure switch is factory-set and
requires no adjustment.
NOTE: A natural to LP/propane gas changeover kit is
necessary to convert this unit. Refer to the changeover kit
installation instruction for the conversion procedure.
High Altitude
LP/Propane Burner
Orifice Kit
Orifice Kit
7501 - 10000 ft
(2286 - 3048m)
*51W01
11K47
Table 17
Issue 1621
6501 - 7500ft.
7501-10000ft.
Low
High
Low
Fire
Fire
Fire
1.5
3.1
1.7
4.3
8.9
4.9
High Altitude Pressure switch
4501 - 7500 ft
(1371 - 2286m)
14A47
14A55
14A54
14A46
Supply Line
Pressure in
w.g.
0 - 10000 ft.
High
Min.
Max.
Fire
3.5
4.5
13.0
10.0
11.0
13.0
7501 - 10000 ft
(2286 - 3048m)
14A50
14A56
14A53
14A51
507052-04

Advertisement

Table of Contents
loading