Water-cooled liquid chiller for indoor installation (65 pages)
Summary of Contents for CLIVET WSAT-XSC3 FC 90.4
Page 1
Installation and operating manual WSAT-XSC3 FC 90.4 - 240.4 High efficiency air cooled water chiller for outdoor installation M08Z40G15-02 07-08-18...
Index of contents General description Reception Positioning Water connections Electrical connections Start-up Control Maintenance Accessories Decommissioning Residual risks Technical information Dimensional drawings WSAT-XSC3 FC 90.4 - 240.4...
Contact a certified service agent. Use original spares parts only. Using the unit in case of breakdown or malfunction: • voids the warranty • it may compromise the safety of the unit • may increase time and repair costs WSAT-XSC3 FC 90.4 - 240.4...
Page 5
1.14 Assistance request Note data from the serial number label and write them in the chart on side, so you will find them easily when needed. Series Size Serial number Year of manufacture Electrical wiringdiagram WSAT-XSC3 FC 90.4 - 240.4...
Align the barycenter to the lifting point Use all the lifting brackets (see the dimensional section) Gradually bring the lifting belts under tension, making sure they are positioned correctly. 10. Before starting the handling, make sure that the unit is stable. WSAT-XSC3 FC 90.4 - 240.4...
Page 7
Keep packing material out of children’s reach it may be dangerous. Recycle and dispose of the packaging material in conformity with local regulations. Supports for handling: remove after the handling. Remove the coil protective mesh before the start-up WSAT-XSC3 FC 90.4 - 240.4...
HIGH PRESSURE (in summer) or LOW PRESSURE (in winter) 3.3 Saftey valve gas side The installer is responsible for evaluating the opportunity of installing drain tubes, in conformity with the local regulations in force (EN 378). WSAT-XSC3 FC 90.4 - 240.4...
Page 9
3.4 AxiTop 3.5 Anti-vibration mount support For details see: 9 Accessories p. 50 WSAT-XSC3 FC 90.4 - 240.4...
For details see: Technical Bulletin, “Considerations on the installation” section 4.5 Minimum system water content Minimum system water volumes are described within ‘General technical data’ section and they have to be satisfied to avoid continuous compressor switching on and off. WSAT-XSC3 FC 90.4 - 240.4...
Page 11
Use filter with mesh pitch: 1,6 mm It must be installed immediately in the water input of the unit, in a position that is easily accessible for cleaning. The filter never should be removed, this operation invalidates the guaranty. WSAT-XSC3 FC 90.4 - 240.4...
Page 12
Leave various point of service free (wells, vent-holes etc). Neglecting the washing will lead to several filter cleaning interventions and at worst cases can cause damages to the exchangers and the other parts. 4.11 hydronic assembly For details see: 9 Accessories p. 50 WSAT-XSC3 FC 90.4 - 240.4...
Guarantee the continuity of the screen during the entire extension of the cable. Respect impendency, capacity and attenuation indications. 5.4 Power input Fix the cables: if vacated may be subject to tearing. The cable must not touch the compressor and the refrigerant piping (they reach high temparatures). WSAT-XSC3 FC 90.4 - 240.4...
Page 14
Flow Switch alarm signal lamp electrical heater electrical panel selector 5.7 Remote ON-OFF Do not perform short On Off cycles Do not use the remote On Off with thermoregulation function. Y E S N O ! WSAT-XSC3 FC 90.4 - 240.4...
Page 15
12. write and run the command Ping 192.168.1.42 13. the message, connection is OK, will appear when successful 14. enter the browser (Crhome, Firefox ecc) 15. write and run the command http:/192.168.1.42 16. Userid = WEB 17. Password = SBTAdmin! WSAT-XSC3 FC 90.4 - 240.4...
Page 16
KNX bus, max 350 mt twisted pair with shield, ø 0,8 mm EIB/KNX cable marking recommende PSX - Mains power supply unit pwer supply unit N125/11 5WG1 125-1AB11 AC 120...230V, 50...60Hz KNX bus, max 350 mt WSAT-XSC3 FC 90.4 - 240.4...
Page 17
• The cable must have insulation features and non-flame propagation in accordance with applicable regulations. • The RS485 serial line must be kept as far away as possible from sources of electromagnetic interference. WSAT-XSC3 FC 90.4 - 240.4...
Page 18
LED BUS communication with BACnet green communication ok green ready for communication yellow software ok but communication with AP1 yellow startup down flashing: software error BACnet server down fixed: hardware error restart after 3 sec WSAT-XSC3 FC 90.4 - 240.4...
10. measure return and supply water temperature 11. measure super-heating and sub-cooling 12. check no anomalous vibrations are present 13. climatic curve personalization 14. climatic curve personalization 15. scheduling personalization 16. complete and available unit documentation WSAT-XSC3 FC 90.4 - 240.4...
Page 20
Free-cooling ( 4 ) Compressors ( 3 ) Fans AE > TW in AE = TW in -2°C AE < TW in -2°C AE << TW in -2°C TW out = setpoint cool AE <<< TW in -2°C WSAT-XSC3 FC 90.4 - 240.4...
Page 21
AE > TW in – 2°C AE = TW in – 2°C AE < TW in – 2°C AE << TW in – 2°C TW out = setpoint cool AE <<< TW in – 2°C WSAT-XSC3 FC 90.4 - 240.4...
Page 22
2 to point 8 until no more air comes out from vents 10. put under pressure the free-cooling hydraulic circuit: use the external pump or city water After 2 / 3 days of free-cooling operation repeat the procedure from point 2 to point 10. WSAT-XSC3 FC 90.4 - 240.4...
Page 23
Check that the remote controls (ON-OFF etc) are connected and, if necessary, enabled with the respective parameters as indicated in the “electrical connections” section. Check that probes and optional components are connected and enabled with the respective parameters (“electrical connections” section and following pages). WSAT-XSC3 FC 90.4 - 240.4...
Page 24
Demand limit Demand limit Confirm Press 3 sec. Select Local connections Path: Main Menu / Unit parameters / Demand limit Parameters Short description Description P0200 setpointdemandlimit Parameter setting of the value % of demand limit WSAT-XSC3 FC 90.4 - 240.4...
Page 25
AirAtSptHigH P0613 AirAtSptHigH external air temperature value where the calculated setpoint takes on the value given by HSptHigh P0606 / P0609: Coooling P0610 / P0613: Heating WSAT-XSC3 FC 90.4 - 240.4...
Page 26
Value of the WR control signal corresponding to the correction of the set Heating equal to P0615 P0620 SWRMinH Value of the WR control signal corresponding to the correction of the set Heating equal to 0 P0616 / P0618: Cooling P0615, P0619, P0620: Heating WSAT-XSC3 FC 90.4 - 240.4...
Page 27
There must be suitable arresters to protect the serial lines from the effects of atmospheric discharges • The data line must be kept separate from the power conductors or powered at different voltage values and away from possible sources of electrical interference WSAT-XSC3 FC 90.4 - 240.4...
Page 28
Temperature Offset the master sum or subtract, depending on the way you set, in order of priority, to the set point of P0657 LNOffset the slave P0658 TypeRegMS Operation mode: 0=mode A; 1=mode B; 2=mode C P0659 LNAddress ProcessBus address unit WSAT-XSC3 FC 90.4 - 240.4...
Page 29
The above-described operating conditions must be considered outside the operating limits. In the event of compressor breakdown, due to operating in the above-mentioned conditions, the guarantee will not be valid and Clivet spa declines any responsibility.
Page 30
(for ex. Condensing circuit + direct expansion unit) Certification of setting in service: • for all the units Periodical verifications: • to be executed with the frequency indicated by the Manufacturer (see the “maintenance inspections” paragraph) WSAT-XSC3 FC 90.4 - 240.4...
Page 31
1 = 1 compr. On circuit 2 = 0 compr. On Heating capacity 7.3 Keys Symbol Name Description Info Main menu Alarm Alarm display Exit Cancel Previous level Keyboard settings Increases value Down Decreases value Confirm Enter Password WSAT-XSC3 FC 90.4 - 240.4...
Page 32
Enable by remote switch P0855 SetPointECOCooling Economic summer SetPoint P0577 SetPointHeating Setpoint Heat P0578 2SetPointHeating 2° Setpoint Heat P0579 SetPointECOHeating Economic winter SetPoint P0640 SetPointRecover Recovery Set Point P0580 ACSSetPoint domestic hot water set point WSAT-XSC3 FC 90.4 - 240.4...
Page 33
Option config P0052=1 Press 3 sec. Select Local connections * Unit Parameters menu is displayed 7.8 Display the status Step Display Action Menu/Variable Keys Notes Press Main menu Select Machine State Select General, circuit, ecc.. Exit WSAT-XSC3 FC 90.4 - 240.4...
Page 37
Alarm list detail Press 3 sec. Password Enter password Alarm list detail Press Alarm list Select Alarm Reset Select Executed Press 3 sec. Password management Select Log off For details see: General list of alarms WSAT-XSC3 FC 90.4 - 240.4...
Page 40
Inverter 1 communication timeout Inverter APY ee2040 Alarm Inverter 2 Inverter 2 in alarm Inverter APY ee2041 Alarm missing comunication inv2 Inverter 2 Modbus communication error Inverter APY ee2042 Timeout comunication inv2 Inverter 2 communication timeout Inverter APY WSAT-XSC3 FC 90.4 - 240.4...
Page 41
Vacuum Circuit Vaacum Alarm Circuit 1 FF1046 LimLp Low pressure limit Circuit 1 ff1047 DFRForced Defrost Forced Circuit 1 ff1048 DFRWaterTLow Low water temperature for defrost operation Circuit 1 ff1049 DFRTimeMax Defrost Maximum Time Circuit 1 WSAT-XSC3 FC 90.4 - 240.4...
Page 42
Source Low Pressure Plant Source low water pressure Sorgente 2 iI2020 Source Low H2O Flow Source side low water flow Sorgente 2 II2021 Source H2O Freeze Alarm Source side water frost protection Sorgente 2 WSAT-XSC3 FC 90.4 - 240.4...
Page 43
* Refer to the local regulations; and ensure correct adherance. Companies and technicians that effect interventions of installation, maintenance/re- pairs, leak control and recovery must be CERTIFIED as expected by the local regulations. The leak control must be effected with annual renewal. WSAT-XSC3 FC 90.4 - 240.4...
Page 44
Verify that the aluminum fins are not bent or damaged, in the event of damages contact the authorized assistance center and get the fins straightened in order to restore the initial condition for an optimal air flow. WSAT-XSC3 FC 90.4 - 240.4...
Page 45
• remove incrustations from the palette 8.12 Compressor supply line shut-off valve A. Supply line shut-off valve Do not remove the seal Remove only if authorized by the manufacturer. Please contact the maker for informations. WSAT-XSC3 FC 90.4 - 240.4...
Page 46
It’s recommended that the re-start after the stopping period is performed by a qualified technician, especially after seasonal stops or seasonal switching. When restarting, refer to what is indicated in the “start-up” section. Schedule technical assistance in advance to avoid hitches and to guarantee that the system can be used when required. WSAT-XSC3 FC 90.4 - 240.4...
Page 47
8.16 Compressor replacement WSAT-XSC3 FC 90.4 - 240.4...
Page 54
IFWX Steel mesh strainer on the water side Cutoff valve Differential pressure switch Steel mesh strainer Temperature probe Pressure gauge TWin Water inlet Safety valve (6 Bar) TW out Water outlet Electric pump WSAT-XSC3 FC 90.4 - 240.4...
Page 55
IFWX Steel mesh strainer on the water side Cutoff valve Differential pressure switch Steel mesh strainer Temperature probe Pressure gauge TWin Water inlet Safety valve (6 Bar) TW out Water outlet Electric pump WSAT-XSC3 FC 90.4 - 240.4...
Page 56
When machine components to be replaced for maintenance purposes are removed or when the entire unit reaches the end of its life and needs to be removed from the installation, waste should be separated by its nature and disposed of by authorised personnel at existing collection centres. WSAT-XSC3 FC 90.4 - 240.4...
Page 57
Do not remain in the vicinity of the safety valve and never leave the refriger- ating system taps closed. WSAT-XSC3 FC 90.4 - 240.4...
Page 58
4. Data compliant to Standard AHRI 550/590 referred to the following conditions: internal exchanger water temperature = 6,7 °C. Water flow-rate 0,043 l/s per kW. Entering external exchanger air temperature 35°C. Evaporator fouling factor = 0.18 x 10^(-4) m K/W. WSAT-XSC3 FC 90.4 - 240.4...
Page 59
If unit is set without Axitop, the sound power level presents an increase up to 3 dB(A). 200.4 220.4 Data referred to the following conditions. - internal exchanger water = 12/7 °C 240.4 - ambient temperature = 35 °C WSAT-XSC3 FC 90.4 - 240.4...
Page 60
‘Operating range - cooling ‘ graph in the “Super-silenced EN” configuration. With outdoor air temperatures the unit operates at full load automatically increasing the airflow and taking the same sound levels of the “Soundproofed 240.4 Compressors SC” configuration. WSAT-XSC3 FC 90.4 - 240.4...
Page 61
Unit operating range in ‘B - Low water temperature’ configuration (40% ethylene glycol) Extended of operating range (extremely low water temperature option available on request) Unit operating range as “Unit equipment with outdoor air low temperatures” table WSAT-XSC3 FC 90.4 - 240.4...
Page 62
High compressor discharge temperature safety thermostat [°C] Exchanger operating range Internal exchanger PED (CE) 4500 4500 1000 DPr = Maximum operating pressure on refrigerant side in kPa DPw = Maximum operating pressure on water side in kPa WSAT-XSC3 FC 90.4 - 240.4...
Page 63
4650 Container shipping depth 2315 2315 2315 2315 2315 2315 2315 2315 The presence of optional accessories may result in a substantial variation of the weights shown in the table. Fan diffusers are separately supplied WSAT-XSC3 FC 90.4 - 240.4...
Page 64
2315 2315 2315 2315 2315 2315 2315 2315 2315 2315 2315 2315 The presence of optional accessories may result in a substantial variation of the weights shown in the table. Fan diffusers are separately supplied. WSAT-XSC3 FC 90.4 - 240.4...
Page 65
2315 2315 2315 2315 2315 2315 2315 2315 2315 2315 2315 2315 The presence of optional accessories may result in a substantial variation of the weights shown in the table. Fan diffusers are separately supplied.. WSAT-XSC3 FC 90.4 - 240.4...
Page 66
7548 7548 7548 Container shipping depth 2315 2315 2315 2315 2315 2315 The presence of optional accessories may result in a substantial variation of the weights shown in the table. Fan diffusers are separately supplied WSAT-XSC3 FC 90.4 - 240.4...
Need help?
Do you have a question about the WSAT-XSC3 FC 90.4 and is the answer not in the manual?
Questions and answers