4.17 Motor connection at 208-230 or 460V only for RLS 300/EV

WARNING :
the motors, manufactured for 208-230/460V IE2/Epact voltage, have a different connection than IE1 motors, no more star/delta but
star/double star.
Please, pay attention to the indications in case of modification of voltage, maintenance, or substitution.
IE1
~ ~ ~
460V

4.18 Motor connection at 575V only for RLS 300/EV

WARNING :
the motors, manufactured for 575V IE2/Epact voltage, have the same control box base of the IE1 motors.
Please pay attention to the indications in case of maintenance or substitution.

4.19 Reversible direction

WARNING :
If it is necessary to reverse the direction then reverse the two main supply phases.
For example: L1 with L2, there is not difference between IE1 and IE2/Epact
20037164
D3686
~ ~ ~
208-230V
L1
L2
VKDIW