13.4. Changing blower external static pressure

The air handler is equipped with an adjustable static pressure
setting. The available settings are shown in the table below.
Model
Available ESP [in. WG]
PVFY-P12
0.30
PVFY-P18
0.30
PVFY-P24
0.30
PVFY-P30
0.30
PVFY-P36
0.30
PVFY-P42
0.30
PVFY-P48
0.30
PVFY-P54
0.30
*PVFY-P36 in Downfl ow External Static pressure: 0.60
**PVFY-P54 in Downfl ow External Static pressure: 0.70
The air handler will be set to 0.50 ESP from the factory.
The blower static pressure setting can be changed by changing the
dip switches SWA & SWC. Vertical, Horizontal Right, and Horizontal
Left Switch C will always be in the "1" position. When the air handler
is installed in the Downfl ow position, Switch C needs to be in the "2"
position.
24
0.50
0.80
0.50
0.80
0.50
0.80
0.50
0.80
0.50
0.80*
0.50
0.80
0.50
0.80
0.50
0.80**
External Static Pressure
0.3 in. WG
(75 Pa)
0.5 in. WG
(125 Pa)
(Factory Setting)
0.8 in. WG
(200 Pa)
Vertical,
Horizontal Right,
Horizontal Left
(Factory Setting)
Downflow
Switch A
3
2
1
3
2
1
3
2
1
Switch C
1
2
1
2