Setpoint Minimum
RoHS Compliance
BAS-SVU040G-EN
Occupied/
• Cooling: 60°F to 85°F (15.5°C to 29.4°C)
Unoccupied
• Heating: 55°F to 80°F (12.7°C to 26.6°C)
Setpoint Range
Heating/Cooling
2°F to 5°F (1.0°C to 2.5°C)
Deadband
Power Supply
24 Vdc / 24 Vac (19 - 30 Vac), 50 / 60 Hz, Class 2
18 AWG or Larger
Power Wire
Power
4 VA
Consumption
• Polycarbonate/ABS blend
• UV protected
Housing
• U.L. 94–5VA flammability rating
• Suitable for application in a plenum
Weight
0.75 lb. (0.34 kg)
Mounting
3.24 in (8.26 cm) for 2 mounting screws (supplied)
• 22 AWG or Larger
• Two conductor shielded twisted pair with drain wire
• Characteristic impedance between 100 and 130 ohms
Communication
• Capacitance between conductors, less than 100 pF per meter (30 pF
Wire
per foot)
• Capacitance between conductors and shield, less than 200 pF meter
(60 pF per foot)
• LVD Directive 2006/95/EC
Safety Standards
• EN60950–a: 2006/A2:2013
• U.L. 873 CSA C22.2 No. 24–93
• EMC Directive 2004/108/EC
• IEC 61326–1: 2005
EMC Standards
• FCC 15 Subpart B, Class A
• ICES-003
Enclosure and components are RoHS compliant (RoHS 2002/95/EC)