seconds to stop.
T indicates alarm 1 on due to high ambient temperature (setting 51). Useful for summer ventilation.

Default Settings

User settings are factory pre-loaded with default values to facilitate set up and can be changed at any time. Upgrading firmware will not
affect user settings.
Alarm thresholds should be set to suit local regulations. Default values for these are general guidelines only.
Changing Settings
Press → and ← to move through the settings. If the keypad lock is on then enter the password first. The screen will display the setting number
0, 1, 2, etc. plus the short description (e.g. AL1 for Alarm 1 and the current setting.)
Press the ↑ or ↓ buttons to increase or decrease the setting.
To save, press ↑ and ← buttons at the same time. The word "OK" will appear. If you do not see "OK" and the new value it is because the
buttons were not pressed simultaneously. Try again.
List of Settings Sensor A (upper socket) Settings
NO.
Name
Description
0
AL1
Alarm 1 threshold, activates relay 1
1
A1Del
Alarm 1 Delay on (seconds)
2
A1Off
Alarm 1 Delay off (seconds)
3
AL2
Alarm 2 threshold, activates relay 2
4
A2Del
Alarm 2 Delay on (seconds)
5
A2Off
Alarm 2 Delay off (seconds)
6
AL3
Alarm 3 threshold, sounder and strobe
7
A3Del
Alarm 3 Delay on (seconds)
8
A3Off
Alarm 3 Delay off (seconds)
9
A1Tx
Alarm 1 transmit message, CAN network
10
A1Tx
Alarm 1 transmit message, CAN network
1 1
A1Tx
Alarm 1 transmit message, CAN network
12
A2Tx
Alarm 2 transmit message, CAN network
13
A2Tx
Alarm 2 transmit message, CAN network
14
A2Tx
Alarm 2 transmit message, CAN network
15
A3Tx
Alarm 3 transmit message, CAN network
16
A3Tx
Alarm 3 transmit message, CAN network
17
A3Tx
Alarm 3 transmit message, CAN network
List of Settings Sensor B (lower socket) Settings
NO.
Name
Description
18
AL1-B
Alarm 1 threshold, activates relay 1
19
A1Del
Alarm 1 Delay on (seconds)
20
A1Off
Alarm 1 Delay off (seconds)
21
AL2-B
Alarm 2 threshold, activates relay 2
22
A2Del
Alarm 2 Delay on (seconds)
23
A2Off
Alarm 2 Delay off (seconds)
24
AL3-B
Alarm 3 threshold, sounder and strobe
25
A3Del
Alarm 3 Delay on (seconds)
26
A3Off
Alarm 3 Delay off (seconds)
27
A1x,A1Tx
Alarm 1 transmit message, CAN network
Range
by sensor
0-999
0-999
by sensor
0-999
0-999
by sensor
0-999
0-999
0-255
0-255
0-255
0-255
0-255
0-255
0-255
0-255
0-255
Range
by sensor
0-999
0-999
by sensor
0-999
0-999
by sensor
0-999
0-999
0-255
Default
30
20
30
20
180
20
1
2
3
Default
30
20
30
20
180
20
1

Advertisement