Model 6002 and 6002-14B Installation, Operation, and Maintenance Manual Gas Detectors READ AND SAVE THESE INSTRUCTIONS The purpose of this manual is to aid in the proper installation and operation of fans manufactured by Soler & Palau USA. These instructions are intended to supplement good general practices and are not intended to cover detailed instruction procedures, because of the wide variety and types of fans manufactured by Soler &...
6002 and 6002-14B offer precision to assure the health and safety to occupants with the tightest possible controls on energy consumption. They are versatile, self-contained dual gas sensors that are network ready for either peer-to-peer (master slave) operation or central control for a smooth integration into new or existing energy management systems.
Installation Guidelines Important. All wiring must conform to local building codes, regulations and laws. If the equipment is used in a manner not specified by the manufacturer, the protection provided by the equipment may be impaired. Use ½ inch EMT conduit for all wiring. 2.
Coverage Guidelines for sensor placement of diffusion type sensors are based on the reasonable delay for gas to get from the source to the sensor. All sensors are created equal in this regard. • For air quality control of exhaust emissions and accumulations of toxic gases the generally acceptable maximum radius of coverage is 50 feet (15 meters).
T indicates alarm 1 on due to high ambient temperature (setting 51). Useful for summer ventilation. Default Settings User settings are factory pre-loaded with default values to facilitate set up and can be changed at any time. Upgrading firmware will not affect user settings.
Page 7
Name Description Range Default A2Tx Alarm 2 transmit message, CAN network 0-255 A2Tx Alarm 2 transmit message, CAN network 0-255 BiTx Binary input transmit message, CAN network 0-255 A3Tx Alarm 3 transmit message, CAN network 0-255 A3Tx Alarm 3 transmit message, CAN network 0-255 A3Tx Alarm 3 transmit message, CAN network...
AMaxB Analog drive. Maximum percent of scale for full scale output. Sensor B 0-100 ADRxB Receive message code to control local 0-255 Analog output B Baud Baud rate for CAN network Maximum network wire length is 1500 feet at rate 0 and 3000 feet at rate 1.
Network Configuration Using CAN Network with No central controller (master/slave operation) One of the 60XX series gas sensors can be used as the controller. It can activate the ventilation for all the sensors, or a group. The use of a dedicated controller is optional, - to add a display in some specific location, such as before entering a mechanical room or to interface with several fan starters located in one place.
Page 10
Calibration Procedure Use certified precision mixtures to adjust the sensitivity of the sensor due to normal wear and aging and guarantee that the designed alarm set points are respected. It will also indicate the general condition of a sensor that is due for replacement. So called “automatic calibration” or “self-test”...
Ventilation Controlled by BACnet Building Automation Object Table Type and Instance Object Name Object Property Parameter AV 0 gas reading 1 Present value (R) Gas reading local sensor A AV 1 gas reading 2 Present value (R) Gas reading local sensor B AV 2 Ambient temperature Present value (R)
Page 12
The foregoing shall constitute our sole and exclusive warranty and our sole and exclusive liability and is in lieu of all other warranties, whether written, oral, implied or statutory. There are no warranties which extend beyond the description of the page hereof. Seller does not warrant that said goods and articles are of merchantable quality or that they are fit for any particular purpose.