Ebyte MA01-AXCX4020 User Manual
Ebyte MA01-AXCX4020 User Manual

Ebyte MA01-AXCX4020 User Manual

Wireless modem
Hide thumbs Also See for MA01-AXCX4020:

Advertisement

Quick Links

【4DI + 2DO】
MA01-AXCX4020

Advertisement

Table of Contents
loading

Summary of Contents for Ebyte MA01-AXCX4020

  • Page 1 【4DI + 2DO】 MA01-AXCX4020...
  • Page 2: Table Of Contents

    EBYTE is strictly prohibited............2 The information contained herein is provided “as is” and EBYTE assumes no liability for the use of the information. No warranty, either express or implied, is given, including but not limited, with respect to the accuracy, correctness, reliability and fitness for a particular purpose of the information.
  • Page 3: Disclaimer

    EBYTE is strictly prohibited. The information contained herein is provided “as is” and EBYTE assumes no liability for the use of the information. No warranty, either express or implied, is given, including but not limited, with respect to the accuracy, correctness, reliability and fitness for a particular purpose of the information.
  • Page 4: Overview

    【4DI+2DO】MA01-AXCX4020 User Manual 1 Overview MA01-AXCX4020 supports the acquisition of 4-channel sensor switch input (DI), which is converted to serial port (RS485) and data is transmitted to configuration software or PLC. The serial port I/O networking module (also known as "remote IO") that controls 2 relay switch outputs (DO) by issuing commands through the serial port to realize remote acquisition and control functions.
  • Page 5: Quick Start

    Screwdriver (Slot SL 2) Signal generator (or sensor) 2.2 Wiring 2.2.1 Power wiring 1.Power supply, using DC 8-28V power supply, can also use DC 12V or 24V power supply. Chart 2-2-1 Wiring Copyright ©2012–2023, Chengdu Ebyte Electronic Technology Co., Ltd.
  • Page 6 (2) Switch input DI wiring, connect the control button to the switch input DI port as shown in the figure. (3) Switch output DO wiring, connect the load to the switch output DO port as shown in the figure. Copyright ©2012–2023, Chengdu Ebyte Electronic Technology Co., Ltd.
  • Page 7: Setting

    Figure 2-3-1 Software interface Steps: 1. Open the serial port, find the corresponding device port number, the baud rate defaults to 9600, and click "open serial port". 2-3-2 open the serial port Copyright ©2012–2023, Chengdu Ebyte Electronic Technology Co., Ltd.
  • Page 8 After the connected device is displayed in the device column of the device window, click the "Stop Searching" menu. Then select the device and click, the connection is successful. 2-3-3 get connected to the device 2.3.2 Testing 2-3-4 testing 2-3-5 Actual test results Copyright ©2012–2023, Chengdu Ebyte Electronic Technology Co., Ltd.
  • Page 9: Parameters

    2 way 2 way 4 way ● × 2DI+2AI+4DO MA02-AACX2240 2 way 2 way 4 way ● × MA01-XXCX0080 8 way ● — — × MA02-XXCX0080 8 way ● — — × Copyright ©2012–2023, Chengdu Ebyte Electronic Technology Co., Ltd.
  • Page 10: Parameters Of Ma01-Axcx4020

    80g ± 5g Working -40 ~ +85℃, 5%~95%RH Others temperature and (non-condensing) humidity Storage temperature -60 ~ +125℃, 5%~95%RH and humidity (non-condensing) Installation method Installation of guide rail and locating hole Copyright ©2012–2023, Chengdu Ebyte Electronic Technology Co., Ltd.
  • Page 11: Port Description

    Switch input channel 1 Switch input channel 2 Switch input channel 3 Switch input channel 4 Switch output channel 1 The relay has normally open and normally closed terminals Switch output channel 2 3.4 Size Copyright ©2012–2023, Chengdu Ebyte Electronic Technology Co., Ltd.
  • Page 12: Installation

    Chengdu Ebyte Electronic Technology Co., Ltd. 【4DI+2DO】MA01-AXCX4020 User Manual Chart 3-4-1 dimensioned drawing 3.5 Installation The equipment is installed with guide rail and positioning hole. Chart 3-5-1 Guide rail installation Copyright ©2012–2023, Chengdu Ebyte Electronic Technology Co., Ltd.
  • Page 13: Detailed Function

    When the switch inputs the DI to collect the signal, it needs to keep multiple sampling periods before confirming. The filter parameter can be set from 1 to 16 (default 6 sampling periods). The DI filter parameters can be set through the configuration software. Copyright ©2012–2023, Chengdu Ebyte Electronic Technology Co., Ltd.
  • Page 14: Switch Output Do

    When the LED indicator light is on, it means the relay is closed (normally open and normally closed); When the LED indicator is off, it means that the relay is not closed (normally open off, normally closed on). 4-2-1 Switch output DO interface Copyright ©2012–2023, Chengdu Ebyte Electronic Technology Co., Ltd.
  • Page 15: Device Address

    Software address: It is realized by the "offset address" set by the configuration tool software (the factory default is 1). For example: If the hardware address is set to 5 and the software address is set to 113, the device address is 118. Copyright ©2012–2023, Chengdu Ebyte Electronic Technology Co., Ltd.
  • Page 16 0 to 31. Hardware address dialing setting instructions: Example 1: Set hardware address 0 (default), binary code. Hardware address 0 4-3-3 Example 2: Set the hardware address to 8, binary code. Copyright ©2012–2023, Chengdu Ebyte Electronic Technology Co., Ltd.
  • Page 17 After changing the address, you need to power off and restart the new address to take effect. To change the software address, it needs to be realized through the configuration tool software, as shown in the figure: Figure 4-3-7 Software address (offset address) Copyright ©2012–2023, Chengdu Ebyte Electronic Technology Co., Ltd.
  • Page 18: Port Wiring

    【4DI+2DO】MA01-AXCX4020 User Manual 5 Port wiring 5.1 Switch input DI port wiring 5.1.1 Two-wire switch wiring Figure 5-1-1 Wiring diagram of two-wire switch 5.1.2 Three-wire switch wiring Figure 5-1-2 Wiring diagram of three-wire switch Copyright ©2012–2023, Chengdu Ebyte Electronic Technology Co., Ltd.
  • Page 19: Switch Output Do Port Wiring

    Figure 5-1-3 Three-wire sensor wiring diagram 5.2 Switch output DO port wiring 5.2.1 The output terminal directly controls the load (small power equipment within 1kW) Figure 5-2-1 The output terminal directly controls the load wiring diagram Copyright ©2012–2023, Chengdu Ebyte Electronic Technology Co., Ltd.
  • Page 20 Figure 5-2-3 Wiring diagram of output terminal control contactor Remarks: The above figure takes the contactor coil voltage AC 220V as an example. The coil voltage of different contactors may be different. Copyright ©2012–2023, Chengdu Ebyte Electronic Technology Co., Ltd.
  • Page 21: Software Use

    6.1 Software Installation The configuration tool software is driver-free installation, directly double-click the .exe file to open it and use it. Figure 6-1-1 Software installation file Figure 6-1-2 Successful software installation opens the interface Copyright ©2012–2023, Chengdu Ebyte Electronic Technology Co., Ltd.
  • Page 22: Software Function Introduction

    Figure 6-2-2 Device window interface (2) Serial port parameter window etc.), and open the Display the serial port parameter information (port, baud rate, data bit, parity bit, stop bit, serial port. Copyright ©2012–2023, Chengdu Ebyte Electronic Technology Co., Ltd.
  • Page 23 Figure 6-2-4 Log window interface (4) Switch input DI [This function is limited to devices that support DI] Display the status of the digital input DI port. Figure 6-2-4 Switch input DI interface Copyright ©2012–2023, Chengdu Ebyte Electronic Technology Co., Ltd.
  • Page 24 Figure 6-2-6 Analog input AI interface (7) Refresh settings Support manual refresh, automatic refresh status. The automatic refresh state can customize the refresh cycle (the custom cycle is a multiple of 500ms). Figure 6-2-7 Refresh setting interface Copyright ©2012–2023, Chengdu Ebyte Electronic Technology Co., Ltd.
  • Page 25 Set the DI function. Set filter parameters (1 ~ 16), trigger mode (rising edge, falling edge, level), and clearing method (automatic, manual). [This function is limited to devices that support DI] Figure 6-2-10 "DI related" interface Copyright ©2012–2023, Chengdu Ebyte Electronic Technology Co., Ltd.
  • Page 26 The advanced setting interface supports device name setting, offset address (software address), read parameters, open write protection, close write protection, restart the module, and restore factory settings. Figure 6-2-13 Device setting interface Copyright ©2012–2023, Chengdu Ebyte Electronic Technology Co., Ltd.
  • Page 27: Device Status Query

    "Refresh All Data" menu. Example: The configuration software has connected 2 devices, try to query and select one of the devices, and click the "Refresh All Data" menu to complete the device status query. Copyright ©2012–2023, Chengdu Ebyte Electronic Technology Co., Ltd.
  • Page 28 Chengdu Ebyte Electronic Technology Co., Ltd. 【4DI+2DO】MA01-AXCX4020 User Manual (1) IO demo interface Figure 6-3-1 Device status query (IO demo interface) (2) Basic setting interface Figure 6-3-2 Device status query (basic setting interface) Copyright ©2012–2023, Chengdu Ebyte Electronic Technology Co., Ltd.
  • Page 29: Equipment Status Control

    Device status control, the device supports ModBus standard command control. It also supports configuration software graphical control. Example: To control the device, open the DO-1 output port. Method 1: Software graphical operation, click the menu button to control. Figure 6-4-1 Software graphical operation Copyright ©2012–2023, Chengdu Ebyte Electronic Technology Co., Ltd.
  • Page 30 Device address: 1 Function: open DO-1 output Sending: 01 05 00 00 FF 00 8C 3A (including CRC check bit) Return: 01 05 00 00 FF 00 8C 3A (including CRC check bit) Copyright ©2012–2023, Chengdu Ebyte Electronic Technology Co., Ltd.
  • Page 31: Modbus

    DO pulse width 0x03、 0x06、 0x10 duration of the pulse, in ms. 0x0000-0x0002, 0x0000 means rising edge count, (41318)0x0526 DI counting method 0x03、 0x06、 0x10 0x0001 means falling edge count, 0x0002 means level Copyright ©2012–2023, Chengdu Ebyte Electronic Technology Co., Ltd.
  • Page 32 Write 5BB5, the device will (42026)0x07EA Restore default parameters 0x03、 0x06、 0x10 restart immediately See the baud rate code table, (42100)0x0834 Device restart the default value is 0003, 0x03、 0x06、 0x10 which is 9600. Copyright ©2012–2023, Chengdu Ebyte Electronic Technology Co., Ltd.
  • Page 33: Instruction Format (Partial)

    After sending the above command to the device via the 485 bus, the device will return the following values: 00 00 XX XX Device ModBus function code Number of bytes of data Returned data CRC check code address The above 00 00 indicates that DO1 is in level mode. Copyright ©2012–2023, Chengdu Ebyte Electronic Technology Co., Ltd.
  • Page 34 0x0002, 0x0003, and 0x0000, respectively. 7.2.5 Write the status of a single DO coil Use 05 command to write a single command, for example: set the working mode of DO1 to pulse mode Copyright ©2012–2023, Chengdu Ebyte Electronic Technology Co., Ltd.
  • Page 35 After sending the above command to the device via the 485 bus, the device will return the following values: 00 00 OO O4 XX XX Device ModBus function CRC check Register address Number of coils address code code The coils of DO2 and DO3 are turned on. Copyright ©2012–2023, Chengdu Ebyte Electronic Technology Co., Ltd.
  • Page 36: Revised History

    2023-3-13 Content Revisions About us Technical support: support@cdebyte.com Documents and RF Setting download link: https://www.cdebyte.com Thank you for using Ebyte products! Please contact us with any questions or suggestions: info@cdebyte.com ------------------------------------------------------------------------------------------------- Phone: +86 028-61399028 Web: https://www.cdebyte.com Address: B5 Mould Park, 199# Xiqu Ave, High-tech District, Sichuan, China...