Daikin RXYQ72XATJ Operation Manual page 17

Vrv system air conditioner
Table of Contents

Advertisement

Available languages

Available languages

• Table 1 "Inspection Cycle" and "Maintenance Cycle" Lists
Name of Main Part
Compressor
Electric motor (fan, damper, etc.)
PC boards
Heat exchanger
Sensor (thermistor, etc.)
Remote controller and switches
Drain pan
Expansion valve
Electromagnetic valve
FAN
Note 1
This table indicates main parts.
See the maintenance and inspection contract for details.
Note 2
This maintenance cycle indicates recommended lengths of time until the need arises for maintenance work, in order to ensure
the product is operational as long as possible.
Use for appropriate maintenance design (budgeting maintenance and inspection fees, etc.).
Depending on the content of the maintenance and inspection contract, the inspection and maintenance cycles may in reality be shorter than those listed here.
Shortening of "maintenance cycle" and "replacement cycle" needs to be considered in the following cases.
1. When used in hot, humid locations or locations where temperature and humidity fluctuate greatly.
2. When used in locations where power fluctuation (voltage, frequency, wave distortion, etc.) is high.
(Cannot be used if it is outside the allowable range.)
3. When installed and used in locations where bumps and vibrations are frequent.
4. When used in bad locations where dust, salt, harmful gas or oil mist such as sulfurous acid and hydrogen sulfide may be present in the air.
5. When used in locations where the machine is started and stopped frequently or operation time is long. (Example: 24 hour air-conditioning)
„Recommended replacement cycle of wear-out parts
[The cycle is not the same as the warranty period.]
• Table 2 "Replacement Cycle" Lists
Name of Main Part
Air filter
High efficiency filter (Optional accessory)
Fuse
Crankcase heater
Note 1
This table indicates main parts.
See the maintenance and inspection contract for details.
Note 2
This maintenance cycle indicates recommended lengths of time until the need arises for maintenance work, in order to ensure
the product is operational as long as possible.
Use for appropriate maintenance design (budgeting maintenance and inspection fees, etc.).
Contact your local dealer for details.
Note: Breakage due to taking apart or cleaning inside by anyone other than our authorized dealers may not be included in the warranty.
„Moving and discarding the unit
• This unit uses hydrofluorocarbon.
Contact your local dealer for discarding this unit since it is required by law to collect, transport and discard the refrigerant in accordance with
"hydrofluorocarbon collection and destruction" law.
„Where to call
For after-sales service, etc., consult with your local dealer.
3P571721-2
English
Inspection Cycle
Maintenance Cycle [replacements and/or repairs]
20,000 hours
20,000 hours
25,000 hours
5 years
5 years
1 year
25,000 hours
8 years
20,000 hours
20,000 hours
Outside : 10 years
Indoor : 13 years
Inspection Cycle
Replacement Cycle
5 years
1 year
1 year
10 years
8 years
13

Advertisement

Table of Contents
loading

Table of Contents